HCWB2 REQUIRED MAINTENANCE

Refer to figure 5 for parts identification when reviewing
the following procedure. Bold text indicates components
that are identified in the illustration.

Electric shock hazard. Can cause injury
or death. Disconnect all electrical power
supplies before servicing.  Shut off wa-
ter supply before disconnecting or tap-
ping into any water supply line.

WARNING

!

− Make sure the main power to furnace is

disconnected.

2 − Make sure the humidistat is in the 

OFF 

position.

3 − Make sure the water supply is turned off.
4 − Slide the 

latch

 to release the 

front cover

. Swing the

cover open, then lift it away from the assembly.

5 − Turn the 

damper handle

 to one of the SUMMER"

positions. Grasp the 

tabs

 on the 

pad assembly

frame

 and lift the assembly out of the 

humidifier

base

.

NOTE − It may be easier to remove the frame by
pulling on the 

tabs 

one at a time.

6 − Unsnap the 

pad assembly frame

 from the sides of

the 

distribution tray

. Remove the 

distribution tray

from the 

pad assembly frame

. Remove the 

tray

cover

 by pulling it straight off of the 

distribution tray

.

Lightly scrape off any mineral deposits from the
surface of the 

distribution tray

.

7 − Slide the 

humidifier pad

 out of the frame. Twist and

flex the frame to loosen the calcium deposits on the
frame or use a putty knife to clean the frame. Replace
the 

humidifier pad

 annually or more frequently if

necessary. Slide the pad into the frame with the black
mark facing up. Snap the 

tray cover

 onto the

distribution tray

. Snap the 

distribution tray

 back

into place.

8 − Position the 

pad assembly frame

 so that the 

tabs

are pointing outward. Align the drain extension on the
pad assembly with the 

drain spud

 in the 

humidifier

base

. Reinsert the 

humidifier pad assembly frame

in the 

base

. Push the 

pad assembly frame

 in at the

top until it snaps into place. Replace the 

front cover

.

Turn the damper handle to the WINTER" position.

9 − Remove  the 

drain hose

 from the bottom of the

humidifier. Bend and flex the hose to loosen any
internal calcium deposits. Flush the hose with water
under pressure and slip it back onto the drain spud.
The 

drain hose

 should have a constant downward

slope and must not be flattened or blocked.

10− Turn on water supply.
11− Check humidifier operation:

Manual Humidistat −

 Adjust humidistat to highest

setting and make sure the furnace blower is
operating. Humidifier will operate if RH is less than
50%. Check the humidifier for leaks during operation.
Adjust, if necessary.

Universal Humidistat −

 Check system operation by

setting the knob to 

TEST 

position. With furnace

blower operating and furnace calling for heat,
humidifier will operate for one minute. Press the

RESET 

button on the side of the control to reset the

Change Humidifier Pad" indicator. Check the
humidifier for leaks during operation. Adjust, if
necessary.

12− Set manual humidistat or universal humidistat to its

original position.

FIGURE 5

HUMIDIFIER BASE

HUMIDIFIER PAD

ASSEMBLY FRAME

(with frame tabs

pointing outward

and black mark 

facing up)

SOLENOID

VALVE

DRAIN HOSE

DISTRIBUTION

TRAY

DAMPER HANDLE

WINTER/SUMMER

ADJUSTMENT LEVER

(Close damper during

summer operation)

LATCH

TABS

FRONT COVER

TRAY COVER

HCWB2 Bypass Humidifier Parts Identification

(Right side discharge orientation shown)

DRAIN SPUD

DAMPER