background image

Page 24

9. Combustion Air Inducer (B6)

All G50UH(X) units use a combustion air inducer to move
air through the burners and heat exchanger during heating
operation. The blower uses a 120VAC motor. The motor
operates during all heating operation and is controlled by
furnace control A92. The inducer also operates for 15 sec-
onds before burner ignition (pre-purge) and for 5 seconds
after the gas valve closes (post-purge).

A proving switch connected to the combustion air inducer ori-
fice  plate is used to prove inducer operation. The combus-
tion air inducer orifice will be different for each model. See
table 9 for orifice sizes. The switch monitors air pressure in
the inducer housing. During normal operation, the pressure
in the housing is negative. If pressure becomes less negative
(signifying an obstruction) the proving switch opens.  When
the proving switch opens, the furnace control (A92) immedi-
ately closes the gas valve to prevent burner operation.

TABLE 9

G50UH(X) Unit

C.A.I. Orifice Size

24A−045

1 1/4"

24A/36A−070

1 7/16"

48B−070

1 1/2"

36B, 48B−090

1 11/16"

48C, 60C−110 (−1, −2, −3 units)

1  7/8"

48C, 60C−110 (−4, −5 units)

2 5/32"

36C−110

2 5/32"

48C, 60D−135 (−6 and later)

(−1 to −5 units)

2  3/8"

(2 5/32")

60D−155

2.60"

Horizontal Applications

The G50UH(X) furnace can be installed in horizontal ap-
plications.

The combustion air inducer may be rotated clockwise or
counterclockwise by 90° to allow for vertical vent dis-
charge in a horizontal application. Remove the four mount-
ing screws, rotate the assembly  (assembly consists  of ori-
fice plate, proving switch, gasket and combustion air in-
ducer), then reinstall the mounting screws. See figure 13.
Use the provided wire tie to bundle the pressure switch
wires with the inducer motor power leads.

 Route the wires

away from moving parts and the heat of the inducer

motor to prevent damage to the wires. 

Use sheet metal

shears to remove the cut out from the side of the cabinet.
See figure 14. Use the two provided sheet metal screws to
install the cut out on the top cap to cover the original flue
outlet opening.

FIGURE 13

Combustion Air Inducer

(Upflow Position)

Mounting Screws

MOUNTING SCREWS

90°

90°

(Remove)

(Remove)

Power Leads

Flue Transition

(Do not remove

)

G50UH−15 and later assembly Shown

Flue Outlet Hole

(

Reattach

Cutout Here)

Supply Air

Opening

Top View of Furnace

Top Cap

Cut out

Optional

Flue Outlet

Optional Flue Outlet

(Horizontal Installation)

FIGURE 14

Summary of Contents for G50UH Series

Page 1: ...n only and do not supersede or replace local or state codes In the absence of local or state codes the guidelines and procedures outlined in this manual except where noted are recommended only and do...

Page 2: ...CH33 36B 2F CH33 42B 2F CH33 44 48B 2F Electrical characteristics 120 volts 60 hertz 1 phase less than 12 amps OPTIONAL ACCESSORIES MUST BE ORDERED EXTRA Air Filter and Rack Kit Number and size of fi...

Page 3: ...36C 2F CH33 48C 2F CH33 50 60C 2F Electrical characteristics 120 volts 60 hertz 1 phase less than 12 amps OPTIONAL ACCESSORIES MUST BE ORDERED EXTRA Air Filter Rack Kit Horizontal end 87L96 1 18 x 25...

Page 4: ...g Base Dimensions H x W x D 4 x 21 5 8 x 28 5 8 in 102 x 549 x 727 mm 4 x 24 5 8 x 28 5 8 in 102 x 625 x 727 mm Number and size of field provided fil ter 20 x 25 x 1 in 508 x 635 x25 mm 24 x 24 x 1 in...

Page 5: ...6K63 1 16 x 25 x 1 406 x 635 x 25 EZ Filter Base Catalog Number Shipping Weight 73P57 8 lbs 4 kg 73P58 10 lbs 5 kg Base Dimensions H x W x D 4 x 21 5 8 x 28 5 8 in 102 x 549 x 727 mm 4 x 24 5 8 x 28 5...

Page 6: ...with 1 in 25 mm cleanable filter not furnished field provided in place Also see Filter Air Resistance table G50UH 24A 070 PERFORMANCE External Static Air Volume Watts at Various Blower Speeds Externa...

Page 7: ...h 1 in 25 mm cleanable filter not furnished field provided in place Also see Filter Air Resistance table G50UH 36B 090 PERFORMANCE External Static Air Volume Watts at Various Blower Speeds External St...

Page 8: ...555 1265 595 459 40 100 1820 860 699 1670 790 611 1470 695 525 1255 590 443 50 125 1740 820 664 1600 755 575 1420 670 496 1215 575 414 60 150 1635 770 624 1530 720 544 1350 635 464 1175 555 400 70 17...

Page 9: ...t with 1 in 25 mm cleanable filter not furnished field provided in place Also see Filter Air Resistance table G50UH 48C 135 PERFORMANCE External Static Air Volume Watts at Various Blower Speeds Extern...

Page 10: ...filter not furnished field provided in place Also see Filter Air Resistance table G50UH 60C 110 1 2 3 PERFORMANCE Single Side Return Air Air volumes in bold require field fabricated transition to acc...

Page 11: ...60 667 30 75 2205 1040 1218 2075 980 924 1860 875 782 1605 755 655 40 100 2130 1005 1189 2005 945 905 1815 855 752 1595 750 636 50 125 2045 965 1159 1920 905 864 1750 825 726 1565 740 619 60 150 1955...

Page 12: ...tts 00 0 2715 1280 1407 2255 1065 1070 1910 900 850 1660 785 674 10 25 2640 1245 1403 2250 1060 1030 1900 895 834 1645 775 668 20 50 2540 1200 1355 2245 1060 1006 1890 890 821 1630 770 665 30 75 2480...

Page 13: ...nable filter not furnished field provided in place Also see Filter Air Resistance table G50UH 60D 155 1 2 3 PERFORMANCE Single Side Return Air Air volumes in bold require field fabricated transition t...

Page 14: ...r Air volumes in bold require field fabricated transition to accom modate 20 x 25 x 1 in 508 x 635 x25 mm cleanable air filter in order to maintain proper air velocity External Static Air Volume Watts...

Page 15: ...10 0 2 49 HIGH ALTITUDE G50UH 1 1 High Altitude Orifice Kit Natural Gas Only High Altitude Prove Switch Kit LPG Propane Kit G50UH 1 to 14 Natural Gas Only 4501 7500 ft 1373 2286m 7501 10 000 ft 2287...

Page 16: ...Burner Bottom Shield Limit Shield Secondary Limit as required NOx Units Only G50UH X PARTS ARRANGEMENT UP FLOW POSITION FIGURE 1 Gas Manifold 135 and 155 kBtuh units only Flame rollout switches are lo...

Page 17: ...HEATING COMPONENTS COMBUSTION AIR INDUCER PROVE SWITCH PRIMARY LIMIT PRIMARY LIMIT SHIELD GAS VALVE ROLLOUT SWITCHES MANIFOLD BURNER ASSEMBLY NOx Insert NOx Units Only HEAT EXCHANGER FLUE COLLECTOR B...

Page 18: ...also located in the control box The switch provides overcurrent protection to the trans former T1 The breaker is rated 3A at 32V If the cur rent exceeds this limit the breaker will trip and all unit...

Page 19: ...times with an inter purge and warm up time between trials of 35 seconds Af ter a total of five trials for ignition including the initial trial the control goes into Watchguard Flame Failure mode Af t...

Page 20: ...4 shows 24 volt and 120 volt control terminal designations Tables 5 and 6 show jack plug terminal designations See table 8 for troubleshooting diagnostic codes Units equipped with the SureLight system...

Page 21: ...ight control utilizes less power to energize the ignitor on successive calls for heat The control continues to ramp down the voltage to the ignitor until it finds the lowest amount of power that will...

Page 22: ...tor improperly attached ON ON ON OFF Circuit board failure or control wired incorrectly OFF ON y FAST FLASH SLOW FLASH Main power polarity reversed Switch line and neutral SLOW FLASH FAST FLASH Low fl...

Page 23: ...the board voltage cannot be measured so ignitor must be ohmed Ohm value should be 10 9 to 19 7 See figure 12 for ignitor location NOTE The G50UH X furnace contains electronic components that are polar...

Page 24: ...60C 110 4 5 units 2 5 32 36C 110 2 5 32 48C 60D 135 6 and later 1 to 5 units 2 3 8 2 5 32 60D 155 2 60 Horizontal Applications The G50UH X furnace can be installed in horizontal ap plications The comb...

Page 25: ...nace control energizes the supply air blower and closes the gas valve The limit automatically resets when unit tempera ture returns to normal The switch must reset within three min utes or SureLight...

Page 26: ...throw proving switch elec trically connected to the furnace control The purpose of the switch is to prevent burner operation if the combustion air inducer is not operating or if the flue becomes obstr...

Page 27: ...rical power to unit if service is to be performed 3 Remove access panel 4 Switch lever on White Rodgers gas valve to OFF turn knob on Honeywell valve clockwise to OFF Do not force 5 Replace access pan...

Page 28: ...anifold pres sure settings Manifold Adjustment Procedure 1 Connect a test gauge to outlet pressure tap on gas valve See figures 15 16 and 17 Start unit and allow 5 minutes for unit to reach steady sta...

Page 29: ...AD TO IGNITION CONTROL SENSOR WIRE FIGURE 20 TABLE 16 FLAME SIGNAL in MICROAMPS SureLight Normal Low Drop Out 56L83 97L48 0 61 0 21 0 60 0 20 69M15 0 31 0 25 0 30 0 24 V TYPICAL OPERATING CHARACTERIST...

Page 30: ...COOL terminal The con tinuous blower tap is connected to the FAN terminal To change existing heat tap turn off power then switch out speed tap on HEAT with tap connected to one of two PARK terminals S...

Page 31: ...n air inducer Leaving off screws may cause leaks 13 Clean burner by running a vacuum with a soft brush at tachment over face of burners Visually inspect inside of burners and crossovers for any blocka...

Page 32: ...2 minutes or control goes into 5 minute Watchguard Pressure Switch delay Once S18 closes a 15 second pre purge follows 4 SureLight control A92 energizes ignitor A 20 second warm up period begins 5 Ga...

Page 33: ...oes into 5 minute Watchguard Pressure Switch delay Once S18 closes a 15 second pre purge follows 4 SureLight control A92 energizes ignitor A 20 second warm up period begins 5 Gas valve opens for a 4 s...

Page 34: ...COMBUSTION AIR INDUCER OFF INDOOR BLOWER OFF WITH DELAY LED 1 OFF LED 2 SLOW FLASH Sequence holds until PROVE switch closes or thermostat resets control NO NO YES NO IS THERE PROPER GROUND IS VOLTAGE...

Page 35: ...CER OFF INDOOR BLOWER OFF WITH DELAY LED 1 ALT SLOW FLASH LED 2 ALT SLOW FLASH IS 60 MINUTE RESET PERIOD COMPLETE YES 4 SECONDS YES HAS CONTROL RESET IGNITION SEQUENCE FOUR TIMES FLAME SIGNAL NORMAL S...

Page 36: ...ACTOR AND SYSTEM FAN ENERGIZED AFTER DELAY Control 69M15 2 second delay Control 56L83 97L48 0 second delay COOL SPEED AND ELECTRONIC AIR CLEANER TERMINAL IS ENERGIZED COMPRESSOR OFF THERMOSTAT OPENS C...

Page 37: ...OPENS COMBUSTION AIR INDUCER AND HEATING ACCESSORY TERMINAL ARE DE ENERGIZED INDOOR BLOWER SWITCHES TO COOL SPEED THERMOSTAT OPENS INDOOR BLOWER SWITCHES TO CONTINUOUS BLOWER ELECTRONIC AIR CLEANER T...

Page 38: ...ION 1 Manually reset the roll out switch by pushing the top button ACTION 2 Determine the cause of the roll out switch activation before leaving furnace code LED 1 O 1 2 2 Roll out switch failure ACTI...

Page 39: ...1997 combustion air inducer will cycle 5 seconds on 55 seconds off LED 1 Alternating Fast Flash LED 2 Alternating Fast Flash 2 1 2 Broken or failed ignitor ACTION 1 Unplug ignitor and read resistance...

Page 40: ...ing demand Diagnostic lights flash the pressure switch failure code 2 5 minutes after heating demand 4 1 2 Prove switch does not close due to obstructions in the pressure lines ACTION 1 Remove any obs...

Page 41: ...ssure switch code LED 1 Off LED 2 Slow Flash 6 1 1 Low pressure differential at the prove switch ACTION 1 Check for restricted exhaust vent Remove all blockage ACTION 2 Check for proper vent sizing Se...

Page 42: ...6 3 3 Insufficient flow through the heat ex changer caused by a sooted or re stricted heat exchanger ACTION 1 Check for sooting deposits or other restrictions in the heat exchanger assembly Clean asse...

Page 43: ...Properly locate the sense rod or replace if rod cannot be located correctly sense code LED 1 Slow Flash LED 2 Fast Flash 7 1 2 Sense rod is contaminated ACTION 1 Check sense rod for contamination or...

Reviews: