background image

Page 12

WARNING

Danger of explosion:  Can cause equipment damage,
injury or death. When using a high pressure gas
such as dry nitrogen to pressurize a refrigeration or
air conditioning system, use a regulator that can
control the pressure down to 1 or 2 psig (6.9 to 13.8
kPa).

Using an Electronic Leak Detector or Halide

 1 − Connect a cylinder of HCFC-22 to the center port of the

manifold gauge set.

 2 − With both manifold valves closed, open the valve on

the HCFC-22 cylinder (vapor only).

 3 − Open the high pressure side of the manifold to allow

the HCFC-22 into the line set and indoor unit. Weigh in
a trace amount of HCFC-22.

 

[A trace amount is a maxi-

mum of 2 ounces (57 g) or 3 pounds (31 kPa) pres-
sure.]

 

Close the valve on the HCFC-22 cylinder and the

valve on the high pressure side of the manifold gauge
set. Disconnect the HCFC-22 cylinder.

 4 − Connect a cylinder of nitrogen with a pressure regulat-

ing valve to the center port of the manifold gauge set.

 5 − Connect the manifold gauge set high pressure hose to

the vapor valve service port. 

(Normally, the high pres-

sure hose is connected to the liquid line port; however,
connecting it to the vapor port better protects the man-
ifold gauge set from high pressure damage.)

 6 − Adjust the nitrogen pressure to 150 psig (1034 kPa).

Open the valve on the high side of the manifold gauge
set which will pressurize line set and indoor unit.

 7 − After a few minutes, open a refrigerant port to ensure

the refrigerant you added is adequate to be detected.
(Amounts of refrigerant will vary with line lengths.)
Check all joints for leaks. Purge nitrogen and HCFC-22
mixture. Correct any leaks and recheck.

Evacuation

Evacuating the system of noncondensables is critical for
proper operation of the unit. Noncondensables are defined
as any gas that will not condense under temperatures and
pressures present during operation of an air conditioning
system. Noncondensables and water vapor combine with
refrigerant to produce substances that corrode copper pip-
ing and compressor parts.

IMPORTANT

Use a thermocouple or thermistor electronic vacuum
gauge that is calibrated in microns. Use an instrument
that reads from 50 microns to at least 10,000 microns.

 1 − Connect manifold gauge set to the service valve ports

as follows:

 

 

low pressure gauge to 

vapor 

line service valve

 

 

high pressure gauge to 

liquid 

line service valve

 2 − Connect micron gauge.

 3 − Connect the vacuum pump (with vacuum gauge) to the

center port of the manifold gauge set.

 4 − Open  both  manifold  valves  and  start  the  vacuum

pump.

 5 − Evacuate the line set and indoor unit to an 

absolute

pressure

 of 23,000 microns (29.01 inches of mercu-

ry). During the early stages of evacuation, it is desir-
able to close the manifold gauge valve at least once to
determine if there is a rapid rise in 

absolute pressure

.

A rapid rise in pressure indicates a relatively large leak.
If this occurs, repeat the leak testing procedure.

NOTE − The term 

absolute pressure

 means the total

actual pressure within a given volume or system,
above the absolute zero of pressure. Absolute pres-
sure in a vacuum is equal to atmospheric pressure mi-
nus vacuum pressure.

 6 − When the absolute pressure reaches 23,000 microns

(29.01 inches of mercury), close the manifold gauge
valves, turn off the vacuum pump and disconnect the
manifold gauge center port hose from vacuum pump.
Attach the manifold center port hose to a nitrogen cylin-
der with pressure regulator set to 150 psig (1034 kPa)
and purge the hose. Open the manifold gauge valves
to break the vacuum in the line set and indoor unit.
Close the manifold gauge valves.

CAUTION

Danger of Equipment Damage.
Avoid deep vacuum operation. Do not use compres-
sors to evacuate a system.
Extremely low vacuums can cause internal arcing
and compressor failure.
Damage caused by deep vacuum operation will void
warranty.

 7 − Shut off the nitrogen cylinder and remove the manifold

gauge hose from the cylinder. Open the manifold
gauge valves to release the nitrogen from the line set
and indoor unit.

 8 − Reconnect the manifold gauge to the vacuum pump,

turn the pump on, and continue to evacuate the line set
and indoor unit until the absolute pressure does not
rise above 500 microns (29.9 inches of mercury) within
a 20−minute period after shutting off the vacuum pump
and closing the manifold gauge valves.

 9 − When the absolute pressure requirement above has

been met, disconnect the manifold hose from the vacu-
um pump and connect it to an upright cylinder of
HCFC-22 refrigerant. Open the manifold gauge valves
to break the vacuum from 1 to 2 psig positive pressure in
the line set and indoor unit. Close manifold gauge
valves and shut off the HCFC-22 cylinder and remove
the manifold gauge set.

Summary of Contents for HS27 Series

Page 1: ...4 669M 02 04 Supersedes 12 02 Table of Contents HS27 Outdoor Unit 1 Shipping Packing List 1 General Information 1 Unit Dimensions 2 Parts Arrangement 3 Setting the Unit 3 Electrical 3 Refrigerant Pipi...

Page 2: ...View Access View 4 1 2 114 2 3 4 70 4 102 6 1 16 154 1 3 8 35 A 4 7 8 22 4 102 2 9 16 65 18 5 8 473 26 5 8 676 34 1 16 865 2 51 28 1 8 714 7 1 2 191 7 1 2 191 3 7 8 98 3 7 8 98 air inlet air inlet 2 5...

Page 3: ...o avoid accidental contact with sharp edges Refer to unit dimensions for sizing mounting slab platform s or supports Refer to figure 2 for installation clearances 36 914 mm 36 914 mm 36 914 mm 36 914...

Page 4: ...structions for additional wiring application diagrams and refer to unit nameplate for minimum circuit ampacity and maximum overcurrent protection size WARNING Unit must be grounded in accordance with...

Page 5: ...R W Y G C Thermostat Furnace Outdoor Unit Y1 Outdoor Unit C Outdoor Unit power heat cooling indoor blower common NOTE see unit wiring diagram for power supply connections NOTE If the indoor unit is no...

Page 6: ...ing Refrigerant Line During the installation of any heat pump or a c system it is important to properly isolate the refrigerant lines to prevent unnecessary vibration Line set contact with the structu...

Page 7: ...id Line IMPORTANT Refrigerant lines must not contact structure Outside Wall Inside Wall Liquid Line Vapor Line IMPORTANT Refrigerant lines must not contact wall Wood Block Between Studs Strap Sleeve W...

Page 8: ...ire Tie Wire Tie around vapor line only Floor Joist or Roof Rafter Tape or Wire Tie Strap the vapor line to the joist or rafter at 8 ft intervals then strap the liquid line to the vapor line To hang l...

Page 9: ...ne Metal Sleeve Anchored Heavy Nylon Wire Tie Automotive Muffler Type Hanger Wall Stud Wall Stud Liquid Line Vapor Line Wrapped in Armaflex Strap Liquid Line To Vapor Line Metal Sleeve Figure 8 Outsid...

Page 10: ...ps If you install an expansion valve with an indoor coil that includes a fixed orifice remove the orifice before instal ling the expansion valve IMPORTANT Failure to remove RFC orifice when installing...

Page 11: ...t hex wrench here valve front seated to outdoor coil to indoor coil Service Valve Valve Open Schrader valve service port service port cap insert hex wrench here to indoor coil to outdoor coil stem cap...

Page 12: ...ollows low pressure gauge to vapor line service valve high pressure gauge to liquid line service valve 2 Connect micron gauge 3 Connect the vacuum pump with vacuum gauge to the center port of the mani...

Page 13: ...or unit should be charged during warm weather However applications arise in which charging must occur in the colder months The method of charging is deter mined by the unit s refrigerant metering devi...

Page 14: ...tdoor ambient temperature to check the liquid line temperature 5 The difference between the ambient and liquid temper atures should match values given in table 4 If the val ues don t agree with the th...

Page 15: ...shed with a water hose Ensure the power is turned off before you clean the coil 2 The outdoor fan motor is prelubricated and sealed No further lubrication is needed 3 Visually inspect connecting lines...

Page 16: ...oor Fan Checked Job No City City Serial No Date State State Service Technician Compressor Outdoor Fan Indoor Filter Clean Electrical Connections Tight Supply Voltage Unit Off Vapor Pressure Thermostat...

Reviews: