Alert Codes
Table 4. Alert Codes
Error
Code
Message
Type
Condition and
Email Notification
Description
Thermostat Display
Text
System Action
Action to Clear /
Recovery Condition
542
Critical
Temperature Sensor
Error
Problem (Zoning
Control)
Indoor temp is displayed
as “--” on the home
screen.
inside
0
1
Anytime there is a zone
sensor temperature
sensor error or any
zone sensor loses
communication with the
damper control module,
the entire system will go
into central mode.
Error could be due to either a
temperature sensor error or lost
communication between zone
sensor and damper control module.
If problem is due to temperature
sensor issue, then zone sensor
will need to be replace. If sensor
auto corrects itself the alert will
be automatically cleared and
system will return to normal zone
operations.
Error codes 542, 543, 544 and
545 could also be caused by lost
communication with the damper
control module. If this is the case,
most likely an error code 551 is
being displayed at the applicable
zone sensor.
Check wiring between damper
control module and the zone
sensor reporting error code 551.
NOTE:
If error is due to lost
communication 551,
error notification 542,
543, 544 and 545 will
only be displayed at the
thermostat.
543
Temperature Sensor
Error
Problem (Zoning
Control)
544
Temperature Sensor
Error
Problem (Zoning
Control)
545
Temperature Sensor
Error
Problem (Zoning
Control)