Section 2 Installation Instructions

Generator sets are shipped with the generator set
neutral attached to the generator set in the junction
box. At installation, the neutral can be grounded at
the generator set or lifted from the ground stud and
isolated if the installation requires an ungrounded
neutral connection at the generator set.

The

generator set will operate properly with the neutral
either bonded to ground or isolated from ground at
the generator set.

Various

regulations

and

site

configurations

including the National Electrical Code (NEC), local
codes, and the type of transfer switch used in the
application determine the grounding of the neutral
at the generator set. NEC 2002 Section 250.20 is
one example that has a very good explanation of
the neutral grounding requirements for generator
sets.

2.2.3

Connect AC and DC Wiring

Note:

Have a licensed electrician make the following
electrical connections.

All connections must

comply with state and local codes.

Size the wire according to the length of run and 115% of
the circuit current (amperage) as directed by the
National Electrical Code

r

(NEC) in ANSI/NFPA 70. See

Figure 2-1 and refer to the wiring diagrams in Section 4,
Diagrams and Drawings.

Refer to Section 1.7 for additional information about
connecting the electrical system.

Load Lead and Engine Start Connections

1. Install a 120 VAC receptacle for the generator set

battery charger and block heater. Supply power to
the receptacle through a circuit that is powered at
all times, by the utility and by the generator set
during utility power outages.

2. Some codes require the use of a disconnect switch.

Check the code requirements for your location and
install a disconnect switch, if required.

3. Use separate conduit for the power cables and the

low voltage engine start leads. Local codes and the
length of run as well as the transfer switch wire size
requirements will determine the wire size needed
for the AC leads. Route the load leads into the
junction box through the access opening in the
back of the box.

4. Connect the load leads from the line circuit breaker

in the generator set junction box to the transfer
switch emergency power connection points. See
Figure 2-1 and refer to transfer switch installation
manual for ATS connection instructions.

5. Use the remote harness with pigtail connector at

the customer interface connector to connect
engine start leads 3 and 4 to the engine start
terminals on the transfer switch.

Refer to the

transfer

switch

installation

manual

for

ATS

connection instructions.

6. If an auxiliary fault switch is used, connect it to

leads 30 and N at the customer interface
connector.

2.2.4

Install Engine Starting Battery

Explosion.
Can cause severe injury or death.
Relays in the battery charger
cause arcs or sparks.

Locate the battery in a well-ventilated
area. Isolate the battery charger from
explosive fumes.

WARNING

Battery gases.

Explosion can cause severe injury or

death.

Battery gases can cause an explosion. Do not smoke

or permit flames or sparks to occur near a battery at any time,
particularly when it is charging. Do not dispose of a battery in a
fire.

To prevent burns and sparks that could cause an

explosion, avoid touching the battery terminals with tools or
other metal objects. Remove all jewelry before servicing the
equipment. Discharge static electricity from your body before
touching batteries by first touching a grounded metal surface
away from the battery. To avoid sparks, do not disturb the
battery charger connections while the battery is charging.
Always turn the battery charger off before disconnecting the
battery connections. Ventilate the compartments containing
batteries to prevent accumulation of explosive gases.

Use a 12 VDC battery with a minimum rating of
525 CCA.

1. Verify that the generator set master switch is in the

OFF/RESET position.

2. Ensure that the starting battery is fully charged

before placing the battery in service.

3. Clean the battery posts and/or adapters if

necessary.

4. Install battery post adapters, if needed.

5. See dimension drawing ADV-7000A in Section 4

for the battery rack location. Place the battery on
the battery rack on the skid.

Summary of Contents for RGEN30

Page 1: ...equipment for shipping damage If you find any damage immediately contact the last carrier INSTALLATION INSTRUCTIONS RGEN30 RESIDENTIAL GENERATOR SET XP 6341 6 10b Table of Contents Safety Precautions...

Page 2: ...s are readily available for future reference Record field installed kit numbers after installing the kits Generator Set Identification Numbers Record the product identification numbers from the genera...

Page 3: ...attery charger 3 Remove the battery cables negative lead first Reconnect the negative lead last when reconnecting the battery Follow these precautions to prevent starting of the generator set by an au...

Page 4: ...utinely inspected WARNING Generator set operation Carbon monoxide can cause severenausea fainting or death Carbon monoxide is an odorless colorless tasteless nonirritating gas that can cause death if...

Page 5: ...dvertent interconnection of standby and normal sources of supply WARNING Welding the generator set Can cause severe electrical equip ment damage Never weld components of the generator set without firs...

Page 6: ...ity electrical system can cause severe injury or death to utility personnel working on power lines Heavy Equipment Unbalanced weight Improper lifting can cause severe injury or death and equipment dam...

Page 7: ...tor Set XP 6198 One Parts Catalog combines generator and engine information Generator set serial numbers below 2272938 w Generator set serial numbers above 2272938 Figure 1 Related Literature Nameplat...

Page 8: ...ult the engine manufacturer s instructions for engine coolant specifications See the List of Related Materials in the Introduction 1 4 Block Heater Use block heaters on all standby applications where...

Page 9: ...or the generator set Route DC leads in separate conduit from AC conductors Carefully install the selected generator set accessories Route wiring to the generator set through flexible connections Compl...

Page 10: ...enerator The generator set will operate properly with the neutral either bonded to ground or isolated from ground at the generator 1 7 5 Terminal Connector Torque Use the torque values shown in Figure...

Page 11: ...4 5 6 50 43 5 385 20 3 180 3 0 4 0 85 0 107 2 5 6 50 56 5 500 28 2 250 250 350 127 177 5 6 50 73 4 650 36 7 325 400 203 5 6 50 93 2 825 36 7 325 500 253 5 6 50 93 2 825 42 4 375 600 750 304 380 5 6 5...

Page 12: ...fails When normal power returns the switch transfers the load back to the normal power source and then signals the generator set to stop The transfer switch uses a set of contacts to signal the engine...

Page 13: ...electricity is present Ensure you comply with all applicable codes and standards Electrically ground the generator set transfer switch and related equipment and electrical circuits Turn off the main c...

Page 14: ...e shown in the dimension drawings in Section 4 Refer to the generator set dimension drawings for conduit and fuel line placement The drawings give dimensions for electrical and fuel connection rough i...

Page 15: ...lding permit and contact your local utility companies to mark the locations of underground pipes and cables 2 Prepare an area for mounting the generator set a Clear all combustible materials including...

Page 16: ...to the junction box through the access opening in the back of the box 4 Connect the load leads from the line circuit breaker in the generator set junction box to the transfer switch emergency power co...

Page 17: ...ve the fuel piping and regulator installed by the fuel supplier The fuel supply installation must comply with NFPA and local codes 1 See Figure 2 2 Figure 2 3 and Figure 2 4 for the fuel supply requir...

Page 18: ...tem shown in Figure 2 8 which has an integrated electronic pressure regulator IEPR mounted above the engine Note The integrated electronic pressure regulator IEPR and air fuel mixer are specially cali...

Page 19: ...ion is complete you will be instructed to check for fuel leaks with the generator set running See Section 2 2 11 Operation Tests 2 2 7 Fuel Type Check and Conversion Procedures Early Models Note This...

Page 20: ...he quick connects in the wiring harness See Figure 2 10 6 Proceed to Section 2 2 10 to check and adjust the fuel supply pressure Natural Gas Fuel Conversion Procedure Use the following steps to conver...

Page 21: ...the type of fuel that will be used natural gas or LP See Figure 2 8 for the location of the fuel solenoid valve To change the fuel type change the connection to the fuel solenoid valve as described be...

Page 22: ...ck the oil level before operating the engine 4 Operate the engine with the radiator s pressure cap removed until the thermostat opens and the radiator upper hose becomes hot 5 Stop the engine and allo...

Page 23: ...or set running 14 Use a digital multimeter to check the output voltage and frequency Verify 120 volts line to neutral and 60 Hz output 15 Allow the generator set to run until the generator set reaches...

Page 24: ...rts WARNING 1 Verify that all guards are in place Install the enclosure s end panels and nonservice side door 2 Check the items in the Prestart Checklist in the generator set operation manual 3 Move t...

Page 25: ...for a CAN gauge communications parameter setting Cn01 the controller will not power down The controller remains powered at all times to allow remote start commands from the remote CAN gauge 1 hour po...

Page 26: ...ch is moved to the OFF RESET position Voltage frequency setting Uu Set the system voltage and frequency to the value shown in Figure 3 1 Note This parameter sets the nominal system voltage and frequen...

Page 27: ...To change the engine type if necessary U u 0 1 U c 1 U u 0 1 1 0 4 0 A d n c Press Now release the Select button or To enter advanced configuration mode Go to Figure 3 3 or To proceed to the save mode...

Page 28: ...s to the last saved settings when the master switch is moved to the OFF RESET position Figure 3 3 Advanced Configuration Mode engine data input type battery voltage and engine communications To save c...

Page 29: ...e generator set shuts down The generator set continues to run with the new settings until it shuts down but then reverts to the previous settings at the next startup if the changes have not been saved...

Page 30: ...de or To raise or lower the voltage stability gain in smaller increments To enter volts Hz adjustment mode To raise or lower the volts Hz 00 low 09 high or Hold Wait about 5 seconds until the display...

Page 31: ...switch is moved to the OFF RESET position To save changes To discard changes without saving or S A V E Y E S Now move the master switch to OFF RESET n o There are 3 options when the display says SAVE...

Page 32: ...Serial Number Drawing Version Number Figure 2 7 Below 2272938 1 Figure 2 8 Above 2272938 2 Figure 4 1 Version Numbers Drawing Description Version 1 Version 2 Drawing Number Page Drawing Number Page G...

Page 33: ...XP 6341 6 10 33 Section 4 Diagrams and Dimension Drawings Note Dimensions are shown in mm in Figure 4 3 Generator Set Dimensions shown without enclosure ADV 7000A D...

Page 34: ...XP 6341 6 10 34 Section 4 Diagrams and Dimension Drawings Note Dimensions are shown in mm in Figure 4 4 Sound Enclosure Dimensions ADV 7000C D...

Page 35: ...XP 6341 6 10 35 Section 4 Diagrams and Dimension Drawings Figure 4 5 Installation Clearance Drawing ADV 7000D D...

Page 36: ...XP 6341 6 10 36 Section 4 Diagrams and Dimension Drawings Note Dimensions are shown in mm in Figure 4 6 High Wind Mounting Pad Detail Drawing ADV 7000E D...

Page 37: ...XP 6341 6 10 37 Section 4 Diagrams and Dimension Drawings Figure 4 7 GM 1 6 L Schematic Diagram Page 1 ADV 7287A A...

Page 38: ...XP 6341 6 10 38 Section 4 Diagrams and Dimension Drawings Figure 4 8 Schematic Diagram Page 2 ADV 7287B A...

Page 39: ...XP 6341 6 10 39 Section 4 Diagrams and Dimension Drawings Figure 4 9 Wiring Diagram Page 1 GM50548A C...

Page 40: ...XP 6341 6 10 40 Section 4 Diagrams and Dimension Drawings Figure 4 10 Wiring Diagram Page 2 GM50548B C...

Page 41: ...XP 6341 6 10 41 Section 4 Diagrams and Dimension Drawings Note See Figure 4 13 for sound enclosure mounting pad details Figure 4 11 Generator Set Dimensions shown without enclosure ADV 7692A A Sheet 1...

Page 42: ...XP 6341 6 10 42 Section 4 Diagrams and Dimension Drawings Figure 4 12 Generator Set Dimensions shown without enclosure ADV 7692B A Sheet 2...

Page 43: ...XP 6341 6 10 43 Section 4 Diagrams and Dimension Drawings Note Dimensions are shown in mm in Figure 4 13 ADV 7694B B Sound Enclosure...

Page 44: ...XP 6341 6 10 44 Section 4 Diagrams and Dimension Drawings Figure 4 14 Installation Clearance Drawing ADV 7694C B...

Page 45: ...XP 6341 6 10 45 Section 4 Diagrams and Dimension Drawings Figure 4 15 Schematic Diagram ADV 7602A B Sheet 1...

Page 46: ...XP 6341 6 10 46 Section 4 Diagrams and Dimension Drawings Figure 4 16 Schematic Diagram ADV 7602B B Sheet 2...

Page 47: ...XP 6341 6 10 47 Section 4 Diagrams and Dimension Drawings Figure 4 17 Schematic Diagram ADV 7602C B Sheet 3...

Page 48: ...XP 6341 6 10 48 Section 4 Diagrams and Dimension Drawings Figure 4 18 Wiring Diagram GM63943A A Sheet 1...

Page 49: ...XP 6341 6 10 49 Section 4 Diagrams and Dimension Drawings Figure 4 19 Wiring Diagram GM63943B A Sheet 2...

Page 50: ...XP 6341 6 10 50 Section 4 Diagrams and Dimension Drawings Notes...

Page 51: ...XP 6341 6 10 51 Section 4 Diagrams and Dimension Drawings Notes...

Page 52: ...XP 6341 6 10 52 Section 4 Diagrams and Dimension Drawings Notes...

Reviews: