Page 14
BLOWER DATA - DIRECT DRIVE - HIGH EFFICIENCY
3 TON
BLOWER TABLE INCLUDES RESISTANCE FOR BASE UNIT ONLY WITH DRY INDOOR COIL AND AIR FILTERS IN PLACE.
FOR ALL UNITS ADD:
1 - Any factory installed options air resistance (economizer, wet coil, etc.) See page 23.
2 - Any field installed accessories air resistance (electric heat, duct resistance, diffuser, etc.) See
page 23.
External Static
Pressure in. w.g.
Air Volume at Specific Blower Taps (cfm)
Tap 1
Tap 2
Tap 3
Tap 4
Tap 5
DOWNFLOW
KDB036H4E
0.0
893
1035
1375
1600
1840
0.1
838
965
1330
1574
1780
0.2
768
895
1277
1543
1748
0.3
705
800
1253
1505
1712
0.4
645
750
1200
1473
1677
0.5
575
690
1150
1435
1638
0.6
- - -
- - -
1095
1390
1608
0.7
- - -
- - -
1052
1345
1577
0.8
- - -
- - -
1004
1302
1528
0.9
- - -
- - -
950
1260
1491
1.0
- - -
- - -
900
1218
1455
HORIZONTAL
KDB036H4E
0.0
900
1045
1379
1599
1810
0.1
828
970
1305
1549
1749
0.2
777
900
1264
1504
1718
0.3
702
800
1216
1479
1677
0.4
635
750
1173
1434
1649
0.5
553
685
1131
1399
1622
0.6
- - -
- - -
1078
1359
1577
0.7
- - -
- - -
1038
1315
1544
0.8
- - -
- - -
986
1280
1509
0.9
- - -
- - -
933
1236
1471
1.0
- - -
- - -
885
1196
1438