background image

11

Figure 10. Typical Power Wiring Diagram (VRF Heat Recovery System Shown)

L2 L3

L1

L2

L1

208/230V 3Ph 60Hz 

or 460V 3Ph 60Hz 

Power supply

208/230V 1Ph 60Hz  

Power supply

Mode Selection Box

Indoor unit

Indoor unit

Indoor unit

Dedicated 

breaker

Service 

Disconnect

L1

L2

L1 L2

Fuse

Service 

Disconnect

L1 L2

Fuse

Service 

Disconnect

L1 L2

Fuse

Service 

Disconnect

L1 L2

Fuse

Outdoor Unit (Main Unit)

L1

L2

L3

Outdoor Unit (Sub1 unit)

L1

L2

L3

Outdoor Unit(Sub2 Unit)

L1

L2

L3

L1 L2 L3

L1 L2 L3

L1 L2 L3

L1 L2 L3

L1 L2 L3

L1 L2 L3

Service 

Disconnect

Service 

Disconnect

Service 

Disconnect

Indoor units and mode selection boxes on the same 

refrigeration circuit should have a common power supply 

but must have an independent disconnect switch installed 

adjacent to each item of equipment for servicing and 

maintenance purposes. 

Indoor unit and mode selection box power supply MUST 

not be taken from the outdoor unit. Always follow NEC/

CEC and Local Codes.

Summary of Contents for VRF V33B Series

Page 1: ...ce can cause property damage personal injury or loss of life Installation and service must be performed by a li censed professional HVAC installer service agency or the gas supplier Failure to follow...

Page 2: ...s are similar in appearance but must not be connected to a Lennox VRF refrigerant circuit Please refer to model numbers to confirm compatibility Model numbers for Lennox VRF units start with a V and m...

Page 3: ...ID PIPE 1 3 4 44 SIDE VIEW 34 5 8 879 Ceiling Opening AIR OUTLET AIR INLET AIR OUTLET LEVELING ADJUSTMENT NUT 4 INSTALLATION HANGERS 4 DIFFUSER PANEL CEILING DRAIN PIPE BOTTOM PANEL VIEW SIDE VIEW LIQ...

Page 4: ...p Ceiling 10 1 4 inches 260 mm 007 009 012 015 models 13 inches 330 mm 015 018 024 030 036 048 models Minimum Clearance to Floor 90 inches 2286 mm Maximum Clearance to Floor 160 inches 4064 mm Minimum...

Page 5: ...ord line radio telephone security system or intercom Electrical interference and radio frequencies from any of these sources may affect operation WARNING Do not install the unit in an area where flamm...

Page 6: ...It may be necessary to add extra support If the structural support is constructed of concrete install anchors to accept four threaded rods to suspend the cassette base If the structural support includ...

Page 7: ...and discard the seal from each of the piping connections 4 Slide the flare nuts onto the ends of the field provided refrigerant piping before using a suitable flaring tool to flare the end of the cop...

Page 8: ...se an appropriately sized wrench to turn an additional Inches U S 1 4 15 ft lb 1 4 turn 3 8 26 ft lb 1 2 turn 1 2 41 ft lb 7 8 turn 5 8 48 ft lb 1 full turn Table 2 Flare Nut Torque Recommendations IM...

Page 9: ...loped no less than 1 4 inch per foot and that each individual drain is connected to the main drain exactly as shown 5 Drain should be as short as possible and should not have any droops or kinks that...

Page 10: ...a ballast The ballast may affect remote control operation 2 Locate the terminal strip in the control box Connect the power wiring sized per NEC CEC and local codes and communications cable per Figure...

Page 11: ...tdoor Unit Main Unit L1 L2 L3 Outdoor Unit Sub1 unit L1 L2 L3 Outdoor Unit Sub2 Unit L1 L2 L3 L1 L2 L3 L1 L2 L3 L1 L2 L3 L1 L2 L3 L1 L2 L3 L1 L2 L3 Service Disconnect Service Disconnect Service Discon...

Page 12: ...olarity sensitive Typical Wiring Diagram NEC CEC and Local Codes apply Outdoor unit Outdoor unit sub1 unit Outdoor unit sub2 unit PQ main unit PQ MS Box PQ PQ MS Box PQ PQ H1 H2 H1 H2 H1 H2 Outdoor Un...

Page 13: ...htening Torque Tightening torque lb ft Terminal base of remote controller Signal transmission wire X2M 0 58 0 72 Terminal base of power supply X1M 0 87 1 06 Grounding terminal M4 1 06 1 43 PQ PQ Outdo...

Page 14: ...erials must be listed ANSI UL and ASTM E 84 approved NOTE A maximum of two sides can be blanked off 1 Remove the decorative cover panel if installed 2 Identify and measure the supply air opening that...

Page 15: ...15 Figure 16 Three way Outlet Possible Flow Patterns Figure 17 Two way Outlet Possible Flow Patterns Typical cassette body shown actual unit may vary...

Page 16: ...18 4 Remove any insulation 5 Connect the secondary supply duct to the cassette body using the eight screw holes shown in figure 18 6 A field supplied duct transition may be required Be sure there is a...

Page 17: ...panel See Figure 21 Figure 21 Remove Corner Covers 4 Position the ceiling panel so that the arrow on the panel is aligned with the arrow sticker on the cassette base both arrow stickers should be on...

Page 18: ...ake sure that the panel is properly aligned with the cassette base 9 Continue to tighten the cover panel securing screws until the insulation between the cover panel and the cassette base has been com...

Page 19: ...nate so that all codes are shown Make note of the code E1 EE etc then reset the display by pressing the ON OFF button on the unit controller Press the ON OFF button a second time to reapply power to u...

Page 20: ...E4 T2B Outlet of evaporator sensor malfunction E5 T2A Inlet of evaporator sensor malfunction E6 DC fan motor error E7 EEPROM failure Eb EXV malfunction Ed Outdoor unit Fault EE High Water Alarm A0 Em...

Reviews: