Table 43. Analog Input Objects List
Object ID
Data Range
Units
Object Name
264
Most Recent Error 10
None
1 − 255
274
Space Carbon Dioxide Sensor (Effective)
Parts−per−million
0 − 2000
275
Space Carbon Dioxide Sensor (Local)
Parts−per−million
0 − 2000
276
Space Humidity (Effective)
Percent
0 − 100
277
Space Humidity (Local)
Percent
0 − 100
278
Dehumidification Set Point (Effective)
Percent
0 − 100
279
Dehumidification Status
None
0 − 2
281
Return Air Temperature
Deg. F
−8.7 – 164.4
282
Building Static Pressure
Inches of water
−0.5 − 0.5
283
Duct Static Pressure
Inches of water
0 – 5.00
285
Exhaust Fan Status
Percent
0 – 100
286
Supply Airflow Status
cubic feet per minute
0 – 480 cfm/ton**
287
Blower Motor Speed
RPM
0 – 1500
288
Blower Motor Torque
Percent
0 – 100
289
Outdoor Airflow
CFM
0–480 cfm/ton**
** Multiply the tonnage of the RTU with the value in cubic feet per minute/ton to derive the value in cubic feet minute units.