Table 63. M3 Control Parameters
Control Parameter
Description
Units
Control Value
No
Description
Units
Max.
Default
Min.
Parameter Short
Description
Screen Name
342
GP A02 SOURCE
General Purpose A02
Source
1
1
3
SOURCE
SELECTION
Source/feedback for the PID
loop.
1 = Analog input 1 on GP3 A02
2 = Analog input 2 on GP3 A02
3 = Analog input 3 on GP3 A02
343
GP A02 CYCL INTRVL
General Purpose A02
Cycle Interval
0
1
180
Sec
Frequency of execution of PID
loop.
344
GP A03 MODE
General Purpose A03
Mode
0
0
11
Mode
Selection
1 - Occupied - PID set point A
Unoccupied - PID set point B
2 - Occupied - PID set point A
Unoccupied -Staged output B
3 - Occupied - Staged output A
Unoccupied - PID set point B
4 - Occupied - Staged output A
Unoccupied - Staged output B
5 - Blower On - PID set point A
Blower Off - PID set point B
6 - Blower On - PID set point A
Blower Off - Staged output B
7 - Blower On - Staged output A
Blower Off - PID set point B
8 - Blower On - Staged output A
Blower Off - Staged output B
9 - DI2 on - PID set point B (1)
DI3 on - PID set point A (2)
Otherwise off.
10 - DI2 on - PID set point B (1)
DI3 on - Staged Output A (2)
Otherwise off.
11 - DI2 on - PID set point B (1)
DI3 on - Staged Output A (2)
Otherwise off.
12 - Reserved
(1) -DI3 (on M3) doesn't matter
(2) -DI2 (on M3) is off
(1) -DI3 (on M3) doesn't matter
(2) -DI2 (on M3) is off
345
GP A03 SP A
General Purpose A03
Set Point A
0
0
100
%
Analog output channel 3, set
point A.
346
GP A03 SP B
General Purpose A03
Set Point B
0
0
100
%
Analog output channel 3, set
point B.
347
GP A03 STG A
General Purpose A03
Stage A
0
0
100
%
Analog output channel 3, stage
A
348
GP A03 STG B
General Purpose A02
Stage B
0
0
100
%
Analog output channel 3, stage
B
349
GP A03 OUTPUT
General Purpose A03
Output
0
0
1
Selection
0 = PWM
1 = 0-10 VDC
350
GP A03 PWM FREQ
General Purpose A03
Pulse-Width Modulation
Frequency
50
200
2000
Hz
Frequency of execution of PID
loop.
351
GP A03 KP
General Purpose A03
Proportional Constant
0
0
100
Count
Analog output channel 3 PID
loop proportional constant.
352
GP A03 KI
General Purpose A03
Integral Constant
0
0
100
Count
Analog output channel 3 PID
loop integral constant.
354
GP A03 MIN OUPUT
General Purpose A03
Minimum Output
0
0
100
%
Analog output channel 3 mini
mum output.
355
GP A03 MAX OUPUT
General Purpose A03
Maximum Output
0
100
100
%
Analog output channel 3 Maxi
mum output.