CAUTION
This is a 12VDC lowvoltage zone sensor. Do not
install on voltages higher than 14VDC.
Electrical Characteristics
All values are at 77°F (25°C). This unit does employ
miswire circuit protection.
Table 1. Zone Sensor Power Requirements
Min
Nom
Max
Unit
Input
Voltage
10
12
14
VDC
Input
Current
-
61.5
133
mA
WARNING
Always turn off power at the main power source
by switching the circuit breaker to the OFF
position before installing or removing this zone
sensor.
All wiring must conform to local and national
building and electrical codes and ordinances.
Dimensions
U
nit
D
imensions
(H
x
W
x
D)
Dimensions: 35/16 x 45/16 x 7/8 in. (84 x 110 x
22mm)
W
all
P
late
D
imensions
(H
x
W)
Dimensions: 41/2” x 53/4” (114 x 146mm)
Installation Guide
i
nstallation
C
onsiDerations
The 17A30 zone sensor is a 12VDC lowvoltage
device and requires a common wire to the damper
control module to operate.
• Shut off all power to system components before
installing zone sensor
• Make sure that all wiring conforms to local
and national building and electrical codes and
ordinances
• Never install the zone sensor on outside walls or
in direct sunlight