background image

Page 22

Ignition Control LED

The ignition control contains a green LED which indicates 

the following:

TABLE 6

  

IGNITION CONTROL LED

LED

UNIT OPERATION

Slow Flash*

Normal Operation - No call for heat

Fast F;lash

Normal Operation - Call for heat

2 Flashes

System lockout - failed to detect or sustain flame

3 Flashes

Pressure switch failed closed before CAI 

is energized or failed open after CAI is 

energized

4 Flashes

High limit (S10) switch open

5 Flashes

Flame sensed and gas valve (GV1) not energized

6 Flashes

On-board microprocessor fault.

7 Flashes

Pressure switch (S18) closed with inducer off.

8 Flashes

Rollout switch (S47/S195) open. Cycle-power to reset.

Steady On

Control board (A3) failure

Steady Off

Internal control board (A3) failure or not power.

High Altitude Adjustments

In  Canada,  certification  for  installation  at  altitudes  over 

4500 feet (1372m) above sea level is the jurisdiction of 

local authorities. Lennox recommends derating 4%/1000 

feet above 4,500 feet. Refer to table 7 for natural gas 

manifold pressures and the Engineering Handbook for 

high altitude kit part numbers.

Units  may  be  fired  at  full  input  up  to  2000  feet.  (610m) 

above sea level. Above 2000 feet (610m), manifold pres-

sure must be adjusted. Adjust pressure regulator to pres-

sure shown in table 7.

TABLE 7

  

CANADA - NATURAL GAS MANIFOLD PRESSURES 

[inch w.g. (kPa)]

Unit

Altitude in Feet (Meters)

0-2000 

(0- 610)

2001-

4500 

(610- 

1372)

4501-

5500 

(1372- 

1676)

5501-

6500 

(1677-

2012)

6501-

7500 

(2012-

2286)

7501-

9500 

(2286-

2896)

125, 150, 

175, 200

3.5 

(0.87)

3.1 

(0.77)

2.8 

(0.70)

2.6 

(0.65)

See Kit Instruction

250, 300, 

350, 400

3.7 

(0.92)

3.2 

(0.80)

2.9 

(0.72)

2.8 

(0.70)

2.6 

(0.65)

See Kit 

Instruction

250, 300, 

350

3.7* 

(0.92)

3.3* 

(0.82)

2.9* 

(0.72)

2.8* 

(0.70)

2.6* 

(0.65)

See Kit 

Instruction

1.6** (0.40)

400

1.7**(0.42)

* High Fire     **Low Fire

NOTE -

  A  natural  to  LP/propane  gas  changeover  kit  is 

required  to  convert  the  unit  in  the  field.  Refer  to  the  in

-

stallation instructions supplied with the changeover kit for 

conversion procedure.

In the US, units may be fired at full input up to 2000 feet 

(610m) above sea level. Above 2000 feet (610m), unit 

must be de-rated by four percent per 1000 feet for in-

stallation above 2000 feet. The de-rate may be accom-

plished by adjusting the manifold pressure. Refer to table 

8 for natural gas manifold pressures and the Engineering 

Handbook for high altitude kit part numbers.

TABLE 8

  

US - NATURAL GAS MANIFOLD PRESSURES 

[inch w.g. (kPa)]

Unit

Altitude in Feet (Meters)

0-2000 

(0- 610)

2001-3000 

(610- 914)

3001-4000 

(915- 1219

4001-5000 

(1220-1524)

5001-10000 

(1524-3048)

125, 150, 

175, 200

3.5 

(0.87)

2.9 

(0.72)

2.7 

(0.67)

See Kit Instruction

250, 300, 

350, 400

3.7 

(0.92)

3.1 

(0.77)

2.8 

(0.70)

2.6 

(0.65)

See Kit 

Instruction

250, 300, 

350

3.7* 

(0.92)

3.1* 

(0.77)

2.8* 

(0.70)

2.6* 

(0.65)

See Kit 

Instruction

1.6** (0.40)

400

1.7** (0.42)

* High Fire     **Low Fire

In some cases, it is necessary to change the pressure 

switch to ensure proper operation at higher altitudes. See 

EHB for high altitude pressure switch kits.
The combustion air inducer proving switch is factory set. 

No adjustment is necessary.

Gas Flow

To check for proper gas flow to the combustion chamber, 

determine the Btu input from the appliance rating plate. Di-

vide this input rating by the Btu per cubic feet of available 

gas. Result is the required number of cubic feet per hour. 

Determine the flow of gas through the gas meter for two 

minutes and multiply by 30 to get the hourly flow of gas.

Supply Gas Pressure Adjustment

Supply pressure should be checked with unit firing at max

-

imum rate. For Natural Gas, supply pressure should be 

maintained in accordance with the specified minimum and 

maximum supply pressures on the unit rating plate.
A natural gas to LP/propane gas changeover kit is re-

quired to convert the unit in the field.  Refer to installation 

instructions provided with changeover kit for conversion 

procedure along with propane minimum and maximum 

supply pressures. 

Supply Pressure Measurement

1 - 

 Shut  off  the  manual  main  supply  valve  (field 

furnished) when installing or removing the measuring 

device (Steps 2 and 6). 

2 –  Connect the measuring device based upon type of 

gas valve. 

For White Rodgers 36G valve (Figure 13), an inlet post lo-

cated on the gas valve provides access to the supply pres-

sure.  Open the inlet port by backing out the 3/32” hex screw 

one turn.  Connect a piece of tubing over the inlet post and 

route to a measuring device to measure supply pressure. 

Summary of Contents for LS25 Series

Page 1: ... cause property damage personal injury or loss of life Installation and service must be performed by a licensed professional installer or equivalent service agency or the gas supplier CAUTION As with any mechanical equipment personal injury can result from contact with sharp sheet metal edges Be careful when you handle this equipment Note Unit heaters are designed for indoor use only RETAIN THESE ...

Page 2: ...rovided and field installed 6 diameter on 350 400 provided and field installed Bag assembly containing 1 Warranty card 1 Brand logo badge 8 10 16 X 5 8 SDST screws 2 Wire ties The heater is shipped completely assembled Check the unit for shipping damage The receiving party should contact the last carrier immediately if any shipping damage is found COMBUSTION AIR BOX UNIT HEATER BAG ASSEMBLY FLUE T...

Page 3: ...1 2 13 5 3 8 137 B 1 2 13 31 7 8 810 14 1 8 356 35 1 4 895 10 1 2 267 2 1 2 64 3 1 8 79 3 76 10 3 4 273 FLUE OUTLET COMBUSTION AIR INLET TOP ORIENTATION COMBUSTION AIR INLET BOTTOM ORIENTATION D 1 2 13 3 1 8 79 1 2 13 LS25 125 150 175 200 SINGLE FAN Model No A B C D in mm in mm in mm in mm LS25 125 LS25 150 19 1 2 495 18 1 2 470 6 3 4 171 5 3 4 146 LS25 175 LS25 200 25 635 23 3 4 603 9 1 2 241 6 1...

Page 4: ...31 7 8 810 14 1 8 356 1 2 13 35 1 4 895 2 5 8 67 3 1 8 79 1 2 13 1 2 13 3 1 8 79 COMBUSTION AIR INLET TOP ORIENTATION COMBUSTION AIR INLET BOTTOM ORIENTATION D D B 16 406 1 2 13 5 3 8 137 10 1 2 267 3 76 10 3 4 273 LS25 250 300 350 400 DUAL FANS Model No A B C D in mm in mm in mm in mm LS25 250 LS25 300 37 5 8 956 36 1 2 927 15 7 8 403 12 1 2 318 LS25 350 LS25 400 47 1194 45 3 4 1162 20 1 2 521 18...

Page 5: ...Page 5 ...

Page 6: ... jurisdiction should be consulted before installation The installation must conform with local building codes or in the absence of local codes with the current edition of CSA B149 installation compliance codes All electrical wir ing and grounding for the unit must also comply with the current edition of CSA C22 1 Canadian Electrical Code These unit heaters are CSA certified for the installation cl...

Page 7: ...o depress spring and release locking tab on the other end locking tab keeps the louver in place for shipping 2 Rotate louvers to direct airflow as desired 3 Cut threaded rods to desired length and slide a 3 8 nut onto the rod TABLE 1 UNIT CLEARANCES TO COMBUSTIBLE MATERIALS Unit Top Side Bottom Back Flue in mm in mm in mm in mm in mm 125 400 6 152 18 457 1 25 18 457 6 152 TABLE 2 MAXIMUM MOUNTING ...

Page 8: ...PIPE AS SHOWN REMOVE AND DISCARD SHIPPING BRACKETS COMBUSTION AIR BOX TWO COMBUSTION AIR BOX BRACKETS ONE ON EACH SIDE COMBUSTION AIR BOX BRACKET TWO ON 250 400 UNITS FOUR SHIPPING BRACKETS TWO ON EACH SIDE IMPORTANT REPLACE TWO SCREWS ON EACH SIDE AFTER DISCARDING THE COMBUSTION AIR BOX BRACKETS FIGURE 2 FIGURE 3 ...

Page 9: ...Page 9 COMBUSTION AIR INTAKE FLANGE CONNECTOR SHIPPED FACING THE INSIDE OF THE BOX TURN DOWNWARD TO ACCEPT THE VENT PIPE AS SHOWN FIGURE 4 ...

Page 10: ...the unit by the approval agencies Concentric venting is not approved for use in either vertical or horizontal vent applications A single wall vent connector may be used between the furnace and the vertical vent pipe in all applications how ever single wall vent material cannot be used for vertical vent piping in residential applications UL ap proved Category III venting materials must be used in a...

Page 11: ...edition of ANSI Z223 1 or CSA B149 installation compliance codes for maximum vent and vent connector lengths 4 The entire length of a single wall metal vent connector shall be readily accessible for inspection cleaning and replacement 5 Single wall vent pipe used as vertical vent in commercial applications must not pass through any attic interior wall concealed space or floor 6 Theunitmaybeventedv...

Page 12: ...t outlet must be 3 feet 1m within a height 15 feet above the meter regulator assembly and 3 feet to a service regulator vent Refer to latest editions of theANSI Z223 1 or CSA B149 for installation compliance codes and with local author ities with jurisdiction 10 Vent termination clearance to an unvented soffit or within 2 feet horizontally of a ventilated soffit must be in accordance with local in...

Page 13: ...HAUST TERMINATION horizontal or vertical EXHAUST VENT TERMINATION TEE COMBUSTION AIR INLET TEE FIGURE 6 CONDENSATE DRAIN THROUGH TEE PIPE AND DRAIN LOOP DOWNWARD SLOPE ON HORIZONTAL VENT Category III adaptor must be installed before optional elbow if used DRAIN LOOP WITH WATER TRAP TO CONDENSATE DRAIN Provided by installer NOTE Minimum horizontal vent length is 3 ft This does not include terminati...

Page 14: ... shall terminate above the roof surface with a listed cap or a listed roof assembly in accordance with the terms of their respective listings and the vent manufacturer s instructions 4 Do not install a manual damper barometric draft regulator or flue restrictor between the unit heater and the chimney 5 If type B1 double wall vent is used inside a chimney no other appliance can be vented into the c...

Page 15: ...pipe 6 After it has been determined that each appliance remaining connected to the common venting system properly vents when tested as outlined above return doors windows exhaust fans fireplace dampers and any other gas burning appliance to their previous condition of use 7 If improper venting is observed during any of the above tests the common venting system must be corrected The common venting ...

Page 16: ...s must be wrapped in electrical tape to avoid damage to the electrical system 2 Make line voltage connections as shown in figure 10 Connect wires to 2 pin P366 plug located on the A3 ignition control board For ease of installation disconnect P366 plug from J366 make wire connections and replace P366 Refer to wiring diagram on unit and the appropriate typical diagram in this manual HIGH VOLTAGE WIR...

Page 17: ...HT RE D 4 CAI N 1 CAI L 1 W HT BL K BLK W HT BLU YEL COM P 001 GND Gr oundi ng Poi nt 4 GND BOARD GRN YEL BLK W HT GRN YEL W HT W HT GRY W HT 538025 02 1 0 538025 02 HI GH VOLTAGE POW ER CONNECTI ONS I GN CTRL A3 1 LOW VOLTAGE THERM OSTAT CONNECTI ONS HEAT W 1 3 9 24VAC I N P368 1 J 368 7 5 4 8 11 12 6 2 P364 P365 P363 L1 P367 J 367 1 3 5 6 R 24V COM M ON C 24V POW ER R BLOW ER G G C P366 W 2 W 1 ...

Page 18: ...XFM R L1 HI 2 1 R C N W HT RE D 4 CAI N 1 CAI L 1 W HT BL K BLK W HT BLU YEL COM P 001 GND Gr oundi ng Poi nt 4 GND BOARD GRN YEL BLK W HT GRN YEL W HT W HT W HT GRY W HT BRN 538024 02 1 0 538024 02 I GN CTRL A3 1 FI ELD PROVI DED POW ER W I RI NG CONNECT TO P366 AND GREEN GROUND SCREW LOCATED I NSI DE UNI T LOW VOLTAGE THERM OSTAT CONNECTI ONS HEAT W 2 HEAT W 1 3 9 24VAC I N P368 1 J 368 7 5 4 8 ...

Page 19: ...shed by installer be installed external to the unit Union must be of the ground joint type A drip leg should be readily accessible to per mit cleaning and emptying See figure 11 NOTE If a switch box is mounted over electrical knock outs on back of unit leave a minimum of 4 102mm clearance between switch box and drip leg A 1 8 NPT plugged tap shall be installed immediately up stream of the gas supp...

Page 20: ...n the building there may be smoke on start up WARNING Danger of explosion Can cause injury or product or property damage You must follow these instructions exactly BEFORE LIGHTING smell all around the appliance area for gas Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor Use only your hand to move the switch Never use tools If the switch will no...

Page 21: ...he ignition sensor proves the flame and the combustion process continues 5 In the event that the flame is not detected after the first 10 second trial for ignition the controller will repeat steps 3 and 4 an additional two times before locking out the gas valve Ignition control will then automatically repeat steps 3 4 and 5 after 60 minutes NOTE To interrupt the 60 minute lockout period move therm...

Page 22: ... four percent per 1000 feet for in stallation above 2000 feet The de rate may be accom plished by adjusting the manifold pressure Refer to table 8 for natural gas manifold pressures and the Engineering Handbook for high altitude kit part numbers TABLE 8 US NATURAL GAS MANIFOLD PRESSURES inch w g kPa Unit Altitude in Feet Meters 0 2000 0 610 2001 3000 610 914 3001 4000 915 1219 4001 5000 1220 1524 ...

Page 23: ...in supply valve 4 Ignite unit and let run for 5 minutes to allow for steady state conditions 5 After allowing unit to stabilize for 5 minutes record supply pressure NOTE On multiple unit installations each unit should be checked separately with and without other units operating Sup ply pressures on both single and multiple unit installations must fall within range listed on the rating plate 6 Shut...

Page 24: ...cks out again call service technician to inspect unit 7 Is pressure switch closed Obstructed flue will cause unit to shut off at pressure switch Check flue passage and outlet SAFETY SHUT OFF VALVE TEST The safety shut off valve test procedure is as follows 1 Turn off the manual gas valve 2 Set the thermostat to call for heat 3 System begins normal sequence of operation 4 After approximately 30 sec...

Reviews: