background image

Page 4

LGH036-360 Agency

HONEYWELL VR9205 GAS VALVE

NEGATIVE AIR

PRESSURE PORT

POSITIVE AIR

PRESSURE PORT

MANIFOLD

PRESSURE TAP

INLET

OUTLET

SUPPLY

PRESSURE

TAP

GAS VALVE SHOWN IN THE ON POSITION

MANIFOLD PRESSURE ADJUSTMENT

(TURN CCW TO INCREASE PRESSURE)

FIGURE 8 

TO GAS

SUPPLY

MANUAL MAIN

SHUT-OFF VALVE

GAS PIPING

SUPPORT

GROUND

JOINT UNION

(REFER TO

LOCAL CODES)

DRIP LEG

OUTSIDE OF UNIT GAS PIPE CONNECTION

TO GAS

VALVE

FIGURE 9

High Alititue Derate

Locate the high altitude conversion sticker in the unit liter-

ature bag. Fill out the conversion sticker and affix next to 

the unit nameplate.
Refer to table 1 for high altitude adjustments.

TABLE 1

HIGH ALTITUDE DERATE

Altitude Ft.*

Gas Manifold Pressure

2000-4500

See Unit Nameplate

4500 And Above

Derate 2% / 1000 Ft. Above Sea Level

*Units installed at 0-2000 feet do not need to be modified.

NOTE

 - This is the only permissible derate for these units.

DRIP LEG

MANUAL MAIN

SHUT-OFF VALVE

GROUND

JOINT UNION

BOTTOM ENTRY GAS PIPING COMPLETED

7” NIPPLE

STREET

ELBOW

TO GAS

SUPPLY

TO GAS

VALVE

Grommets for both gas pipe openings are field provided.

2-1/2” NIPPLE

FIGURE 10

High Altitude Derate - ULNOx Units

Ultra-Low NOx units are approved for installations from 0 

-4500 ft. No modifications are required. Above 2000 ft, the 

furnace will naturally de-rate approximately 10%.

Pressure Test Gas Piping

Operating pressures at the unit gas connection must be 

as shown in table 2.

TABLE 2

OPERATING PRESSURE AT GAS CONNECTION “w.c

Model

Natural Gas

LP/ Propane Gas

Min.

Max.

Min

Max.

KG/KD 024-090

4.5

10.5

11

13

KG/KD 092-300

4.7

10.5

11

13

When testing the pressure of gas lines, the gas valve must 

be disconnected and isolated. Gas valves can be dam-

aged if subjected to more than 0.5 psig.

 WARNING

FIRE OR EXPLOSION HAZARD Failure 

to  follow  the  safety  warnings  exactly  could 

result in serious injury, death or property 

damage. Never test for gas leaks with an 

open  flame.  Use  a  commercially  available 

soap  solution  made  specifically  for  the 

detection of leaks to check all connections. A 

fire or explosion may result causing property 

damage, personal injury or loss of life.

Summary of Contents for LGH 036

Page 1: ...e replaced and pre filter must be removed upon construction completion The input rate and temperature rise must be set per the unit r ating plate The heat exchanger components duct system air filters...

Page 2: ...n LGH156 180 210 240 242 300 360 UNIT CLEARANCES C D B A Outdoor Air Hood Number of fans varies by model Figure 3 1 Unit Clearance A in mm B in mm C in mm D in mm Top Clearance Service Clearance 60 15...

Page 3: ...ocal codes require the installation of such a valve Install a ground joint union between the gas control mani fold and the main manual shut off valve When making piping connections a drip leg should b...

Page 4: ...NION BOTTOM ENTRY GAS PIPING COMPLETED 7 NIPPLE STREET ELBOW TO GAS SUPPLY TO GAS VALVE Grommets for both gas pipe openings are field provided 2 1 2 NIPPLE Figure 10 High Altitude Derate ULNOx Units U...

Page 5: ...o measure manifold pressure Start unit and allow 5 minutes for unit to reach steady state 2 After allowing unit to stabilize for 5 minutes record manifold pressure and compare to value given in table...

Page 6: ...AY COMBUSTION AIR BLOWER K123 1 RELAY SINGLE THROW LIMIT K125 1 RELAY HEAT SHUT OFF P15 PLUG BURNER 1 P19 PLUG COMBUSTION AIR BLOWER 1 P135 PLUG PRIMARY LIMIT P228 PLUG VESTIBULE HEATER P229 PLUG VEST...

Page 7: ...Page 7 LGH036 360 Agency Typical Unit Schematic...

Page 8: ...Condenser Fan Relays Capacitor CAB Relay CAB Disconnect Switch Opt Defrost Control KD only Fan Control Board KD only Proper Gas Flow Approximate 1 Operate unit at least 15 minutes before checking gas...

Reviews: