background image

6

Cassette Base Installation

It is important to locate the cassette unit in the center of 

the area that is being conditioned. This will provide the 

best air distribution.
1.  If the unit is to be installed in an application that 

includes a drop-down tile ceiling, remove the ceiling 

tiles necessary to accommodate installation of the 

four-way cassette. Before removing the drop ceiling 

support grid, use a plumb line or laser device to  

identify the center point of the structural ceiling. 

Make 

sure that the ceiling is supported before removing 

any of the support grid. It may be necessary to add 

extra  support to maintain the structural integrity 

of the drop ceiling.

2.  If the unit is to be installed in an application that 

includes  a  sheet  rock  (plasterboard)  ceiling,  the 

installation site must be carefully measured and the 

sheet rock must be cut to accommodate the cassette 

unit. First, identify the center point of the installed 

cassette. Use a plumb line to transfer the center mark 

to the floor for future use. Use the provided template 

to mark the area of the required opening. Carefully cut 

the required opening.  

Make sure that the removal 

of  the  required  ceiling  support  does  not  affect 

the structural integrity of the ceiling. It may be 

necessary to add extra support.

3.  Use the unit as a template or use the provided paper 

template to mark the location of the hanging brackets 

on the floor. Use a plumb line or a laser to transfer the 

bracket positions to the main structural ceiling.

4.  Make sure that structure within ceiling void 

such  as  a  sub-floor  or  crawl  space  is  able 

to support the weight of the cassette unit. 

It may be necessary to add extra support. 

 

If the structural support is constructed of 

concrete,  install  anchors  to  accept  four  ⅜” 

threaded rods to suspend the cassette  base. 

 

If the structural support includes wooden joists, 

use  angle  iron  or  a  Unistrut  channel  fixed 

securely  in  place  to  accept  the  ⅜”  threaded  rods. 

 

NOTE - 

Threaded rod (requirement of Lennox 

warranty program) is the ONLY acceptable method of 

suspending the unit; do not use chains or straps. 

 See 

Figure 1.

5.  Use either a mechanical lifting device or a minimum 

of two people to raise the unit and insert the threaded 

rods into the suspension brackets on the cassette 

base. Slide a washer and then a nut onto each rod 

below each suspension bracket. Use the leveling nut 

(beneath suspension bracket) to adjust the cassette 

base to the correct height. Remove the electrical 

tape holding the upper washers and nuts in place 

and tighten each of the four nuts above the brackets 

down onto the brackets. This will ensure that the unit 

remains level.

Figure 1. Suspending Methods

ANGLE IRON

BOLTED IN

PLACE ACROSS

WOODEN JOISTS

WOODEN JOIST

⅜”  THREADE

D

ROD

ANGLE IRON

ACROSS

WOODEN JOISTS

ANCHOR

CONCRETE CEILING

USING ANCHORS

⅜”  THREADE

D

ROD

L

⅜”

 to

 ½

UNIT CHASSIS

DROP CEILING

LEVELING NUT

⅜” THREADE

D

ROD

SUSPENSION

BRACKET

STRUCTURAL

SUPPORT

Figure 2. Suspension Hardware

6.  If the unit is being installed in an application that includes 

a sheet rock (plasterboard) ceiling, it is required that 

an access panel be installed in a suitable location.  

This will also allow access for future maintenance 

(requirement of Lennox warranty program).

7.  Access is required during the commissioning process 

to test the condensate disposal system (See Figure 

9),  to  check  the  electronic  expansion  valve  and 

associated flare nuts (See Figure 3), and to check the 

local disconnect. Ceiling framing should not restrict 

access.

Summary of Contents for VRF V33B Series

Page 1: ...ce can cause property damage personal injury or loss of life Installation and service must be performed by a li censed professional HVAC installer service agency or the gas supplier Failure to follow...

Page 2: ...s are similar in appearance but must not be connected to a Lennox VRF refrigerant circuit Please refer to model numbers to confirm compatibility Model numbers for Lennox VRF units start with a V and m...

Page 3: ...ID PIPE 1 3 4 44 SIDE VIEW 34 5 8 879 Ceiling Opening AIR OUTLET AIR INLET AIR OUTLET LEVELING ADJUSTMENT NUT 4 INSTALLATION HANGERS 4 DIFFUSER PANEL CEILING DRAIN PIPE BOTTOM PANEL VIEW SIDE VIEW LIQ...

Page 4: ...p Ceiling 10 1 4 inches 260 mm 007 009 012 015 models 13 inches 330 mm 015 018 024 030 036 048 models Minimum Clearance to Floor 90 inches 2286 mm Maximum Clearance to Floor 160 inches 4064 mm Minimum...

Page 5: ...ord line radio telephone security system or intercom Electrical interference and radio frequencies from any of these sources may affect operation WARNING Do not install the unit in an area where flamm...

Page 6: ...It may be necessary to add extra support If the structural support is constructed of concrete install anchors to accept four threaded rods to suspend the cassette base If the structural support includ...

Page 7: ...and discard the seal from each of the piping connections 4 Slide the flare nuts onto the ends of the field provided refrigerant piping before using a suitable flaring tool to flare the end of the cop...

Page 8: ...se an appropriately sized wrench to turn an additional Inches U S 1 4 15 ft lb 1 4 turn 3 8 26 ft lb 1 2 turn 1 2 41 ft lb 7 8 turn 5 8 48 ft lb 1 full turn Table 2 Flare Nut Torque Recommendations IM...

Page 9: ...loped no less than 1 4 inch per foot and that each individual drain is connected to the main drain exactly as shown 5 Drain should be as short as possible and should not have any droops or kinks that...

Page 10: ...a ballast The ballast may affect remote control operation 2 Locate the terminal strip in the control box Connect the power wiring sized per NEC CEC and local codes and communications cable per Figure...

Page 11: ...tdoor Unit Main Unit L1 L2 L3 Outdoor Unit Sub1 unit L1 L2 L3 Outdoor Unit Sub2 Unit L1 L2 L3 L1 L2 L3 L1 L2 L3 L1 L2 L3 L1 L2 L3 L1 L2 L3 L1 L2 L3 Service Disconnect Service Disconnect Service Discon...

Page 12: ...olarity sensitive Typical Wiring Diagram NEC CEC and Local Codes apply Outdoor unit Outdoor unit sub1 unit Outdoor unit sub2 unit PQ main unit PQ MS Box PQ PQ MS Box PQ PQ H1 H2 H1 H2 H1 H2 Outdoor Un...

Page 13: ...htening Torque Tightening torque lb ft Terminal base of remote controller Signal transmission wire X2M 0 58 0 72 Terminal base of power supply X1M 0 87 1 06 Grounding terminal M4 1 06 1 43 PQ PQ Outdo...

Page 14: ...erials must be listed ANSI UL and ASTM E 84 approved NOTE A maximum of two sides can be blanked off 1 Remove the decorative cover panel if installed 2 Identify and measure the supply air opening that...

Page 15: ...15 Figure 16 Three way Outlet Possible Flow Patterns Figure 17 Two way Outlet Possible Flow Patterns Typical cassette body shown actual unit may vary...

Page 16: ...18 4 Remove any insulation 5 Connect the secondary supply duct to the cassette body using the eight screw holes shown in figure 18 6 A field supplied duct transition may be required Be sure there is a...

Page 17: ...panel See Figure 21 Figure 21 Remove Corner Covers 4 Position the ceiling panel so that the arrow on the panel is aligned with the arrow sticker on the cassette base both arrow stickers should be on...

Page 18: ...ake sure that the panel is properly aligned with the cassette base 9 Continue to tighten the cover panel securing screws until the insulation between the cover panel and the cassette base has been com...

Page 19: ...nate so that all codes are shown Make note of the code E1 EE etc then reset the display by pressing the ON OFF button on the unit controller Press the ON OFF button a second time to reapply power to u...

Page 20: ...E4 T2B Outlet of evaporator sensor malfunction E5 T2A Inlet of evaporator sensor malfunction E6 DC fan motor error E7 EEPROM failure Eb EXV malfunction Ed Outdoor unit Fault EE High Water Alarm A0 Em...

Reviews: