Section 2 Installation Instructions
2.2.8
Fuel Type Check and Conversion
Procedures, Later Models with
IEPR
Note:
This procedure applies to models equipped with
the integrated electronic pressure regulator and
fuel valves shown in Figure 2-8.
Check the connections to the fuel solenoid valve to
verify that the fuel system is set up for the type of fuel that
will be used (natural gas or LP). See Figure 2-8 for the
location of the fuel solenoid valve.
To change the fuel type, change the connection to the
fuel solenoid valve as described below and shown in
Figure 2-12.
LP Connections:
D
Disconnect lead 73A from the fuel valve.
D
Connect lead 73B to the fuel valve.
D
Connect lead 65 to lead N3 (ground).
Natural Gas Connections:
D
Disconnect lead 65 from N3.
D
Disconnect lead 73B from the fuel valve.
D
Connect lead 73A to the fuel valve.
ADV-7602
Figure 2-12
Fuel Type Connections, Models with
IEPR