Lennox iHarmony 10C16 Installation Instructions Manual Download Page 5

5

• 

If  the  switch  does  not  close  within  60  seconds,  the 

Lennox communicating series thermostat stops heat 

pump  heating  and  satisfies  the  heating  demand  with 

backup heat (backup heat is either electric or gas) 

regardless of the ambient temperature being above the 

hi balance point. 

The heat pump is used again on the next call provided 

the pressure switch has closed; otherwise backup heat 

is used on subsequent heating calls until the pressure 

switch closes.

Freezestat (Optional)

This optional component is only required if there is a small 

zone with little airflow which is causing the indoor coil to 

freeze up. However, normal return air temperature should 

prevent this from occurring. The addition of the freezestat 

will provide for added protection.

NOTE: 

The damper control module comes from the factory 

with a insertion bridge installed on the freezestat 

terminals (see “Figure 7. Damper Control Jumpers 

and Connections” on page 7). Do not remove 

unless a freezestat is connected. Outdoor unit will 

not operate if insertion bridge is removed (missing) 

and no freezestat is installed.

CLIP

COPPER

LINE

EXPANSION

VALVE

FREEZESTAT

SUCTION

MANIFOLD

LIQUID LINE

LAST HAIRPINS

COPPER LINES

Figure 6.  Typical Freezestat Installation - Indoor 

Coil

The table below lists available freezestats for use with the 

damper control module.

Table 4.  Available Freezestats

Catalog 

Number

Piping Size

Description

93G35

⅜”

Opens at 29°F, and closes at 58°F

50A93

⅝”

Opens at 36°F, and closes at 58°F

Suggested Freezestat Installation Method

The following is the recommended method for installation 

of the freezestat for connection to the damper control 

module.

1. 

 A freezestat, sized per “Table 4. Available Freezestats” 

and  ordered  separately,  can  be  installed.  Install  the 

freezestat on one of the copper lines between the 

last hairpins and the suction manifold (see “Figure 6. 

Typical Freezestat Installation - Indoor Coil”) of the 

indoor coil.

2. 

The freezestat senses the line temperature and cycles 

the compressor off when the line temperature fails 

below its setpoint. The freezestat will open and close 

as listed in 

“Table 4. Available Freezestats” 

3. 

Connect freezestat wires to the freezestat terminals 

on the damper control module after removing the 

factory installed bridge (see “Figure 7. Damper Control 

Jumpers and Connections” on page 7).

Setup and Configuration

Damper Control Module Jumper Settings, LEDs 

and Connections

Use the following procedure to install the damper control 

module. For information concerning connections see 

“Table  5.  Damper  Control  Connections,  Insertion  Bridge 

and Jumpers” on page 6.

1. 

Remove the module cover.

2. 

Install the damper control module near the indoor unit 

using provided fasteners.

NOTE: 

DO NOT install damper control module assembly 

to indoor unit or equipment that could induce 

vibration  to  the  module.  Install  assembly  on  flat 

surface away from indoor unit to minimize vibration. 

Securing assembly to a wall stud is desirable.

NOTE: 

By relocating the jumper to system terminals you 

can shift the VA load from the damper transformer 

to the system transformer if needed. 

3. 

Use the default jumper setting for using an external 

24VAC transformer (

DMPR

 

XFMR

). Connect the 

external 24VAC transformer wires to terminals 

DMPR

 

XFMR R

 and 

C

  (see  “Figure  7.  Damper  Control 

Jumpers and Connections” on page 7).

4. 

Verify that the ZONE ID jumper is set to Zone 1-4 only. 

NOTE: 

In-zone thermostats control zones 2, 3 and 4. 

The Lennox communicating series thermostat will 

always control zone 1. 

5. 

Connect wiring from the Lennox communicating 

indoor unit to damper control module RSBus terminals 

marked I

NDOOR

R

I+

I -

  and  C  (see  “Figure  7. 

Damper Control Jumpers and Connections” on page 

7). 

6. 

Connect  in-zone  thermostats  from  zones  2,  3  and 

4 as needed to terminals 

PWR

D+

D-

 and 

C

 (see 

“Figure 7. Damper Control Jumpers and Connections” 

on page 7). 

Summary of Contents for iHarmony 10C16

Page 1: ... zones maximum supported Lennox communicating variable speed indoor unit and communicating or non communicating conventional two stage outdoor unit four zones maximum supported Table of Contents Shipping and Packing List 1 General 1 Required Items Sold Separately 2 Recommended Items Sold Separately 2 Zoning Components 2 Transformer Phasing 2 Dampers 3 Discharge Air Temperature Sensor DATS 3 DATS T...

Page 2: ...see recommendations in following table The damper control module and three in zone thermostats require a total of 6VA to operate Table 1 Zone Damper Transformer Selection Chart Catalog Number Size Description VA LOAD 10P17 40VA 120 208 240VAC 24VAC Damper VA x number of dampers 6VA damper control module 3 in zone thermostats damper transformer VA requirement 10P87 50VA 12P61 75VA 83P74 Electrical ...

Page 3: ...charge Air Temperature Sensor DATS The included discharge air temperature sensor 88K38 monitors the supply air Figure 4 Discharge Air Temperature Sensor Installation Typical Up Flow Furnace shows the discharge air temperature sensor This electronic sensor s probe is inserted into the discharge air plenum see Figure 3 Discharge Air Temperature Sensor Installation DATS to gather air temperature data...

Page 4: ...ing pressure switch valve tee adapter catalog number 87071 Other conditions Pressure switch status is used only for the heat pump heating and does not have any affect on non zone demands Heat pump will stop after the pressure switch status remains open for 60 seconds CAUTION High Pressure Switch must be installed on open side of tee first to prevent refrigerant loss Pressure switch 27W13 should be...

Page 5: ... the suction manifold see Figure 6 Typical Freezestat Installation Indoor Coil of the indoor coil 2 The freezestat senses the line temperature and cycles the compressor off when the line temperature fails below its setpoint The freezestat will open and close as listed in Table 4 Available Freezestats 3 Connect freezestat wires to the freezestat terminals on the damper control module after removing...

Page 6: ...nnect zone damper 24VAC transformer wires to terminals DMPR R and XFMR C see figure 8 Factory default is DMPR XFMR G SENSE Connect the IAQ device requiring blower operation to the indoor unit control G terminal as illustrated in the wiring diagrams located in the applicable iComfort Series Thermostat Installer Guide Place a wire jumper between the indoor unit G and damper control module G sense te...

Page 7: ...amper Transformer R C JUMPER MUST BE SET TO 1 4 THE SETTING FOR 5 8 IS FOR FUTURE USE NC NO C DAMPER RSBUS COMM LED GREEN STATUS LED GREEN PS LED RED CNTRL LED RED ZONING OFF DMPR1 LED RED DMPR2 LED RED DMPR3 LED RED DMPR4 LED RED 3 3 AMP FUSE IN ZONE THERMOSTAT COMM LED GREEN NOTE 1 FREEZESTAT TERMINAL WILL HAVE FACTORY INSTALLED INSERTION BRIDGE DO NOT REMOVE UNLESS CONNECTING A FREEZESTAT 93G35...

Page 8: ...ge the value 4 Press save F Change other red settings if present using a similar process After completing the settings press the back button to continue On the system devices screen continue by pressing the next button Table 7 Adjustable Parameters for Zoning System Parameter Name Default Min Max Incr Parameter Description Zone 2 through 4 Temp Reading Calibration 0ºF 5ºF 5ºF 1ºF Recalibrating the...

Page 9: ...e delivered not the design CFM Table 8 Air Flow System Devices System Parameter Names Edit and Test Airflow Screen Parameter Names Zones 1 4 Continuous Blower CFM Blower Circulation Airflow Zones 1 4 Cooling CFM Cooling Airflow Zones 1 4 Heating CFM Heating Airflow 1 Select the desired radio button option Blower Circulation Airflow Cooling Airflow or Heating Airflow A 2 Adjust airflow for a specif...

Page 10: ...of parameters available for modification Table 11 Smart Hub Parameters Parameter Description About This screen provides information concerning lan guage supported equipment type name control software revision model control mode number control serial number control hardware revision protocol revision number device product level 24VAC average power consumption 24VAC peak power consumption compatible...

Page 11: ... F 4 44 15 56 C Default is 45 F 7 22 C Adjustments are in increments of 1 F 0 56 C Zoning Target Supply Air Temp for HP Heating In heat pump heating mode this setting sets the target discharge air temperature Range is 85 to 110 F 29 44 to 43 33 C Default is 90 F 32 22 C Adjustments are in increments of 1 F 0 56 C Zoning Target Supply Air Temp for Gas Electric Heating Default is 110 F Range is 100 ...

Page 12: ...t When the Emergency Heat setting is OFF the heat pump is used to satisfy heating demands Humidity Control Refer to Lennox communicating thermostat installation and setup guide for more information on humidity control settings and operating modes Note there is no capability to control humidity humidification or dehumidification per individual zone Various humidity control modes would be applicable...

Page 13: ... 380 SLP98xx090V60C 1HP motor 450 SLP98xx110V60C 1HP motor 450 SLP98UH135V60D 1HP motor 450 SL280xxV 3 ton 250 SL280xxV 4 5 ton 450 EL296xxV 2 3 ton 250 EL296xxV 4 ton 380 EL296xxV 5 ton 450 CBX32MV 018 024 250 CBX32MV 024 030 Rev 06 250 CBX32MV 036 Rev 06 250 CBX32MV 048 060 068 Rev 06 450 CBX40UHV 024 030 250 CBX40UHV 036 380 CBX40UHV 042 048 060 450 A 3 duty cycle corresponds to the minimum CFM...

Page 14: ...ically clears when the system detects the issue no longer exists 115 Critical Low Secondary 24VAC Voltage 24VAC power to a system component control is lower than the required range of 18 to 30VAC Check and correct voltage Check for additional power robbing system components devices connected to system This alert code may require the installation of an additional or larger VA transformer Damper con...

Page 15: ...fully NOTE If this issue occurred on an iHarmony zoning system the field will need to manually activate the zoning 310 Moderate Discharge Air Temp Sensor Problem There is a discharge air temperature sensor issue Compare discharge temperature sensor DATS resistance to temperature resistance charts in system component installation instruction Replace discharge air sensor if necessary NOTE Confirm th...

Page 16: ...16 ...

Reviews: