background image

3DJH 

SETTING THE UNIT

Refer to unit dimensions on page 2 for sizing mounting
slab, platforms or supports. Refer to figure 1 for instal-
lation clearances.

INSTALLATION CLEARANCES

FIGURE 1

36

(914 mm)

*36

(914 mm)

36

(914 mm)

NOTE—48 inch clearance required on top of unit.

*NOTE—One side must be 36 inches. Two side may be 12”.

*36

(914 mm)

Slab Mounting

When installing unit at grade level, install on a level
slab high enough above grade to allow adequate drain-
age of water. Top of slab should be located so run--off
water from higher ground will not collect around unit.

Roof Mounting

Install unit at a minimum of 4 inches above the surface

of the roof. Care must be taken to ensure weight of unit

is properly distributed over roof joists and rafters. Ei-

ther redwood or steel supports are recommended.

ELECTRICAL

In the U.S.A., wiring must conform with current local
codes and the current National Electric Code (NEC). In
Canada, wiring must conform with current local codes
and the current Canadian Electrical Code (CEC). Refer to
the furnace or blower coil installation instructions for
additional wiring application diagrams and refer to
unit rating plate for minimum circuit ampacity and
maximum overcurrent protection size.

WARNING

Unit must be grounded in accordance with nation-

al and local codes. Electric Shock Hazard.

Can cause injury or death.

Line Voltage

To facilitate conduit, a hole is provided in bottom of the
control box. Connect conduit to hole in control box
with proper conduit fitting.
127( 8QLWV DUH DSSURYHG IRU XVH ZLWK FRSSHU FRQGXF
WRUV RQO\

24V, Class II Circuit

24V, Class II Circuit connections are made up in the low
voltage junction box. Refer to figure 2 for field wiring
diagram.
NOTE -- A complete unit wiring diagram is located in-
side the unit control box cover.

TO

COOLING

SPEED

TO

HEATING

SPEED

Y1

RC

W

G

RH

CONDENSING UNIT

TYPICAL INDOOR UNIT

ROOM THERMOSTAT

POWER

GROUND

PER NATIONAL

AND LOCAL

CODES

24v

TRANSFORMER

24V

CLASS II

JUNCTION

BOX

TO

HEATING

CONTROLS

TO 24V CLASS II POWER SOURCE

-- 20 VA MINIMUM

K3 INDOOR BLOWER RELAY

NOTE--IF INDOOR UNIT IS NOT EQUIPPED WITH

BLOWER RELAY, IT MUST BE FIELD PROVIDED

AND INSTALLED (P--8--3251 OR EQUIVALENT)

NOTE--SEE UNIT WIRING DIAGRAM

FOR POWER SUPPLY CONNECTIONS.

24V CLASS II INSTALLED AT FACTORY

24V CLASS II FIELD INSTALLED

FIGURE 2

Y1

C

C

T1

R

W1

G

C

W2

10ACB TYPICAL FIELD WIRING DIAGRAM

All manuals and user guides at all-guides.com

Summary of Contents for Value 10ACB Series

Page 1: ...LHV RQGHQVLQJ 8QLWV 21 16 1 81 76 1 1 2 through 5 ton 503 800M 2 98 Supersedes 503 755M TABLE OF CONTENTS VALUE 10 CONDENSING UNIT 1 SHIPPING AND PACKING LIST 1 GENERAL INFORMATION 1 10ACB UNIT DIMENS...

Page 2: ...COIL FAN COMPRESSOR INLET AIR INLET AIR SUCTION LINE CONNECTION B 24 1 4 616 3 4 19 2 3 4 70 24 1 4 616 ELECTRICAL INLETS LIQUID LINE CONNECTION Model No A B 10ACB12 10ACB18 in 25 24 1 4 10ACB18 10AC...

Page 3: ...on diagrams and refer to unit rating plate for minimum circuit ampacity and maximum overcurrent protection size WARNING Unit must be grounded in accordance with nation al and local codes Electric Shoc...

Page 4: ...SUCTION LINE L10 LINE SETS 10ACB24 10ACB30 10ACB42 3 8 in 10 mm 3 4 in 19 mm L10 41 20 ft 50 ft 6 m 15 m 10ACB18 5 16 in 8 mm 3 8 in 10 mm L10 65 30 ft 50 ft 9 m 15 m L10 21 20 ft 50 ft 6 m 15 m 5 8 i...

Page 5: ...he primary leak seal To Access Schrader Port 1 Remove service port cap with an adjustable wrench 2 Connect gauge to the service port 3 When testing is completed replace service port cap Tighten finger...

Page 6: ...TEM USE ADJUSTABLE WRENCH ROTATE STEM CLOCKWISE 90E TO CLOSE ROTATE STEM COUNTER CLOCKWISE 90E TO OPEN BALL SHOWN OPEN TO OUTDOOR COIL TO INDOOR COIL 7 67 1 After the line set has been connected to th...

Page 7: ...urs the leak testing procedure must be repeated NOTE The term absolute pressure means the to tal actual pressure within a given volume or sys tem above the absolute zero of pressure Absolute pressure...

Page 8: ...t 6 1m line set 3 8 in 10mm 5 16 in 8mm 2 ounce per 5 ft 57ml per 1 5m 3 ounce per 5 ft 85ml per 1 5m If line length is greater than 20 ft 6 1m add this amount If line length is less than 20 ft 6 1m s...

Page 9: ...e sys tem Used prudently table 4 could serve as a useful service guide Before charging the unit follow the procedure below to determine the liquid line temperature and the out door ambient temperature...

Page 10: ...Liquid Line EF EC Out door Ambient EF EC Approach Temperature The resulting difference Approach temperature should agree with the values given in table 6 If not add refrig erant to lower the approach...

Page 11: ...nd coils for evi dence of oil leaks 3 Check wiring for loose connections 4 Check for correct voltage at unit unit operating 5 Check condenser fan motor amp draw Unit nameplate _________ Actual _______...

Page 12: ...H 6WDWH 6WDWH 6HUYLFH WHFKQLFLDQ PSV 6XSSO RQGHQVHU DQ RPSUHVVRU QGRRU LOWHU OHDQ QGRRU ORZHU 0 6XSSO 9ROWDJH 8QLW 2II 6 3 URS 2YHU YDSRUDWRU U RQGHQVHU QWHULQJ LU 7HPSHUDWXUH LVFKDUJH 3UHVVXUH 6XFWLR...

Reviews: