BLOWER DATA - DIRECT DRIVE - HIGH EFFICIENCY
4 TON
BLOWER TABLE INCLUDES RESISTANCE FOR BASE UNIT ONLY WITH DRY INDOOR COIL AND AIR FILTERS IN PLACE.
FOR ALL UNITS ADD:
1 - Any factory installed options air resistance (economizer, wet coil, etc.) See page 23.
2 - Any field installed accessories air resistance (electric heat, duct resistance, diffuser, etc.) See
page 23.
External Static
Pressure in. w.g.
Air Volume at Specific Blower Taps (cfm)
Tap 1
Tap 2
Tap 3
Tap 4
Tap 5
DOWNFLOW
KDB048H4E
0.0
1225
1310
1561
2015
2168
0.1
1167
1254
1514
1995
2143
0.2
1112
1203
1473
1977
2126
0.3
1052
1145
1424
1942
2097
0.4
1000
1098
1387
1917
2078
0.5
939
1040
1343
1888
2049
0.6
894
996
1300
1854
2020
0.7
840
941
1250
1819
1991
0.8
780
883
1201
1787
1952
0.9
734
839
1159
1749
1914
1.0
681
784
1115
1704
1856
HORIZONTAL
KDB048H4E
0.0
1185
1265
1504
1983
2120
0.1
1130
1213
1467
1957
2098
0.2
1085
1171
1432
1932
2077
0.3
1035
1125
1395
1906
2054
0.4
978
1069
1347
1870
2023
0.5
929
1023
1304
1841
1992
0.6
880
977
1267
1811
1962
0.7
822
920
1224
1776
1931
0.8
764
863
1175
1740
1900
0.9
718
820
1133
1710
1869
1.0
549
712
1096
1652
1772