XP-6341 6/10
27
Section 3 Controller
0
Wait about 5 seconds until the display shows
the program version number. (The number
may be different than the one shown here.)
Hold the Select button:
or
To set the voltage/frequency setting to Uu01. See
Figure 3-1.
To step to the next parameter, unit configuration
Uc.
or
To set the unit configuration setting to Uc01, if
necessary.
To step to the next parameter, engine type Ec.
To step to the next parameter, advanced
configuration mode or save mode selection.
Move the generator set master switch to the
RUN position. (The generator set engine will
not start.)
Display:
or
To change the engine type, if necessary.
U u 0 1
U c
1
U u 0 1
1 0 4
.
0
A d n c
Press:
Now release the Select button.
or
To enter advanced configuration mode.
Go to Figure 3-3.
or
To proceed to the save mode without
entering the advanced configuration mode.
Go to Figure 3-4.
Now either save your settings or enter the Advanced Configuration Mode to
set the engine data inputs, battery voltage, and communications.
Press:
S A V E
E d 0 1
Note:
Shaded boxes show which number in the controller display changes when the up or down arrow
key is pressed.
Press the down arrow key and then the up
arrow key 3 times to enter the configuration
mode. (This is the controller “password.”)
Controller Configuration Mode:
E c 1 1
Figure 3-2
Configuration Mode (system voltage/frequency, unit configuration, and engine type parameters)