61
DACC OAT RS ADJ BND
Parameter 201
Example 10.0
°
F
DACC OAT RS PRP BND
Parameter 203
Example 10.0
°
F
Reset Set point (Approx. 60.0
°
F at 75.0
°
F OAT)
55.0
°
F
65.0
°
F
70.0
°
F Out
door Air Temp.
Parameter 202 (DACC OAT RS ADJ SP)
DACC or Free Cooling Set point
80
°
F
Figure 14. Outdoor Air Reset Example
To use example values, set the following parameters:
Parameter 201 – Set to 10.0°F (this setting is for Discharge Air Control Cooling Outdoor Air Temperature Adjustment
Band.
Parameter 202 – Set to 80.0°F (this setting is for Discharge Air Control Cooling Outdoor Air Temperature Cooling
Reset Set Point
Parameter 203 – Set to 10.0°F (this setting is for Discharge Air Control Cooling Outdoor Ambient Air Temperature
Cooling Proportional Band.
14.1.2.
Discharge Air Control Cooling (DACC) Return Air Temperature Reset
IMPORTANT
Return air reset can also be used to adjust parameter 159 when Discharge Air Control Cooling is not used. All
references to the Discharge Air Control Cooling set point apply to the free cooling set point.
The DACC RAT and free cooling set point can be automatically reset when outdoor air temperature becomes cooler.
NOTE
: Parameter 287 cannot be modify directly from the M3 unit controller interface.
For DACC RAT Reset, use the Lennox UC software to access parameter 287 and enable DACC RAT Reset.
For DACC RAT Reset, the discharge air cooling set point starts to increase when the return air temperature drops
to the parameter 205 (DACC RAT RS ADJ SP) which has a default of 70.0°F. The reset set point will continue to
increase at the rate equal to the parameter 204 (DACC RAT RS ADJ BND) divided by the parameter 206 (DACC
RAT RS PRP BND). See the following example:
EXAMPLE
: The application calls for the discharge air occupied set point parameter 180 to be 55.0°F when Return Air
Temperature is 70.0°F or higher. When the Return Air Temperature drops below 70°F, the set point needs to increase
proportionately with the Outdoor Air Temperature decrease (maximum set point increase of 10°F). The 10.0°F Return Air
Temperature difference is called parameter 203 and the set point increase of 10.0°F is called the parameter 204. See
figure 15.
DACC RAT RS ADJ BND
Parameter 204
Example 10.0
°
F
DACC RAT RS PRP BND
Parameter 206
Example 10.0
°
F
Reset Set point Approx.60.0
°
F (at 65.0
°
F RAT)
55.0
°
F
65.0
°
F
60.0
°
F Return
Air Temp.
Parameter 205 (DACC RAT RS ADJ SP)
70.0
°
F
Discharge Air Cooling Control or Free
Cooling Set point
Figure 15. Return Air Reset Example