background image

Page 10

Brazing Connection Procedure

 1 − Cut ends of the refrigerant lines square (free from nicks

or dents). Debur the ends. The pipe must remain
round, do not pinch end of the line.

 2 − Before making line set connections, use dry nitrogen to

purge the refrigerant piping. This will help to prevent
oxidation and the introduction of moisture into the sys-
tem.

 3 − Use silver alloy brazing rods (5 or 6 percent minimum

silver alloy for copper−to−copper brazing or 45 percent
silver alloy for copper−to−brass or copper−to−steel braz-
ing) which are rated for use with HCFC−22 refrigerant.
Wrap a wet cloth around the valve body and the copper
tube stub. Braze the line set to the service valve.

 4 − Wrap a wet cloth around the valve body and copper

tube stub to protect it from heat damage during braz-
ing. Wrap another wet cloth underneath the valve body
to protect the base paint.

NOTE − The tube end must stay bottomed in the fitting
during final assembly to ensure proper seating, sealing
and rigidity.

 5 − Install a field−provided thermal expansion valve (ap-

proved for use with HCFC−22 refrigerant) in the liquid
line at the indoor coil.

Refrigerant Metering Device

H27 units are used in expansion valve systems only. See
the Lennox Engineering Handbook for approved TXV
match-ups and application information.

Expansion valves equipped with Chatleff fittings are avail-
able from Lennox. Refer to the Engineering Handbook for
applicable expansion valves for use with specific match-
ups.

If you install an expansion valve with an indoor coil that
includes a fixed orifice, remove the orifice before instal-
ling the expansion valve.

IMPORTANT

Failure to remove RFC orifice when installing an ex-
pansion valve on the indoor coil will result in improp-
er operation and damage to the system.

See figure 10 for installation of the check expansion valve.

Metering Device Installation

expansion 

valve

o−ring

o−ring

strainer

liquid line 

stub

distributor

Figure 10

Manifold Gauge Set

When checking the unit charge, use a manifold gauge set
that is equipped with low loss" hoses. Do not use a man-
ifold gauge set with anything other than a low loss" hose.

Service Valves

The liquid line and vapor line service valves (figures 11 and
12) and gauge ports are used for leak testing, evacuating,
charging and checking charge. See table 2 for torque re-
quirements.
Each valve is equipped with a service port which has a fac-
tory−installed Schrader valve. A service port cap protects
the Schrader valve from contamination and serves as the
primary leak seal.

Table 2

Torque Requirements

Part

Recommended Torque

Service valve cap

8 ft.− lb.

11 NM

Sheet metal screws

16 in.− lb.

2 NM

Machine screws #10

28 in.− lb.

3 NM

Compressor bolts

90 in.− lb.

10 NM

Gauge port seal cap

8 ft.− lb.

11 NM

To Access Schrader Port:

 1 − Remove the service port cap with an adjustable wrench.
 2 − Connect gauge to the service port.
 3 − When testing is complete, replace the service port cap.

Tighten finger tight, then an additional 1/6 turn.

To Open Service Valve:

 1 − Remove stem cap with an adjustable wrench.
 2 − Use a service wrench with a hex−head extension to

back the stem out counterclockwise as far as it will go.

Summary of Contents for HS27 Series

Page 1: ...4 669M 02 04 Supersedes 12 02 Table of Contents HS27 Outdoor Unit 1 Shipping Packing List 1 General Information 1 Unit Dimensions 2 Parts Arrangement 3 Setting the Unit 3 Electrical 3 Refrigerant Pipi...

Page 2: ...View Access View 4 1 2 114 2 3 4 70 4 102 6 1 16 154 1 3 8 35 A 4 7 8 22 4 102 2 9 16 65 18 5 8 473 26 5 8 676 34 1 16 865 2 51 28 1 8 714 7 1 2 191 7 1 2 191 3 7 8 98 3 7 8 98 air inlet air inlet 2 5...

Page 3: ...o avoid accidental contact with sharp edges Refer to unit dimensions for sizing mounting slab platform s or supports Refer to figure 2 for installation clearances 36 914 mm 36 914 mm 36 914 mm 36 914...

Page 4: ...structions for additional wiring application diagrams and refer to unit nameplate for minimum circuit ampacity and maximum overcurrent protection size WARNING Unit must be grounded in accordance with...

Page 5: ...R W Y G C Thermostat Furnace Outdoor Unit Y1 Outdoor Unit C Outdoor Unit power heat cooling indoor blower common NOTE see unit wiring diagram for power supply connections NOTE If the indoor unit is no...

Page 6: ...ing Refrigerant Line During the installation of any heat pump or a c system it is important to properly isolate the refrigerant lines to prevent unnecessary vibration Line set contact with the structu...

Page 7: ...id Line IMPORTANT Refrigerant lines must not contact structure Outside Wall Inside Wall Liquid Line Vapor Line IMPORTANT Refrigerant lines must not contact wall Wood Block Between Studs Strap Sleeve W...

Page 8: ...ire Tie Wire Tie around vapor line only Floor Joist or Roof Rafter Tape or Wire Tie Strap the vapor line to the joist or rafter at 8 ft intervals then strap the liquid line to the vapor line To hang l...

Page 9: ...ne Metal Sleeve Anchored Heavy Nylon Wire Tie Automotive Muffler Type Hanger Wall Stud Wall Stud Liquid Line Vapor Line Wrapped in Armaflex Strap Liquid Line To Vapor Line Metal Sleeve Figure 8 Outsid...

Page 10: ...ps If you install an expansion valve with an indoor coil that includes a fixed orifice remove the orifice before instal ling the expansion valve IMPORTANT Failure to remove RFC orifice when installing...

Page 11: ...t hex wrench here valve front seated to outdoor coil to indoor coil Service Valve Valve Open Schrader valve service port service port cap insert hex wrench here to indoor coil to outdoor coil stem cap...

Page 12: ...ollows low pressure gauge to vapor line service valve high pressure gauge to liquid line service valve 2 Connect micron gauge 3 Connect the vacuum pump with vacuum gauge to the center port of the mani...

Page 13: ...or unit should be charged during warm weather However applications arise in which charging must occur in the colder months The method of charging is deter mined by the unit s refrigerant metering devi...

Page 14: ...tdoor ambient temperature to check the liquid line temperature 5 The difference between the ambient and liquid temper atures should match values given in table 4 If the val ues don t agree with the th...

Page 15: ...shed with a water hose Ensure the power is turned off before you clean the coil 2 The outdoor fan motor is prelubricated and sealed No further lubrication is needed 3 Visually inspect connecting lines...

Page 16: ...oor Fan Checked Job No City City Serial No Date State State Service Technician Compressor Outdoor Fan Indoor Filter Clean Electrical Connections Tight Supply Voltage Unit Off Vapor Pressure Thermostat...

Reviews: