Wattstopper

 

®

360

°

 Passive Infrared-Low Voltage Occupancy Sensor 

with Light Level, Isolated Relay and Manual On Feature (version 5)
Détecteur de mouvement basse tension à infra-rouge passif 360° (v5) 

avec contrôle du niveau de luminosité, relais isolé et marche en mode manuel
Sensor de ocupación con tecnología infrarroja pasiva de baja tensión 360° 

con nivel de luz, relé aislado y función de encendido manual (v5)

Installation Instructions • Instructions d’Installation • Instrucciones de Instalación

No:24053 – 09/20  rev. 2

Catalog Numbers • Les Numéros de Catalogue • Números de Catálogo: CI-300, CI-300-1

Country of Origin: Made in China • Pays d’origine: Fabriqué en Chine • País de origen: Hecho en China

DESCRIPTION AND OPERATION

The Wattstopper CI-300 360° passive infrared (PIR) occupancy sensors turn lighting systems on and off based on occupancy and 

ambient light levels. The light level feature keeps lights from turning on if the ambient light level is sufficient. 
The sensors can be configured to turn lighting on, and hold it on as long as the sensor detects occupancy. After no movement is 

detected for a user specified time (30 seconds to 30 minutes) the lights are switched off. A “walk-through” mode can turn lights off after 

only 3 minutes, if no activity is detected after 30 seconds of an occupancy detection.
The CI-300 operates on 24V supplied by Wattstopper Power Packs, 24VAC, or half wave rectified AC. CI-300 sensors also have an 

isolated relay with Normally Open and Normally Closed contacts for interfacing with HVAC or EMS.

PLACEMENT GUIDELINES

Depending upon obstacles such as furniture or partitions, the area of coverage may be less or more 

than the sensing distances shown in the coverage pattern. This must be considered when planning 

the number of sensors and their placement. It is also recommended to place the sensor 4 to 6 feet 

away from air supply ducts as rapid air currents or the differences in temperatures may cause false 

activations.
Mount the sensor to the ceiling. The CI-300 sensors are designed for a ceiling height of about 8-10 

feet. Mounting above or below this range will significantly affect the coverage patterns. Be aware 

that as you decrease the mounting height, you decrease the range and increase the sensitivity to 

smaller motions. Conversely, when you increase the height, you increase the range and decrease 

the sensitivity to smaller motions. At heights of more than 12-14 feet, you may start to significantly 

reduce sensitivity. As a general rule, each occupant should be able to clearly view the sensor.
Often the best location to install a CI- 300 in a closed office is off-center. Avoid placing a sensor directly in 

line with an open door through which it has a clear view out, as the sensor may detect people walking by.

Open Office Area Coverage

To get complete coverage in an open office area, install multiple sensors so that there is an overlap 

with each adjacent sensor’s coverage area.
For open office areas with partitions it is best to place sensors over intersection of four workstations.
For large areas of coverage use multiple sensors.

Masking the PIR Lens

Opaque adhesive tape is supplied so that sections of the PIR lens can be masked. This restricts the 

sensor’s view and allows you to eliminate PIR coverage in unwanted areas such as hallways outside of the desired coverage area. 

Since masking removes bands of coverage, remember to take this into account when troubleshooting coverage problems.

6HQVRU

P

P

6HQVRU

P

P

SPECIFICATIONS

Voltage  ................................ 18-28VDC/VAC, half wave rectified AC
Current Consumption ...............................................................15 mA
Power Supply ............................................Wattstopper Power Packs
Isolated Relay Rating ............................................ 1A @30VDC/VAC
Operating Temperature ..............................32° to 131°F (0° to 55°C)
Light Level One-Step Adjustment ................................10FC—300FC
Time Delay Adjustment .............................30 seconds to 30 minutes
 

Walk-Through Mode ...........3 minutes if no activity after 30 sec.

 

Test Mode ..................................... 5 sec. upon DIP switch reset

PIR Coverage
 

Model CI-300 ..........................................................up to 1200ft

2

 

Model CI-300-1 ........................................................up to 500ft

2

Sensitivity Adjustment ................................ High or Low (DIP switch)
UL & CUL Listed for use with Wattstopper Power Packs

Summary of Contents for Wattstopper CI-300

Page 1: ...temperatures may cause false activations Mount the sensor to the ceiling The CI 300 sensors are designed for a ceiling height of about 8 10 feet Mounting above or below this range will significantly affect the coverage patterns Be aware that as you decrease the mounting height you decrease the range and increase the sensitivity to smaller motions Conversely when you increase the height you increas...

Page 2: ...er Class 2 Power Packs For Indoor Use Only LISTED www legrand us wattstopper Relay Com N O N C Control Out Man Switch 24V Common v5 Wiring terminals Load 1 Load 2 Optional CI 300 Rear Housing Depluggable Terminal Front Cover Ceiling Spring Clips 2 Blue Control Out 24V Common Low Voltage Class 2 Line Voltage Line Neutral Feed Through Power Pack Black Red 1 2 Line Voltage Switches Standard wiring wi...

Page 3: ...is optional The sensors are factory preset to allow for quick installation in most applications Verification of proper wiring or coverage or customizing the sensor s settings can be done using the following procedures To make adjustments open the Front Cover by pulling on the cover tab There is a 30 second warm up period when power is first applied Before making adjustments make sure the office fu...

Page 4: ...hanged DIP SWITCH SETTING The CI 300 has 7 DIP switches under the cover Time Delay Switches 1 2 3 The sensor will hold the lights ON as long as occupancy is detected The time delay countdown starts when no motion is detected After no motion is detected for the length of the time delay the sensor will turn the lights OFF Walk Through Switch 4 Walk through mode turns the lights OFF three minutes aft...

Page 5: ...o not turn OFF automatically 1 The sensor technology PIR may be experiencing activations from outside the controlled area or from some type of interference see Unwanted Sensor Activations below 2 Check all sensor and power pack wire connections 3 Disconnect power pack s blue wire If the lights do not turn off replace power pack Reconnect blue wire If the lights turn off the problem may be in the s...

Page 6: ...nts À l inverse lorsque vous augmentez la hauteur vous augmentez la portée et diminuez la sensibilité aux petits mouvements À des hauteurs supérieures à 3 7 4 3 m 12 14 pi vous commencez à réduire la sensibilité de manière significative En règle générale chaque occupant doit être capable de voir clairement le détecteur Souvent l emplacement idéal d un CI 300 dans un bureau fermé est excentré Évite...

Page 7: ...pper Relay Com N O N C Control Out Man Switch 24V Common v5 Bornes de raccordement AVERTISSEMENT COUPER LE COURANT AU DISJONCTEUR PRINCIPAL AVANT D INSTALLER LE CÂBLAGE Câblage standard avec interrupteur d arrêt local Câblage de la marche manuelle avec un interrupteur instantané basse tension Charge 1 Charge 2 en option CI 300 Boîtier arrière Borne débranchable Couvercle frontal Plafond Clips à re...

Page 8: ... Couvercle frontal Plafond Vis Montage avec une boîte de jonction RÉGLAGE DU DÉTECTEUR L unité est préréglée pour un fonctionnement de base comme décrit dans ce guide LE RÉGLAGE EST OPTIONNEL Les détecteurs sont préréglés en usine afin de vous permettre de l installer rapidement dans la plupart des applications Pour vérifier que le câblage ou la portée sont corrects ou pour personnaliser les régla...

Page 9: ...ité des occupants Une fois la temporisation écoulée si aucun mouvement n est détecté pendant la période de redéclenchement de 30 secondes l interrupteur manuel doit être utilisé pour remettre la charge en MARCHE Automatique MARCHE ce mode se sert des déclenchements dus à la présence ainsi que de l activation de l interrupteur pour ACTIVER la charge Un interrupteur manuel fournit les fonctionnalité...

Page 10: ... Vérifiez que le disjoncteur de circuit a bien été réenclenché 2 Vérifiez tous les raccordements des fils du détecteur et du bloc d alimentation 3 Vérifiez que le capteur est raccordé à une tension de 24 V Si du 24 V est bien présent remplacez le détecteur Si vous ne trouvez pas de 24 V vérifiez la présence de haute tension au niveau du bloc d alimentation Si c est le cas remplacez le bloc d alime...

Page 11: ...r los paquetes de alimentación Wattstopper de 24 V CA o CA de media onda rectificada Los sensores CI 300 también tienen un relé aislado con contactos Normalmente abierto N A y Normalmente cerrado N C para acoplarse con el sistema de calefacción ventilación y aire acondicionado HVAC o el sistema de administración de energía EMS GUÍAS PARA LA COLOCACIÓN Según los obstáculos como muebles o divisiones...

Page 12: ...minal de 24 del sensor El cable del otro lado del interruptor a la terminal de interruptor man del sensor Cableado del relé aislado El relé aislado es apto para 1 A a 30 V CA V CC Conecte los cables necesarios para la aplicación que requiere esta salida Relé común se debe usar para el funcionamiento adecuado Normalmente abierto N A se cierra cuando se detecta una presencia Normalmente cerrado N C ...

Page 13: ...para que los tornillos de montaje se inserten en las ranuras de los orificios tipo bocallave 6 Apriete los dos tornillos para fijar el sensor a la caja de conexiones 7 Encastre la cubierta frontal en el sensor ORMDPLHQWR WUDVHUR 7HUPLQDO GHVHQFKXIDEOH XELHUWD IURQWDO LHOR UDVR EUD DGHUDV GH UHVRUWH Montaje en techo Alojamiento trasero Terminal desenchufable Caja de conexiones octágonal de 4 al men...

Page 14: ...rante el día cuando la luz ambiente en el área esté en el nivel deseado El nivel de luz no se puede activar mientras esté activo el modo de prueba Espere a que finalice el modo de prueba o seleccione cualquiera de las configuraciones adicionales de demora de tiempo antes de activar la función de nivel de luz El indicador LED de presencia PIR quizás aún responda cuando las luces se mantienen apagad...

Page 15: ...omo la activación mediante interruptor para encender la carga Un interruptor manual proporciona la siguiente funcionalidad adicional 1 La carga puede encenderse con la activación del interruptor manual y permanece encendida según la configuración de lógica de presencia La demora de tiempo del sensor funciona según lo programado Cuando la carga se apaga a causa de la falta de detección de presencia...

Page 16: ... algún tipo de interferencia consulte Activaciones no deseadas del sensor a continuación 2 Controle todas las conexiones de cables del sensor y de la fuente de alimentación 3 Desconecte el cable azul de la fuente de alimentación Si las luces no se apagan reemplace la fuente de alimentación Vuelva a conectar el cable azul Si las luces se apagan el problema puede estar en el sensor Para comprobar Vu...

Reviews: