Table 3. Alarm Faults
Alarm
Mgr
Alarm
ID
Category
Alert
Level
(Severe,
Low,
Info)
Local
Display:
Alert Title
Local Display: Alert
Detailed Description
M3-Specific
Description
IMC Error Description
IMC Action
91
Sensor
Low
Outdoor Enthalpy
Sensor
Outdoor enthalpy sensor
(A7) error Check sensor and
wiring.
Outdoor Enthalpy
Sensor
Outdoor enthalpy sensor (A7) open.
Check sensor and wiring.
No economizer free cooling
operation if economizer mode is
set to ODE or DIF.
92
Sensor
Low
Indoor Enthalpy
Sensor
Indoor enthalpy sensor (A62)
error. Check sensor and
wiring.
Indoor Enthalpy
Sensor
Indoor enthalpy sensor (A62) open.
Check sensor and wiring.
No economizer free cooling
operation if economizer mode is
set to DIF.
93
General Fault
Low
Unit Operating in
Backup Mode
The control has changed the
system mode because of
an error with the controlling
sensor or because of a loss of
communication.
Backup Mode
The control has changed the system
mode because of an error with the
controlling sensor or because of a loss
of communication.
IMC has switched over to the
backup mode option set with
ECTO 6.01.
94
Sensor
Low
Zone sensor
setpoint range
error
Zone sensor setpoint out-of-
range error.
Removed
Zone sensor setpoint out-of-range
error.
IMC reverts to default 65°F (18°C)
heating and 80°F (27°C) cooling
setpoints.
95
Configuration
Info
ECTO parameter
changed
ECTO parameter has been
changed by the pushbutton.
Reserved
ECTO parameter has been changed by
the pushbutton.
For information only. Indicates
that someone has made an ECTO
change.
96
Configuration
Low
Four-Stage
Interface
Failure
Four stage interface failure
A138. ECTO 6.01 set to option
12 when no A138 board present
can also cause this alarm
Reserved
Four stage interface failure A138.
ECTO 6.01 set to option 12 when no
A138 board present can also cause this
alarm
No heating or cooling.
97
Configuration
Low
Four-Stage
Configuration
Error
Four stage interface A138
detected but ECTO 6.01 is not
set to option 12 or equipment
type is set to heat pump.
Reserved
Four stage interface A138 detected but
ECTO 6.01 is not set to option 12 or
equipment type is set to heat pump.
No heating or cooling.
98
Configuration
Info
ECTO Memory
Chip Write
Error
ECTO memory chip write
error.
Reserved
ECTO memory chip write error.
ECTO settings may not be
saved.
99
Economizer
Low
Outside Air
Velocity Sensor
Error
A24 sensor input signal is
continuously above 25% of
sensor measuring range for
more than five minutes with
blower stopped.
OAS Error A24
Outdoor Air Control Sensor (A24) open.
Cleared by IMC reset.
No OAC operation. Damper closed
to minimum position.