4

DATS Temperature / Resistance Chart

Table 3.  DATS Temperature / Resistance Chart

Sensor 

°C        °F       (ohm)

VDC 

(Volts)

Sensor 

°C        °F       (ohm)

VDC 

(Volts)

-6.6        20    46,134

1.513

46.2      115      4,169

0.304

-3.9        25    39,869

1.425

49.0      120      3,749

0.277

-1.1        30    34,520

1.335

51.8      125      3,368

0.252

1.7        35    29,936

1.247

54.5      130      3,037

0.229

4.4        40    26,104

1.161

57.3      135      2,750

0.209

7.2        45    22,764

1.077

60.0     140      2,489

0.191

10.1        50    19,842

0.993

62.8      145      2,250

0.174

12.8        55    17,406

0.916

65.7      150      2,033

0.158

15.6        60    15,294

0.842

68.5      155      1,847

0.145

18.4        65    13,442

0.772

71.3      160      1,678

0.132

21.2        70     11,849

0.706

73.9      165      1,536

0.121

23.9        75    10,501

0.647

76.8      170      1,397

0.111

26.7        80      9,282

0.589

79.7      175      1,272

0.101

29.5        85      8,233

0.537

82.2      180      1,170

0.094

32.3        90      7,322

0.489

85.1      185      1,070

0.086

35.0        95      6,523

0.445

87.8      190         982

0.079

37.8      100      5,819

0.405

90.8      195         895

0.072

40.6      105      5,193

0.368

93.4      200         829

0.067

43.4      110      4,654

0.335

Pressure Switch

(Required for heat pump applications.)

NOTE: 

Outdoor unit (heat pump) will not operate if 

pressure switch is not installed)

HIGH PRESSURE

SWITCH (27W13)

NEW SERVICE

PORT

VALVE DEPRESSOR

TEE (LENNOX 87071)

Figure 5.  Tee and Vapor Line High Pressure 

Switch

A field-provided HFC-410A high pressure switch (catalog 

number 27W13) is required for applications with a Lennox 

heat pump. This switch protects the system in the event a 

high pressure condition occurs in the outdoor unit during 

heating mode. The switch operates in tandem with the 

factory installed high pressure switch, but connects to the 

iHarmony control instead. The switch is an auto-reset type 

that opens at 550 psig and closes at 425 psig. 

NOTE: 

If a pressure switch is factory installed in the 

outdoor unit, do not remove the switch or switch 

wires.

The damper control module pressure switch may also 

be fastened directly to the vapor valve service port using 

a  field-provided  tee  adapter.  This  line  becomes  the 

discharge line in heat pump heating mode. Recommend 

using pressure switch valve tee adapter (catalog number 

87071). 
Other conditions:
• 

Pressure switch status is used only for the heat pump 

heating and does not have any affect on non-zone 

demands.

•  Heat pump will stop after the pressure switch status 

remains open for 60 seconds.

 CAUTION

High Pressure Switch must be installed on open side of 

tee first to prevent refrigerant loss. 

Pressure  switch  27W13  should  be  installed  near  air 

handler or indoor coil. If installed at outdoor unit, a separate 

2-wire conductor must be used for communicating outdoor 

systems.

Staged Heat Pump Units

Should the pressure switch open during heat pump 

heating second stage operation:
•  Lennox communicating thermostat will downstage the 

heat  pump  from  second-stage  to  first-stage  heating 

operation in order to bring the system pressure down to 

a point where the switch closes again. 

• 

If  the  unit  is  already  running  in  first-stage  when  the 

pressure switch opens, the unit will shut off.

• 

If the switch closes within 60 seconds, then the Lennox 

communicating series thermostat may send a demand 

for second-stage heat pump if needed. 

• 

If  the  switch  does  not  close  within  60  seconds,  the 

Lennox communicating thermostat stops heat pump 

heating and satisfies the heating demand with backup 

heat (backup heat is either electric or gas) regardless of 

the ambient temperature being above the high balance 

point. 

The heat pump is used again on the next call provided 

the pressure switch has closed; otherwise backup heat 

is used on subsequent heating calls until the pressure 

switch closes.

Modulating Heat Pump Unit (XP20 and XP25)

If the pressure switch opens during heat pump heating 

operation:
•  Lennox communicating series thermostat will respond 

by sending a HP heat demand with the demanded rate 

equal  to  the  current  rate   25%.  (i.e.  the  switch  opens 

during a 90% heating demand, 

•  Lennox communicating thermostat then sends a 

demand for 90 25 = 65%) If new calculated rate is below 

the minimum for the unit, minimum demand is sent. 

• 

If the switch closes within 60 seconds, then the Lennox 

communicating series thermostat may change the 

demand for the heat pump as determined by the DATS. 

Summary of Contents for iHarmony 10C16

Page 1: ... zones maximum supported Lennox communicating variable speed indoor unit and communicating or non communicating conventional two stage outdoor unit four zones maximum supported Table of Contents Shipping and Packing List 1 General 1 Required Items Sold Separately 2 Recommended Items Sold Separately 2 Zoning Components 2 Transformer Phasing 2 Dampers 3 Discharge Air Temperature Sensor DATS 3 DATS T...

Page 2: ...see recommendations in following table The damper control module and three in zone thermostats require a total of 6VA to operate Table 1 Zone Damper Transformer Selection Chart Catalog Number Size Description VA LOAD 10P17 40VA 120 208 240VAC 24VAC Damper VA x number of dampers 6VA damper control module 3 in zone thermostats damper transformer VA requirement 10P87 50VA 12P61 75VA 83P74 Electrical ...

Page 3: ...charge Air Temperature Sensor DATS The included discharge air temperature sensor 88K38 monitors the supply air Figure 4 Discharge Air Temperature Sensor Installation Typical Up Flow Furnace shows the discharge air temperature sensor This electronic sensor s probe is inserted into the discharge air plenum see Figure 3 Discharge Air Temperature Sensor Installation DATS to gather air temperature data...

Page 4: ...ing pressure switch valve tee adapter catalog number 87071 Other conditions Pressure switch status is used only for the heat pump heating and does not have any affect on non zone demands Heat pump will stop after the pressure switch status remains open for 60 seconds CAUTION High Pressure Switch must be installed on open side of tee first to prevent refrigerant loss Pressure switch 27W13 should be...

Page 5: ... the suction manifold see Figure 6 Typical Freezestat Installation Indoor Coil of the indoor coil 2 The freezestat senses the line temperature and cycles the compressor off when the line temperature fails below its setpoint The freezestat will open and close as listed in Table 4 Available Freezestats 3 Connect freezestat wires to the freezestat terminals on the damper control module after removing...

Page 6: ...nnect zone damper 24VAC transformer wires to terminals DMPR R and XFMR C see figure 8 Factory default is DMPR XFMR G SENSE Connect the IAQ device requiring blower operation to the indoor unit control G terminal as illustrated in the wiring diagrams located in the applicable iComfort Series Thermostat Installer Guide Place a wire jumper between the indoor unit G and damper control module G sense te...

Page 7: ...amper Transformer R C JUMPER MUST BE SET TO 1 4 THE SETTING FOR 5 8 IS FOR FUTURE USE NC NO C DAMPER RSBUS COMM LED GREEN STATUS LED GREEN PS LED RED CNTRL LED RED ZONING OFF DMPR1 LED RED DMPR2 LED RED DMPR3 LED RED DMPR4 LED RED 3 3 AMP FUSE IN ZONE THERMOSTAT COMM LED GREEN NOTE 1 FREEZESTAT TERMINAL WILL HAVE FACTORY INSTALLED INSERTION BRIDGE DO NOT REMOVE UNLESS CONNECTING A FREEZESTAT 93G35...

Page 8: ...ge the value 4 Press save F Change other red settings if present using a similar process After completing the settings press the back button to continue On the system devices screen continue by pressing the next button Table 7 Adjustable Parameters for Zoning System Parameter Name Default Min Max Incr Parameter Description Zone 2 through 4 Temp Reading Calibration 0ºF 5ºF 5ºF 1ºF Recalibrating the...

Page 9: ...e delivered not the design CFM Table 8 Air Flow System Devices System Parameter Names Edit and Test Airflow Screen Parameter Names Zones 1 4 Continuous Blower CFM Blower Circulation Airflow Zones 1 4 Cooling CFM Cooling Airflow Zones 1 4 Heating CFM Heating Airflow 1 Select the desired radio button option Blower Circulation Airflow Cooling Airflow or Heating Airflow A 2 Adjust airflow for a specif...

Page 10: ...of parameters available for modification Table 11 Smart Hub Parameters Parameter Description About This screen provides information concerning lan guage supported equipment type name control software revision model control mode number control serial number control hardware revision protocol revision number device product level 24VAC average power consumption 24VAC peak power consumption compatible...

Page 11: ... F 4 44 15 56 C Default is 45 F 7 22 C Adjustments are in increments of 1 F 0 56 C Zoning Target Supply Air Temp for HP Heating In heat pump heating mode this setting sets the target discharge air temperature Range is 85 to 110 F 29 44 to 43 33 C Default is 90 F 32 22 C Adjustments are in increments of 1 F 0 56 C Zoning Target Supply Air Temp for Gas Electric Heating Default is 110 F Range is 100 ...

Page 12: ...t When the Emergency Heat setting is OFF the heat pump is used to satisfy heating demands Humidity Control Refer to Lennox communicating thermostat installation and setup guide for more information on humidity control settings and operating modes Note there is no capability to control humidity humidification or dehumidification per individual zone Various humidity control modes would be applicable...

Page 13: ... 380 SLP98xx090V60C 1HP motor 450 SLP98xx110V60C 1HP motor 450 SLP98UH135V60D 1HP motor 450 SL280xxV 3 ton 250 SL280xxV 4 5 ton 450 EL296xxV 2 3 ton 250 EL296xxV 4 ton 380 EL296xxV 5 ton 450 CBX32MV 018 024 250 CBX32MV 024 030 Rev 06 250 CBX32MV 036 Rev 06 250 CBX32MV 048 060 068 Rev 06 450 CBX40UHV 024 030 250 CBX40UHV 036 380 CBX40UHV 042 048 060 450 A 3 duty cycle corresponds to the minimum CFM...

Page 14: ...ically clears when the system detects the issue no longer exists 115 Critical Low Secondary 24VAC Voltage 24VAC power to a system component control is lower than the required range of 18 to 30VAC Check and correct voltage Check for additional power robbing system components devices connected to system This alert code may require the installation of an additional or larger VA transformer Damper con...

Page 15: ...fully NOTE If this issue occurred on an iHarmony zoning system the field will need to manually activate the zoning 310 Moderate Discharge Air Temp Sensor Problem There is a discharge air temperature sensor issue Compare discharge temperature sensor DATS resistance to temperature resistance charts in system component installation instruction Replace discharge air sensor if necessary NOTE Confirm th...

Page 16: ...16 ...

Reviews: