background image

8

Installation of Indoor Unit on Wall Mounting Plate

1. 

A length of field-provided flexible condensate piping 

should be connected to the drain prior to securing the 

unit to the wall mounting plate.

2.  If the factory­provided refrigerant piping connections 

and field-provided flexible condensate piping are long 

enough to enable final field connections after unit is 

installed  on  wall  mounting  plate,  use  field-provided 

tape to bundle them together.

3.  The utility bundle may be routed out of the back of 

the unit or out either side. If the bundle is to be routed 

out the back through an external wall, feed the utility 

bundle through the wall sleeve. If the utility bundle is 

to be routed out of the side of the indoor unit and up 

an inside wall, carefully form the utility bundle so that 

it makes a gentle 90° turn.

4.  Align the back of the indoor unit with the hooks at the 

top of the wall mounting plate. Move the unit from side 

to side to make sure that it settles securely.

5.  The bottom of the unit can be lifted to facilitate 

refrigerant piping and condensate drain connections, 

if necessary.

TEMPORARY

SPACER

(To facilitate

connections)

HOOKS AT TOP

OF MOUNTING

BRACKET

Figure 14. Secure Unit to Wall Mounting Plate

Indoor Unit Condensate Piping Connections

IMPORTANT

Make sure that drain piping is properly routed and 

insulated to prevent both leaks and condensation.

1. 

Use a field-provided hose clamp to secure the drain 

line stub on the side of the cabinet to a field-supplied 

1­inch (25 mm) drain line. 

NOTE: 

Take care not to over-tighten the hose clamps this 

may damage the drain line stub.

NOTE: 

Connection between stub and drain line must be 

watertight. Apply non-hardening plumbing joint 

compound if needed to ensure a watertight seal. 

2. 

Confirm proper slope (not less than 1/4 inch per foot 

(18 mm per meter) and routing of condensate lines to 

ensure moisture is drained away from the indoor unit.

3.  Drain should be as short as possible and should 

not have any droops or kinks that would restrict 

condensate flow and shall be approved resistant pipe. 

There must be a 2­inch (51 mm) space between the 

end of the condensate drain and the final termination 

point (ground, open drain, etc.) to ensure that the line 

will drain freely.

4.  After the system installation is complete, the 

condensate drain line must be checked for leaks 

and proper drainage. If a field-provided condensate 

pump has been installed, it must be checked to 

ensure proper operation. This check is part of the 

start­up process which must be done by the installing 

contractor.

IMPORTANT

Drain should have a slope of at least ¼ inch per foot and 

should be approved corrosion-resistant pipe. You must 

confirm operation of every drain and pump in the system 

as part of the commissioning procedure.

CORRECT 

Make sure there are no 

kinks or dent in drain 

hose to ensure proper 

drainage.

Figure 15. Condensate Line

Outdoor Unit Installation

Installing Drain Connector and Seal

Condensate formed during the heating and defrost 

processes must be drained from heat pump units. Drain 

holes are provided in the base of the units to ensure proper 

drainage. Heat pumps must be raised when installed on a 

concrete pad or the ground to allow drainage to occur. If 

the heat pump unit is installed on wall mounting bracket, 

insert the provided drain connector into one of the 1 

inch (25 mm) drain holes and attached a field-provided 

insulated drain hose to the connector. Use field-provided 

rubber plugs to cover any unused drain holes (see “Figure 

16. Installing Drain Connector and Seal”. 

1.  Fit the rubber seal on the end of the drain joint that will 

connect to the outdoor unit.

2.  Insert the drain joint into the hole in the base pan of 

the unit.

3.  Rotate the drain joint 90° until it clicks in place facing 

the front of the unit.

4.  Connect a drain hose extension (not included) to 

the drain joint to redirect water from the unit during 

heating mode

Seal

Drain Connector

Base pan hole of

outdoor unit

Seal 

Figure 16. Installing Drain Connector and Seal

Summary of Contents for MWHB Series

Page 1: ...indoor wall unit assembly must be thoroughly cleaned following final construction clean up All mini split operating conditions must be verified ac cording to these installation instructions MHB and M...

Page 2: ...ing of refrigerant CFCs HCFCs and HFCs as of July 1992 Approved methods of recovery recycling or reclaiming must be followed Fines and or incarceration may be levied for non compliance CAUTION As with...

Page 3: ...n 012 1 ton 018 1 5 tons 024 2 tons Refrigerant Type 4 HFC 410A Minor Design Sequence 1 1st Revision M H B 009 S 4 S 1 P Series Type M Mini Split OUTDOOR SINGLE ZONE HEAT PUMP UNITS Cooling Efficiency...

Page 4: ...14 11 1 4 286 30 7 8 784 21 7 8 556 17 3 4 451 30 1 8 765 2 3 4 70 2 3 8 60 3 5 8 92 11 7 8 302 Figure 2 9K and 12K Outdoor Unit Dimensions Inches mm DRAIN HOLE bottom of unit FRONT VIEW SIDE VIEW TOP...

Page 5: ...mm inch Indoor unit outline Right rear side refrigerant pipe inlet 2 1 2 64 diameter 18K 3 1 2 90 24K Left rear side refrigerant pipe inlet 2 1 2 64 diameter 18K 3 1 2 90 24K 1 7 8 48 18K 2 1 8 54 24K...

Page 6: ...Rc Rockwell scale minimum Fully insert the wrench into the valve stem recess Service valve stems are factory torqued from 9 ft lbs 12 N m for small valves to 25 ft lbs 34 N for large valves to prevent...

Page 7: ...se a carpenter s level or measuring tape to verify the wall mounting plate is horizontally level 2 Secure the wall mounting plate to the wall using the provided screws and screw anchors NOTE It is imp...

Page 8: ...r unit 3 Drain should be as short as possible and should not have any droops or kinks that would restrict condensate flow and shall be approved resistant pipe There must be a 2 inch 51 mm space betwee...

Page 9: ...ne security system or intercom Electrical interference and radio frequencies from any of these sources may affect operation Since water drains from the outdoor unit during vari ous stages of operation...

Page 10: ...earing wall or area of the roof that can adequately support the unit Consult local codes for rooftop applications CAUTION Roof Damage This system contains both refrigerant and oil Some rubber roofing...

Page 11: ...nto the refrigerant piping before it is connected 10 CAREFULLY adjust refrigerant piping connections to suit the application 11 Slowly loosen one of the flare nuts to release the factory nitrogen char...

Page 12: ...sible and must be insulated to prevent condensation OUTDOOR UNIT OUTDOOR UNIT INDOOR UNIT INDOOR UNIT Maximum Line Set Length Maximum Line Set Length Maximum Elevation Outdooor Unit BELOW Indoor Unit...

Page 13: ...port connections liquid and gas line pipes until a positive pressure is achieved 3 Evacuate the system to a reading of 5000 Microns 5 Torr 4 Break the vacuum by allowing nitrogen into the port connec...

Page 14: ...ingle Zone Wiring IMPORTANT This unit must be properly grounded and protected by a circuit breaker The ground wire for the unit must not be connected to a gas or water pipe a lightning conductor or a...

Page 15: ...line service valves to release the refrigerant charge contained in outdoor unit into the system 5 Replace the stem caps and tighten to the value listed in Table 1 Torque Requirements on page 6 6 Check...

Page 16: ...Anti cold Air Flow n a cF Remote On Off n a CP ECO mode n a On display 3 seconds Outdoor Unit LED Slow flash Flashing at 1Hz Fast flash Flashing at 2Hz Test Run Pre Checks Only perform test run after...

Page 17: ...is below 60 F 16 C In this instance you can use the MANUAL CONTROL button on the indoor unit to test the COOL function 1 Lift the front panel of the indoor unit and raise it until it clicks in place 2...

Page 18: ...18 Indoor Unit Wiring Diagrams Figure 34 MWHB 09K 12K and 18K 115V and 208 230VAC Indoor Unit Wiring Diagram 16022000C27182 Figure 35 MWHB 24K 208 230VAC Indoor Unit Wiring Diagram...

Page 19: ...19 Outdoor Unit Wiring Diagrams Figure 36 MHB 9K and 12K 115VAC Outdoor Unit Wiring Diagram Figure 37 09K 12K and 18K 208 230VAC Outdoor Unit Wiring Diagram...

Page 20: ...20 Figure 38 MHB 24K 208 230VAC Outdoor Unit Wiring Diagram...

Reviews: