Page 21
TABLE 4
SW 120 BLOWER PERFORMANCE
NOTE - Blower Table Includes Resistance For Base Unit With Wet Indoor Coil And Air Filters In Place.
Air
Volume
cfm
EXTERNAL STATIC PRESSURE - Inches Water Gauge
Drive
No.
0.10
0.20
0.30
0.40
0.50
0.60
0.70
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
3000
Field
Fur
nished
538
0.67
567
0.79
597
0.93
627
1.06
658
1.18
689
1.30
720
1.41
3200
554
0.79
583
0.92
612
1.05
643
1.18
673
1.31
704
1.42
735
1.53
3400
570
0.92
599
1.05
629
1.18
659
1.31
690
1.44
721
1.55
752
1.66
3600
588
1.06
616
1.19
646
1.32
677
1.45
708
1.58
739
1.69
769
1.80
3800
606
1.21
635
1.34
665
1.48
696
1.61
727
1.73
758
1.85
788
1.95
4000
626
1.37
655
1.50
685
1.64
716
1.77
747
1.90
778
2.01
808
2.10
4200
647
1.54
676
1.68
707
1.82
738
1.95
769
2.07
799
2.18
828
2.27
4400
1
669
1.72
699
1.87
730
2.01
761
2.14
791
2.25
820
2.35
849
2.44
4600
693
1.92
724
2.07
755
2.21
785
2.34
814
2.45
842
2.54
871
2.62
4800
718
2.14
749
2.29
780
2.43
809
2.54
837
2.64
865
2.73
893
2.81
Air
Volume
cfm
EXTERNAL STATIC PRESSURE - Inches Water Gauge
Drive
No.
0.80
0.90
1.00
1.10
1.20
1.20
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
3000
1
751
1.50
782
1.58
815
1.67
849
1.76
884
1.87
922
1.99
3200
766
1.62
797
1.71
830
1.79
863
1.89
899
2.00
936
2.12
3400
782
1.75
814
1.84
846
1.93
879
2.03
914
2.13
951
2.25
3600
800
1.89
831
1.98
863
2.07
896
2.17
931
2.28
967
2.39
3800
818
2.04
849
2.13
881
2.22
913
2.32
948
2.42
983
2.53
4000
837
2.20
868
2.28
899
2.38
932
2.47
965
2.57
1000
2.68
4200
857
2.36
887
2.45
918
2.54
950
2.63
983
2.73
1018
2.84
4400
878
2.53
908
2.61
938
2.70
969
2.79
1002
2.89
1036
2.99
4600
899
2.71
928
2.79
958
2.87
989
2.96
1021
3.06
1054
3.16
4800
*
920
2.88
949
2.96
979
3.04
1009
3.13
1041
3.22
1073
3.32
*NOTE
-
italics
- field furnished.