background image

14

Zoning Alert Codes

Table 13. Alert Codes and Troubleshooting

Initial notification of critical alerts will pop up on the home screen and will be listed under notification menu. Minor and moderate alerts are found only 

under the notification menu. 

Alert 

Code

Priority 

Condition

Actual 

Displayed Alert 

Text

Component or System Operational State and Troubleshooting Tip

How to clear 

alert code

105

Critical

Communication 

Problem

A system component has lost communication with the system. System compo-

nent (device) is unable to communicate. 
•  This may indicate the existence of other active alert codes. 
•  In most cases errors are related to electrical noise. Verify that high voltage 

power is separated from the low voltage communication wires. 

•  Check for incorrectly wired or loose connections between system 

components (devices). 

•  Check for a high voltage source of noise close to the system. 

Automatically clears 

when the system 

detects the issue no 

longer exists.

114

Moderate / 

Critical

AC Line 

Frequency / 

Distortion Prob

There is a frequency / distortion problem with the power to a specific system 

component. There is a frequency / distortion problem with the power to a spe-

cific system component.

•  This alert code may indicate transformer overloading. 
•  Check the voltage and line power frequency. 
• 

Check the generator operating frequency, if the system is running on back-

up power. 

•  Correct voltage and frequency problems. 
• 

System will resume normal operation five seconds after fault recovered.

•  All applicable system component outputs are disabled – moderate 

condition.

• 

After 10 minutes, the priority condition is escalated – critical condition.

•  Damper control module will operate in central mode only until proper 

voltage is restored or frequency distortion is resolved – moderate condition.

Automatically clears 

when the system 

detects the issue no 

longer exists.

115

Critical

Low Secondary 

(24VAC) Voltage

24VAC power to a system component control is lower than the required range 

of 18 to 30VAC.
•  Check and correct voltage. 
•  Check for additional power-robbing system components (devices) 

connected to system. 

•  This alert code may require the installation of an additional or larger VA 

transformer.

•  Damper control module will operate in non-zone mode until proper voltage 

is restored.

Automatically clears 

when the system 

detects the issue no 

longer exists.

120

Moderate

Unresponsive 

DEVICE2.

There is a delay in the system component responding to the system. Typically 

this alert code does not cause any operational issues and will clear on its 

own. 
•  This alert code is usually caused by a delay in the outdoor unit responding 

to the thermostat.

•  Check all wiring connections. 

Automatically clears 

after an unresponsive 

system component 

(device) responds to 

any inquiry.

124

Critical

Active Subnet 

Controller 

Missing

The thermostat has lost communication with a system component for more 

than three minutes. System component has lost communication with the ther-

mostat. 
•  Check the wiring connections.
•  Ohm wires.
•  Cycle power. 
•  Check voltage at component.
This alert code stops all associated system operations and waits for a heart-

beat message from the system component that is not communicating. 

Automatically clears 

after communication 

is re-established with 

applicable system 

component (device).

125

Critical

Control Hardware 

Problem

There is a hardware problem on a system component control. There is a con-

trol hardware problem. 
•  Replace the control if the problem prevents operation and is persistent. 
•  Damper control module will remain in non-zone mode (all dampers open) 

for five minutes after priority condition no longer exist.

•  Remove jumper if present on indoor unit between R and W2 if equipment 

interface module is in use.

Automatically clears 

five minutes after the 

issue no longer exists.

Summary of Contents for iHarmony 10C16

Page 1: ... zones maximum supported Lennox communicating variable speed indoor unit and communicating or non communicating conventional two stage outdoor unit four zones maximum supported Table of Contents Shipping and Packing List 1 General 1 Required Items Sold Separately 2 Recommended Items Sold Separately 2 Zoning Components 2 Transformer Phasing 2 Dampers 3 Discharge Air Temperature Sensor DATS 3 DATS T...

Page 2: ...see recommendations in following table The damper control module and three in zone thermostats require a total of 6VA to operate Table 1 Zone Damper Transformer Selection Chart Catalog Number Size Description VA LOAD 10P17 40VA 120 208 240VAC 24VAC Damper VA x number of dampers 6VA damper control module 3 in zone thermostats damper transformer VA requirement 10P87 50VA 12P61 75VA 83P74 Electrical ...

Page 3: ...charge Air Temperature Sensor DATS The included discharge air temperature sensor 88K38 monitors the supply air Figure 4 Discharge Air Temperature Sensor Installation Typical Up Flow Furnace shows the discharge air temperature sensor This electronic sensor s probe is inserted into the discharge air plenum see Figure 3 Discharge Air Temperature Sensor Installation DATS to gather air temperature data...

Page 4: ...ing pressure switch valve tee adapter catalog number 87071 Other conditions Pressure switch status is used only for the heat pump heating and does not have any affect on non zone demands Heat pump will stop after the pressure switch status remains open for 60 seconds CAUTION High Pressure Switch must be installed on open side of tee first to prevent refrigerant loss Pressure switch 27W13 should be...

Page 5: ... the suction manifold see Figure 6 Typical Freezestat Installation Indoor Coil of the indoor coil 2 The freezestat senses the line temperature and cycles the compressor off when the line temperature fails below its setpoint The freezestat will open and close as listed in Table 4 Available Freezestats 3 Connect freezestat wires to the freezestat terminals on the damper control module after removing...

Page 6: ...nnect zone damper 24VAC transformer wires to terminals DMPR R and XFMR C see figure 8 Factory default is DMPR XFMR G SENSE Connect the IAQ device requiring blower operation to the indoor unit control G terminal as illustrated in the wiring diagrams located in the applicable iComfort Series Thermostat Installer Guide Place a wire jumper between the indoor unit G and damper control module G sense te...

Page 7: ...amper Transformer R C JUMPER MUST BE SET TO 1 4 THE SETTING FOR 5 8 IS FOR FUTURE USE NC NO C DAMPER RSBUS COMM LED GREEN STATUS LED GREEN PS LED RED CNTRL LED RED ZONING OFF DMPR1 LED RED DMPR2 LED RED DMPR3 LED RED DMPR4 LED RED 3 3 AMP FUSE IN ZONE THERMOSTAT COMM LED GREEN NOTE 1 FREEZESTAT TERMINAL WILL HAVE FACTORY INSTALLED INSERTION BRIDGE DO NOT REMOVE UNLESS CONNECTING A FREEZESTAT 93G35...

Page 8: ...ge the value 4 Press save F Change other red settings if present using a similar process After completing the settings press the back button to continue On the system devices screen continue by pressing the next button Table 7 Adjustable Parameters for Zoning System Parameter Name Default Min Max Incr Parameter Description Zone 2 through 4 Temp Reading Calibration 0ºF 5ºF 5ºF 1ºF Recalibrating the...

Page 9: ...e delivered not the design CFM Table 8 Air Flow System Devices System Parameter Names Edit and Test Airflow Screen Parameter Names Zones 1 4 Continuous Blower CFM Blower Circulation Airflow Zones 1 4 Cooling CFM Cooling Airflow Zones 1 4 Heating CFM Heating Airflow 1 Select the desired radio button option Blower Circulation Airflow Cooling Airflow or Heating Airflow A 2 Adjust airflow for a specif...

Page 10: ...of parameters available for modification Table 11 Smart Hub Parameters Parameter Description About This screen provides information concerning lan guage supported equipment type name control software revision model control mode number control serial number control hardware revision protocol revision number device product level 24VAC average power consumption 24VAC peak power consumption compatible...

Page 11: ... F 4 44 15 56 C Default is 45 F 7 22 C Adjustments are in increments of 1 F 0 56 C Zoning Target Supply Air Temp for HP Heating In heat pump heating mode this setting sets the target discharge air temperature Range is 85 to 110 F 29 44 to 43 33 C Default is 90 F 32 22 C Adjustments are in increments of 1 F 0 56 C Zoning Target Supply Air Temp for Gas Electric Heating Default is 110 F Range is 100 ...

Page 12: ...t When the Emergency Heat setting is OFF the heat pump is used to satisfy heating demands Humidity Control Refer to Lennox communicating thermostat installation and setup guide for more information on humidity control settings and operating modes Note there is no capability to control humidity humidification or dehumidification per individual zone Various humidity control modes would be applicable...

Page 13: ... 380 SLP98xx090V60C 1HP motor 450 SLP98xx110V60C 1HP motor 450 SLP98UH135V60D 1HP motor 450 SL280xxV 3 ton 250 SL280xxV 4 5 ton 450 EL296xxV 2 3 ton 250 EL296xxV 4 ton 380 EL296xxV 5 ton 450 CBX32MV 018 024 250 CBX32MV 024 030 Rev 06 250 CBX32MV 036 Rev 06 250 CBX32MV 048 060 068 Rev 06 450 CBX40UHV 024 030 250 CBX40UHV 036 380 CBX40UHV 042 048 060 450 A 3 duty cycle corresponds to the minimum CFM...

Page 14: ...ically clears when the system detects the issue no longer exists 115 Critical Low Secondary 24VAC Voltage 24VAC power to a system component control is lower than the required range of 18 to 30VAC Check and correct voltage Check for additional power robbing system components devices connected to system This alert code may require the installation of an additional or larger VA transformer Damper con...

Page 15: ...fully NOTE If this issue occurred on an iHarmony zoning system the field will need to manually activate the zoning 310 Moderate Discharge Air Temp Sensor Problem There is a discharge air temperature sensor issue Compare discharge temperature sensor DATS resistance to temperature resistance charts in system component installation instruction Replace discharge air sensor if necessary NOTE Confirm th...

Page 16: ...16 ...

Reviews: