30
2.- INSTALLATION
CHARGE OF REFRIGERANT FOR THE SET:
EXAMPLE:
To install a KVHK 38E + LEHK 38E set, with a 22m refrigerant line length between outdoor and indoor unit, then
the refrigerant charge must be calculated as follow:
1º Type of refrigerant R-22 or R-407C, in this case, R-407C .
2º The TABLE 4 shows, that for 22m of line length between indoor unit and outdoor unit, the line sizes are, liquid
7/8", and gas 1-5/8".
3º TABLE 4 shows, for line sizes of 7/8"- 1-5/8", the charge per meter line is: 327 gr/m.
4º TABLE 2 shows, charge of refrigerant for the set with 0m of line length is 10.500gr.
5º To determine the charge of the set:
Add charge of the refrigerant lines + charge of refrigerant indoor unit and outdoor unit.
Total charge for the set: (327 gr/m) x 22m + 10.500 gr = 17.694 gr
MODEL 22E
MODEL 24E
MODEL 28E
MODEL 32E
MODEL 38E
MODEL 44D / D2
MODEL 48D / D2
5/8"
5/8"
5/8"
7/8"
1-1/8"
1-3/8"
151
155
155
155
232
151
155
1-1/8"
1-1/8"
2x7/8"
2x1-1/8"
5/8"
3/4"
2x5/8"
2x5/8"
3/4"
3/4"
1-3/8"
155
232
232
232
327
155
232
1-3/8"
3/4"
1-1/8"
1-3/8"
1-5/8"
2x1-1/8"
2x1-3/8"
5/8"
7/8"
2x5/8"
2x3/4"
Suction Liquid
Suction
Liquid
FROM 0 TO 10M
FROM 30 TO 50M
gr/m
gr/m
MODEL 56D / D2
155
2x1-1/8" 2x5/8"
232
2x1-3/8"
2x3/4"
MODEL 64D / D2
155
2x1-1/8" 2x5/8"
232
2x1-3/8"
2x3/4"
MODEL 76D / D2
232
2x1-3/8" 2x3/4"
327
2x1-5/8"
2x7/8"
MODEL 86D / D2
327
2x1-5/8" 2x7/8"
340
2x2-1/8"
2x7/8"
5/8"
5/8"
3/4"
1-1/8"
1-3/8"
1-5/8"
155
155
155
232
327
155
155
1-1/8"
1-1/8"
2x1-1/8"
2x1-1/8"
5/8"
7/8"
2x5/8"
2x5/8"
Suction
Liquid
FROM 10 TO 30M
gr/m
155
2x1-1/8" 2x5/8"
232
2x1-3/8" 2x3/4"
327
2x1-5/8" 2x7/8"
327
2x1-5/8" 2x7/8"
MODEL 100D / D2
327
2x1-5/8" 2x7/8"
581
2x2-1/8" 2x1-1/8"
327
2x1-5/8" 2x7/8"
2.7.-REFRIGERANT CONNECTIONS
TABLE 4: WEIGHT OF REFRIGERANT R-22 R-407C PER METER LINE OF LINE