background image

Page 10

 6 - After it has been determined that each appliance re­

maining connected to the common venting system
properly vents when tested as outlined above, return
doors, windows, exhaust fans, fireplace dampers and
any other fuel burning appliance to its previous condi­
tion of use.

 7 - If improper venting is observed during any of the

above tests, the common venting system must be
corrected.

Flue Connections

IMPORTANT

When flue pipe is installed at less than minimum
clearance listed in table 2, radiation shields must be
installed. See figure 13.

Use 24 gauge or heavier galvanized smoke pipe and fit­
tings to connect the furnace to the vent. Connect flue pipe
to chimney using the least number of elbows and angles
possible. Flue pipe or vent connector must be inserted into
but not beyond the inside surface of the chimney flue. No
reduction in diameter of flue pipe is acceptable. It is best to
have flue pipe as short and direct as possible. Where two
or more appliances vent into a common flue, the area of
the common flue should be at least equal to the area of the
largest flue or vent connector, plus 50% of the area of any
additional flues or vent connectors. Install a barometric
draft control (provided) and flue pipe according to instruc­
tions packed with control.

Inspect flue pipe annually. Clean soot or ash from flue pipe,
if necessary. If pipe is rusted, replace.

Barometric Draft Control Installation

NOTE -

 DO NOT install  the barometric draft control if the

furnace is equipped with an air intake kit. See figure 9.

Install the provided barometric draft control in the flue pipe

at least 12 inches

 beyond the furnace flue outlet to pro­

vide space for flue gas sampling. The barometric draft con­
trol may be installed in either vertical or horizontal sections
of the flue pipe; however, it should be positioned 

no more

than 18” 

beyond the furnace flue outlet. Follow the instruc­

tions packed with the barometric draft control.

Alternate Side Flue Connections

The vent pipe may exit the top or sides of the cabinet. A
hole is provided in the top cap for top exit. For side exit, lo­
cate the center hole punched in the side of the cabinet. See
unit dimensions on page 2. Using it as the center point,
cut a 6 inch (152 mm) round hole in the cabinet's side.

Install the barometric draft control within 18 inches of
the furnace flue outlet. 

Attach the provided finishing

plate to cover rough edges.

Supply & Return Air Plenums

Secure return air plenum to unit using sheet metal screws.

NOTE - The following are suggested procedures that should
be followed when installing the supply air plenum.

1. Use sealing strips of fiberglass.
2. In all cases, the plenum should be secured to furnace or

evaporator cabinet with sheet metal screws.

3. Install supply and return air ducts as desired.

Oil Supply Line Sizing

Ensure that the restrictions of the piping system, plus any
lift involved, do not exceed the capability of the oil pump.
Use the following guidelines when determining whether to
use a single-or two-stage oil pump.

One-Pipe System

When using a one-pipe system (see figure 14), even with
the oil tank that is above the burner and a vacuum of 6”
(152 mm) Hg or less, a single-stage fuel pump with a sup­
ply line and no return line should be adequate.

Manual bleeding of the fuel pump is required on initial start
up. Failure to bleed air from the oil pump could result in an
air lock/oil starvation condition.

NOTE - As an extra precaution, cycle heating on and off
ten times after bleeding air from the oil pump. This will
eliminate air in the gun assembly.

ÏÏÏÏÏÏÏÏ

ÏÏÏÏÏÏÏÏ

ÏÏÏÏÏÏÏÏ

ÏÏÏÏÏÏÏÏ

ÏÏÏÏÏÏÏÏ

ÏÏÏÏÏÏÏÏ

ÏÏÏÏÏÏÏÏ

ÏÏÏÏÏÏÏÏ

ÏÏÏÏÏÏÏÏ

ÏÏÏÏÏÏÏÏ

ÏÏÏÏÏÏÏÏ

ÏÏÏÏÏÏÏÏ

ÏÏÏÏÏÏÏÏ

ÏÏÏÏÏÏÏÏ

ÏÏÏÏÏÏÏÏ

ÏÏÏÏÏÏÏÏ

ÏÏÏÏÏÏÏÏ

ÏÏÏÏÏÏÏÏ

1” (25 mm) min

Figure 13

COMBUSTIBLE

MATERIAL

Radiation Shield Installation

SLO185UFV UNIT

(TOP)

SLO185UFV UNIT

(FRONT)

RADIATION

SHIELDS

FLUE

PIPE

UNIT

CABINET

NOTE 1-Radiation shields must be constructed of 24 gauge sheet
metal

 minimum

.

NOTE 2-Radiation shields required when A is less than 9” (229 mm).

NOTE 3-Radiation shields should extend from the top of the unit to
the top of the flue pipe.

NON-

COMBUSTIBLE 

SPACERS

RADIATION SHIELDS 

(SEE NOTE 1)

7” (178

mm) min

12” (305 mm) min

A

A

B

SEE

NOTE

3

SEE

NOTE 2

Summary of Contents for SIGNATURE SLO185UFV Series

Page 1: ...ng List 1 SLO185UFV Unit Dimensions 2 SLO185UFV Unit Parts Arrangement 3 SLO185UFV Oil Burner Parts Arrangement 3 Requirements 4 Combustion Ventilation Air 5 Locate Level the Unit 6 Adjustments 7 Vent...

Page 2: ...her Side ELECTRICAL INLET Right Side Only OIL PIPING INLET Left Side Only OPT OUTDOOR COMBUSTION AIR INLET CENTERING HOLE Field Fabricate Right Side only RETURN AIR OPENING Either Side 3 4 19 A B C D...

Page 3: ...SPEED BLOWER MOTOR OBSERVATION PORT HEAT EXCHANGER FLUE COLLAR LIMIT SWITCH INDOOR BLOWER CAPACITOR BLOWER CONTROL Figure 2 SLO185UFV NX Burner Parts Arrangement Blower Motor Blower Wheel With Air Gu...

Page 4: ...gs required SLO185UFV 79 105 10 X 20 254 mm X 508 mm SLO185UFV 124 141 11 X 22 279 mm X 559 mm This unit is approved for use on combustible flooring and for clearances to combustible material as liste...

Page 5: ...ed at the same time as the furnace much more air is required to ensure proper combustion and to prevent a down draft situation Insufficient amounts of air also cause incomplete combustion which can re...

Page 6: ...tional area as the free area of the openings to which they connect The minimum dimension of rectangular air ducts shall be no less than 3 76 mm In calculating free area the blocking effect of louvers...

Page 7: ...le assembly must be checked for proper depth and alignment You must remove the entire burner assembly not just the nozzle from the furnace to check the nozzle depth and alignment The smaller sized fir...

Page 8: ...make a thorough inspection of the chimney to determine whether repairs are necessary Make sure the chimney is properly constructed and sized ac cording to the requirements of the National Fire Protec...

Page 9: ...nt connectors serving this appliance shall not be connected into any portion of mechanical draft sys tems operating under positive pressure 18 Keep the area around the vent terminal free of snow ice a...

Page 10: ...aft control Alternate Side Flue Connections The vent pipe may exit the top or sides of the cabinet A hole is provided in the top cap for top exit For side exit lo cate the center hole punched in the s...

Page 11: ...returning it to the tank To determine the run and lift for piping refer to table 5 Use continuous lengths of heavy wall copper tubing or steel pipe for oil supply pipe Install oil supply pipe under f...

Page 12: ...he building between the tank shut off valve and the burn er Locate filter close to burner for easy maintenance Table 6 lists the filters for the SLO185UFV furnace Table 6 Oil Filters Cat No 10 micron...

Page 13: ...this product may result in a fire causing property dam age severe injury or death Use copper wire only with this product CAUTION Failure to use properly sized wiring and circuit breaker may result in...

Page 14: ...Page 14 Figure 17 Field Wiring Diagrams 1 Heat 1 Cool 1 Heat 2 Cool 1 Heat 1 Cool With Thermostat Dehumidification Mode 1 Heat 2 Cool With Thermostat Dehumidification Mode...

Page 15: ...iagrams Continued Dual Fuel Single Stage Heat Pump With Dual Fuel Control Mode Dual Fuel Two Stage Heat Pump With Dual Fuel Control Mode Dual Fuel Two Stage Heat Pump With Dual Fuel Control Mode and T...

Page 16: ...of each cooling demand to allow for greater humidity removal and to conserve energy If after 7 1 2 minutes the Y demand is not met 100 CFM is supplied until the demand is satisfied OFF CALL 100 82 Y...

Page 17: ...flash 10 times At times the light may appear to flicker or glow This takes place when the control is communicating with the motor between cycles This is normal operation After the CFM for each applica...

Page 18: ...External Static Pressure Range ADJUST Jumper Setting Jumper Speed Positions HEAT Speed COOL Speed 85 High Fire 75 Low Fire A C A B C D cfm cfm cfm cfm cfm cfm N A N A 2000 2000 1800 NORM 1850 1550 20...

Page 19: ...of bubbles Then terminate the call for heat The burner control will resume normal operation Fuel Pump Pressure Adjustment Measure fuel pump pressure with unit off Attach pressure gauge to pump outlet...

Page 20: ...er obtain and record the flue gas temperature at the service hole 11 Use the CO2 reading and the flue gas temperature reading to determine unit efficiency 12 When proper combustion and smoke readings...

Page 21: ...tube CAUTION Do not attempt to clean the combustion chamber It can be easily damaged 5 Replace the three clean out caps and flue access el bow Make sure locking screws are secure 6 Brush out and vacu...

Page 22: ...nal is de energized Response D After the thermostat is satisfied the thermostat circuit opens The oil delay valve and burner are de energized D Burner is de energized D Heat fan off ramp timing begins...

Page 23: ...speed ramps down Circulating fan shuts off after 60 seconds Thermostat begins call for fan G terminal is energized Indoor blower is energized immediately at 50 of cool speed ST9103A may be factory co...

Page 24: ...ect the flame detector wires at the primary control If the burner starts fault is in the detector circuit Flame detector leads are shorted Separate leads Flame detector exposed to light Seal off false...

Page 25: ...must be removed from unit Inspect the nozzle for plugged orifice or carbon build up around orifice Nozzle orifice plugged Replace nozzle with the same size spray angle and spray pattern Nozzle straine...

Page 26: ...ter burner fires immedi ately jumper across flame detector termi nals at the pri mary control If burner con tinues to run does not lock out of safety fault may be due to poor fire Inspect fire Unbalan...

Page 27: ...wheel dirty Clean blower wheel Wrong motor rotation Replace motor Restrictions in return or supply air system Correct cause of restriction Power If voltage fluctuates fault is in the power source Rech...

Page 28: ...ed heat exchanger Clean heat exchanger Readjust burner Insufficient overfire draft Increase draft Incorrect nozzle assembly depth Set to 1 13 Too little combustion air Increase combustion air High sta...

Reviews: