background image

G61MPVT − 50hz

 / Page 3

FEATURES

HEATING SYSTEM − continued

Lennox Designed Flue Condensate Trap Assembly

Condensate trap assembly is mounted outside the
conditioned air stream.
Assembly can be mounted on either side of cabinet in
up−flow and down−flow applications. Assembly is mounted
on the bottom of the cabinet in horizontal applications. See
Installation Instructions.
Connection can be made with field provided 1/2 in. PVC
pipe, 3/4 in. PVC coupling, or 1−1/4 in. OD x 1 in. ID tubing
with hose clamp.
Easy to clean and winterize.

Inshot Burners

Aluminized steel inshot burners provide efficient,
trouble−free operation.
Burner venturi mixes air and gas in correct proportion for
proper combustion.
Burner assembly is removable from the unit as a single
component for ease of service.

Two−Stage Gas Control Valve

24 volt redundant combination two stage gas control
valve combines manual shut off valve (On−Off),
automatic electric valve (dual) and gas pressure
regulation into a compact combination control.

Flame Rollout Switch

Manual reset switches are factory installed on burner
box.
Switch provides protection from abnormal operating
conditions.

Hot Surface Mini−Nitride Ignitor

Unique, non−porous, high strength proprietary ceramic
material provides long life and trouble−free
maintenance.
Low mass element provides fast heat−up and consistent
igniter temperature with low power usage.
Cemented to alumina block for positive mounting and
protection against current leakage.
High temperature Teflon

®

 insulated ignition lead wires

for dependable operation.

Combustion Air Inducer

PSC, heavy−duty blower prepurges heat exchanger and
safely vents flue products.
Pressure switches prove blower operation before
allowing gas valve to open.
Operates only during heating cycle.

Limit Control

Automatic reset, primary and secondary limits are
accurately located.
Primary limit factory installed on vestibule panel on all
units, secondary limit factory installed on blower
housing.

OPTIONS

High Altitude Pressure Switch Kit

Required on certain units for proper unit operation on
installations above 610 m.
Units not approved for installations above 1372 m.
Order two per unit.

LPG/Propane Conversion Kit

Required for field changeover from natural gas to
LPG/Propane.

Natural Gas Conversion Kit

Required for field changeover from LPG/Propane to
natural gas.

CONTROLS

Integrated Two Stage / Variable Speed Blower
Control

Solid−state board contains all necessary controls and
relays to operate furnace.
Combustion air inducer is controlled by board. Prior to
ignition, a pre−purge cycle for 15 seconds is initiated.
After the main burners are turned off, a post−purge cycle
for 5 seconds is run.
Electronic flame sensor assures safe, reliable
operation.
Should flame fail to ignite, flame sensor will initiate 4
re−attempts at ignition before locking out unit operation
for 60 minutes.
Watchguard type circuit automatically resets ignition
controls after one hour of continuous thermostat
demand after unit lockout, eliminating nuisance calls for
service.
To aid in troubleshooting, the last three fault codes are
stored for a maximum of six months. Displays the fault
codes through indicator LED’s.
Jumper settings for 1 or 2 stage thermostat operation.
Two selectable 2nd stage recognition times (10 and 15
minutes) are available on the board when the furnace is
used with a single stage thermostat. When used with a
two stage thermostat, furnace will only initiate second
stage operation with a second stage thermostat
demand.
Two accessory terminals furnished for additional power
supply requirements for 240 volt (less than 1 amp)
power humidifiers and powered air cleaners.
Two blower speeds − second stage heat and second
stage cool (with four air volume selections for each) are
selected by DIP switches on board. Heat speed can be
adjusted to optimize discharge temperature. Cool
speed can be adjusted to correct optional cooling
capacity. See Blower Performance tables.
First stage blower speed is a percentage of 2nd stage
speed.
The ADJUST switch (DIP) allows normal (NORM), 10%
higher (+ plus) or 10% lower 

(

 minus) motor speed

selection within HEAT and COOL speeds selected for
fine tuning air volume.
DELAY switch (DIP) allows one of four de−humidification
profiles during cooling mode.

Profile A

 − Motor runs at 50% for 30 seconds, then at

82% for 7−1/2 minutes, then at 100% (if needed) until
demand is satisfied. Once demand is met, motor runs
at 50% for 30 seconds, then ramps down to stop.

Profile B

 − Motor runs at 82% for 7−1/2 minutes and

then at 100% (if needed) until demand is satisfied.
Once demand is met,motor ramps down to stop.

Profile C

 − Motor runs at 100% until demand is

satisfied. Once demand is met, motor runs at 100% for
60 seconds, then ramps down to stop.

Profile D

 − Motor runs at 100% until demand is satisfied.

Once demand is met, motor ramps down to stop.

In heat mode, blower on time is fixed at 45 seconds,
blower off time is adjustable from 60, 90, 120 and 180
seconds (factory setting − 90 seconds).

Power Lead

2.5 m power lead is provided for connection to an IEC
receptacle located on the right side of the furnace.

IEC Receptacle

IEC receptacle provided on right side of furnace cabinet
for easy, plug−in electrical connection.

24 Volt Transformer

Furnished and factory installed on blower wrapper.
40VA transformer has circuit breaker wired in series.

D

E

F

G

H

I

Summary of Contents for G61MPVT

Page 1: ...6 kW MODEL NUMBER IDENTIFICATION G 61 36 B 070 Unit Type G Gas Furnace Series 61 Two Stage Nominal Add On Cooling Capacity 36 10 5 kW 60 17 6 kW 1 Cabinet Width B 445 mm C 533 mm D 622 mm Gas Heat Inp...

Page 2: ...ir is supplied from outdoors and flue gases are discharged outdoors In Non Direct Vent applications combustion air is supplied from indoors and flue gases are discharged outdoors OPTIONS Termination K...

Page 3: ...for 15 seconds is initiated After the main burners are turned off a post purge cycle for 5 seconds is run Electronic flame sensor assures safe reliable operation Should flame fail to ignite flame sens...

Page 4: ...when blower compartment access door is removed Gas piping inlets are provided in both sides of cabinet Return Air Entry For bottom end return air entry for up flow horizontal applications remove furni...

Page 5: ...x 508 Blower Motor output W 373 745 745 745 kW of add on cooling 7 0 12 2 12 2 17 6 12 2 17 6 12 2 17 6 Air Volume Range L s 295 660 410 1020 350 1045 430 1035 Shipping Data kg 1 package 68 82 85 94...

Page 6: ...e collar The street ell must be included in the elbow count 3 135 models installed in down flow applications must have 80 to 50 mm 3 in to 2 in reducing elbow supplied installed directly into the flue...

Page 7: ...sed On horizontal installations the drain must be located at the bottom and the vent piping at the top FILTER AIR RESISTANCE For 25 mm Cleanable Filter Field Provided L s Pa 0 0 95 2 190 7 285 10 375...

Page 8: ...OPTIONAL RETURN CUTOUT Either Side Up Flow Only 1 NOTE 60C and 60D size units that require air volumes over 850 L s must have one of the following a Single side return air with transition to accommoda...

Page 9: ...C33 43B 724 1740 667 1683 CX34 43C 6F C33 43C 724 1740 654 1670 C33 44C 622 1638 546 1562 CX34 44 48B 6F C33 48B 622 1638 562 1578 CX34 44 48C 6F C33 48C 622 1638 546 1562 CX34 49C 6F C33 49C 749 176...

Page 10: ...RNACE A B 692 503 38 21 13 16 FLOOR OPENING 38 1 1 2 38 38 Front Of Furnace 559 C DOWN FLOW COMBUSTIBLE FLOOR BASE G61MPVT 50hz Page 10 OPTIONAL ACCESSORY DIMENSIONS MM Model No A B C G61MPVT 36B 070...

Page 11: ...metal strap must be field installed to support the weight of the termination kit FLASHING Not Furnished CLAMP GRADE Field Supplied ELBOW INTAKE AIR EXHAUST AIR TERMINATION ASSEMBLY Furnished 71M80 69...

Page 12: ...proper air velocity across the filter ADJUST Speed Switch Positions ADJUST Switch P iti Second Stage HEAT Speed L s Second Stage COOL Speed L s S tc Positions 1 1 2 3 4 1 2 3 1 4 685 775 860 970 745...

Page 13: ...ttom Return Air Return Air from Both Sides or Return Air from Bottom and One Side ADJUST Speed Switch Positions ADJUST Switch P iti Second Stage HEAT Speed L s Second Stage COOL Speed L s S tc Positio...

Page 14: ......

Page 15: ......

Page 16: ...nd Dimensions subject to change without notice and without incurring liability Improper installation adjustment alteration service or maintenance can cause property damage or personal injury Installat...

Reviews: