Multi Variable Air Conditioners Cassette Type Indoor Unit

20

7 Table of Error Codes for Indoor Unit

Error 

Code

Content

Error 

Code

Content

Error 

Code

Content

L0

Indoor Unit Error

L9

Quantity Of Group Control 

Indoor Units Setting Error

d8

Water Temperature Sensor 

Error

L1

Indoor Fan Protection

LA

Indoor Units Incompatibility 

Error

d9

Jumper Cap Error

L2

E-heater Protection

LH

Low Air Quanlity Warning

dA

Indoor Unit

Hardware Address Error

L3

Water Full Protection

LC

Outdoor-Indoor Incompatibility 

Error

dH

Wired Controller PC-Board 

Error

L4

Wired Controller Power 

Supply Error

d1

Indoor Unit PC-Board Error

dC

Capacity DIP Switch Setting 

Error.

L5

Anti-Frosting Protection

d3

Ambient Temperature Sensor 

Error

dL

Outlet Air Temperature

Sensor Error

L7

No Master Indoor Unit 

Error

d4

Inlet Pipe Temperature Sensor 

Error

dE

Indoor Unit CO

2

 Sensor

Error

L8

Power Insufficiency

Protection

d6

Outlet Pipe Temperature

Sensor Error

db

Special Code: 

Field Debugging Code

8 Troubleshooting

The air conditioner is not expected to be serviced by users. Incorrect repair may cause electric 

shock or fire, so please contact an authorized service center for professional service. The following 

checks prior to contact may save your time and money. 

Phenomenon

Troubleshooting

The unit can’t start

Power supply is not connected.

Circuit breaker tripping caused by leakage of electricity.

Input voltage is too low.

Defect of main PC-board.

The unit stops after running 

for a while.

The inlet or outlet of ODU or IDU are blocked by obstacle.

Poor cooling effect

The filter is dirty.

Too heavy heat load of room(e.g. too many people)

Door or windows is open.

Inlet and outlet of IDU are blocked.

Setting temperature is too high.

Refrigerant is insufficient (e.g. refrigerant leakage)

Poor heating effect

The filter is dirty.

Door or window is open.

Setting temperature is too low.

Refrigerant is insufficient (e.g. refrigerant leakage)

Indoor fan doesn’t start 

up during heating 

At starting, the IDU fan could not operate till the heat exchange become

hot, for preventing delivering the cool air.

At defrosting, the IDU fan stopped due to system switch to cooling

mode. for preventing delivering the cool air, and resume operating after

defrosting.

Note:

If air conditioner still fails to work normally after checking and handling as described above, please 

stop using it immediately and contact local service center for assistance.

Summary of Contents for VE4C007C432P

Page 1: ...n Coil LD Low Static Fan Coil GD Large Fan Coil HS AH Air Handler OA Outside Air Evaporator Types Thank you for selecting LENNOX air conditioners Please read this manual carefully before operation and keep it for further reference K 230 60 3 and 220 50 3 N 380V 50 60Hz 3Ph G 460V 60Hz 3Ph Y 230V 60Hz 3Ph T 220V 50Hz 1Ph P 230V 60Hz 1Ph U 220V 50 60Hz 1Ph Voltage Rating V E HW 007 N 4 32 P Availabl...

Page 2: ...intainers should well keep this manual 6 If this unit fails to operate normally please contact our service center as soon as possible and provide the following information 1 Content on the nameplate model number cooling capacity production code ex factory date 2 Malfunction details before and after the malfunction occurs 7 Each unit has been strictly tested and proved to be qualified before ex fac...

Page 3: ... and Drainage System Testing 10 4 4 Panel installation 12 4 5 Wired controller installation 14 5 Wiring Work 15 5 1 Connection of Wire and Patch Board Terminal 15 5 2 Power Cord Connection 15 5 3 Connection of Communication Wire between Indoor Unit and Outdoor Unit or indoor unit 16 5 4 Connection of Communication Wire for Wired Controller 16 5 5 Illuminate for Connection of Wired Controller and I...

Page 4: ...ren operate this unit 13 Do not operate this unit with wet hands 14 Turn off the unit or cut off the power supply before cleaning the unit otherwise electric shock or injury may happen 15 Never spray or flush water towards unit otherwise malfunction or electric shock may happen 16 Do not expose the unit to the moist or corrosive circumstances 17 Under cooling mode please don t set the room tempera...

Page 5: ...le liquid such as diluent or gas will damage the unit appearance Only use soft cloth with a little neutral detergent to clean the outer casing of unit 26 If anything abnormal happens such as burning smell please power off the unit and cut off the main power supply and then immerdiately contact Lennox appointed service center If abnormality keeps going the unit might be damaged and lead to electric...

Page 6: ...9 0 7 44 6 6 42 8 Indoor Unit Working Temperature Range 16 C 60 8 F 32 C 89 6 F 2 3 Unit Functions Unit Functions Wired Controller VEWCL1B Remote Controller VERCL1A Operation Mode Cooling Heating Fan Dehumidifying Fan Speed Adjustment Temperature Adjustment X fan Function Quiet Function Sleep Function Save Function E heater Function Memory Function Absence Function Timer Function Low Temp Dehumidi...

Page 7: ...nstallation hole in the main body Installation hole in the main body Installation hole in the main body 1 Locate the drill hole on ceiling 3 Tapping screw with washer 4 Fix paper pattern 4 Washer fixing plate 4 Prevent the washer from falling off 5 Drain Hose Assembly 1 To connect with the hard PVC drain pipe 6 Special nut 1 To connect gas pipe 7 Special nut 1 To connect liquid pipe 8 M10X8 Nut wi...

Page 8: ...smog spread in the air 7 The indoor unit outdoor unit power cord and connection electricity wire should be at least 1m 39 3 8 inch from television and radio in order to prevent interference and noise Even though 1m 39 3 8 inch distance is ensure there may be noise if the electric wave is too strong Unit mm inch 1500mm 59 inch 1500mm 59inch H 20mm 3 4 inch 30 48 Ceilin Wall Model H 210 8 1 4 340 13...

Page 9: ... Circular cord the cores shall be twisted together 3 If unit is installed in places with intense magnetic field or strong interference it is necessary to use shielded wire 3 3 2 Selection of communication wire between indoor unit and indoor unit or outdoor unit Indoor Unit 1 Indoor Unit 2 Indoor Unit n Outdoor unit1 Outdoor unit 2 Outdoor unit 3 Outdoor unit 4 LO1 L LO1 LO2 LO3 Li1 Li2 Lin n 80 LO...

Page 10: ...79 0 44 NOTICE 1 An all pole disconnection switch having a contact separation of at least 3mm 1 8 inch in all poles should be connected in fixed wiring 2 The circuit breaker and power cord specification in above sheet is based on max power max current of the unit 3 The power cord specification in above sheet is based on ambient temperature of 40 104 F 4 The circuit breaker specification in above s...

Page 11: ...nd the indoor unit 1 Drill bolt holes and install bolts 1 Stick the reference cardboard on the installation position drill 4 holes according to the hole site on the cardboard as shown in fig 4 1 2 diameter of drilling hole is according to the diameter of expansion bolt and the depth is 60 70mm 2 3 8 2 3 4 inch as shown in fig 4 1 3 Paper pattern Hole diameter Drill hole according to the hole site ...

Page 12: ...rainage pipe by screws 4 Adjust the unit to the right position 5 Check the level of the unit The indoor unit is equipped with build in water pump and float switch verify the levelness of 4 directions by level gauge or vinyl tube filled with water respectively 6 Remove the washer locating plate and then tighten the nut on it 7 Remove the paper pattern fix the hoisting stand firmly hoisting stand fi...

Page 13: ...rd PVC pipe used as the drainage pipe During connection insert the end of PVC pipe into the drainage hole and then tighten it with drainage hole and wire binder Can t connect the drainage hole and drainage hole with glue 5 When the drainage pipelines are used for several units the position of pipeline should be about 100mm 4 inch lower than the drainage port of each unit In this case thicker pipes...

Page 14: ...nch 07 170 6 3 4 830 32 5 8 09 48 220 8 5 8 780 30 3 4 10 Drain pipes should have a downward slope of at least 1 2 in order to prevent pipes from sagging install hanger bracket at intervals of 1000 1500mm 39 3 8 59 inch 1000 1500mm 39 3 8 59 inch Fig 4 3 4 4 3 3 Test of Drainage System 1 Please test drainage system after electric work is finished Inject approximately 1L purified water to drain pan...

Page 15: ...e about 100mm 4 inch above 100mm 4 inch drainage pipe Fig 4 3 5 4 4 Panel installation 4 4 1 Notices for installation 1 Improper decorative panel installation could cause the following problems Condensation cause water drop dew air leakage Fig 4 4 1 2 Ensure that its clearance free between decoration panel and ceiling board after installation if not please adjust the body position There can t be g...

Page 16: ... on each corner of the panel hang the hangers to corresponding hooks on the body as shown in fig 4 4 4 3 Detach the air inlet grille from panel make a wiring connection of signal receiver Notices that the connection wire not stuck in the middle of body and panel or may cause air leakage and lead to condensation water drop 4 Tighten 4 screws at each corner of panel respectively fix the panel on the...

Page 17: ... controller is optional accessory If wired controller is needed please contact your local dealer and install the wired controller according to the instruction manual NOTICE Do perform the commissioning operation before first use automatic addressing or other settings please refer to the manual of ODU ...

Page 18: ...t the static pressure via wired controller according to site circumstance 5 1 Connection of Wire and Patch Board Terminal 1 The connection of wire as shown in fig 5 1 1 1 Strip about 25mm 1 inch insulation of the wire end by stripping and cutting tool 2 Remove the wiring screws on the terminal board 3 Shape the tail of wire into ring by needle nose plier and keep the gauge of ring in accordance wi...

Page 19: ...r unit previous IDU match resistance for communication communication interface CN12 Fig 5 3 1 Fig 5 3 2 4 Fix the communication cable with clamp of electric box 5 For more reliable communication make sure connect the terminal resistor to the most downstream IDU of the communication bus terminal D1 and D2 as shown in fig 5 3 2 terminal resistor is provided with each ODU 5 4 Connection of Communicat...

Page 20: ...1 D2 2 Wired controller is connected to H1 H2 3 One indoor unit can connect two wired controllers that must be set as master one and slave one 4 One wired controller can control 16 indoor unitS in maximum at the same time as shown in fig 5 5 NOTICE 1 The type of indoor units must be the same if they are controlled by the same wired controller 2 When the indoor unit is controlled by two wired contr...

Page 21: ...Multi Variable Air Conditioners Cassette Type Indoor Unit 18 D1 D2 H1 H2 D1 D2 H1 H2 D1 D2 H1 H2 D1 D2 H1 H2 D1 D2 H1 H2 D1 D2 H1 H2 D1 D2 H1 H2 D1 D2 H1 H2 D1 D2 D1 D2 Fig 5 5 ...

Page 22: ...DU Use a vacuum cleaner to remove dust If the filters are dirty wash them with warm water and mild detergent and dry the filters in the shade 2 If the unit used in the environment with much dust please clean it regularly usually once every two weeks 6 2 Maintenance before the Seasonal Use 1 Check if the air inlet and air outlet of indoor and outdoor unit are blocked 2 Check if securely grounded 3 ...

Page 23: ...e so please contact an authorized service center for professional service The following checks prior to contact may save your time and money Phenomenon Troubleshooting The unit can t start Power supply is not connected Circuit breaker tripping caused by leakage of electricity Input voltage is too low Defect of main PC board The unit stops after running for a while The inlet or outlet of ODU or IDU...