Blower Performance

NOTE − All air data is measured external to unit with 1 in. cleanable filter (not furnished − field provided) in place.

G40DF−48C−110 PERFORMANCE

External

Static

Pressure

in. w.g.

Air Volume / Watts at Different Blower Speeds

High

Medium−

High

Medium−

Low

Low

cfm Watts cfm Watts cfm Watts cfm Watts

0.00

2035

846

1790

712

1510

595

1225

477

0.05

2000

825

1760

694

1495

581

1225

470

0.10

1970

803

1730

675

1475

567

1220

463

0.15

1925

781

1710

657

1475

555

1220

455

0.20

1880

758

1685

638

1465

542

1215

447

0.25

1835

736

1655

618

1440

528

1200

437

0.30

1795

714

1625

597

1420

514

1185

427

0.40

1680

669

1550

564

1360

483

1135

400

0.50

1620

630

1445

524

1280

447

1065

371

0.60

1445

592

1310

479

1165

404

1000

343

0.70

1290

545

1180

434

1055

369

905

319

0.80

1155

502

1065

406

955

348

815

296

0.90

1010

472

930

372

840

320

690

265

G40DF−60C−110 PERFORMANCE

External

Static

Pressure

in. w.g.

Air Volume / Watts at Different Blower Speeds

High

Medium−

High

Medium−

Low

Low

cfm Watts cfm Watts cfm Watts cfm Watts

.00

2475 1276 2280

987

1995

845

1690

698

.10

2390 1248 2235

955

1990

829

1675

690

.20

2330 1223 2180

945

1975

809

1665

675

.30

2245 1192 2125

911

1940

786

1660

657

.40

2175 1187 2050

880

1895

757

1650

636

.50

2085 1145 1970

849

1835

734

1625

619

.60

2020 1129 1880

815

1750

695

1580

599

.70

1920 1094 1775

785

1660

669

1525

579

.80

1785 1052 1685

762

1585

645

1440

556

.90

1670 1020 1600

741

1520

633

1370

538

G40DF−60D−135 PERFORMANCE

External

Static

Pressure

in. w.g.

Air Volume / Watts at Different Blower Speeds

High

Medium−High

Medium−Low

Low

cfm

Watts

cfm

Watts

cfm

Watts

cfm

Watts

.00

2660

1379

2325

1059

1960

864

1655

684

.10

2560

1353

2310

1030

1945

840

1640

667

.20

2490

1325

2280

1000

1940

824

1630

661

.30

2415

1293

2225

972

1930

801

1625

649

.40

2345

1264

2170

941

1910

779

1620

638

.50

2265

1235

2115

918

1870

754

1615

624

.60

2165

1199

2020

880

1830

733

1585

604

.70

2050

1160

1940

854

1755

705

1570

604

.80

1955

1112

1865

828

1680

683

1515

584

.90

1865

1096

1760

797

1605

656

1465

567

Summary of Contents for G40DF Series

Page 1: ...Blower Performance 26 Service 28 Planned Service 30 Repair Parts List 30 Ignition Control Board Diagnostic Codes 31 Troubleshooting 32 G40DF X Start Up Performance Check List 35 WHAT TO DO IF YOU SMEL...

Page 2: ...7 8 124 Right 2 1 4 57 Left 40 1016 3 3 4 95 5 8 16 AIR FLOW 5 8 16 3 4 19 19 1 2 495 5 8 16 B 5 8 16 5 8 16 Supply Air Supply Air Model No A B C D in mm in mm in mm in mm G40DF X 24A 045 G40DF X 36A...

Page 3: ...Flue Collector Box Gasket Combustion Air Inducer Gasket Manifold Burner Gas Valve Flame Rollout Switches Flame Sensor Primary Limit Igniter Heat Exchanger Igniter Bracket Combustion Air Pressure Swit...

Page 4: ...d other applicable local codes Adequate clearance must be made around the air open ings into the vestibule area In order to ensure proper unit operation combustion and ventilation air supply must be p...

Page 5: ...rating plate D One hundred percent 100 outdoor air must be pro vided for combustion air requirements during construc tion Temporary ducting may supply outdoor air to the furnace Do not connect duct d...

Page 6: ...B149 installation codes CAUTION Do not install the furnace in a corrosive or contami nated atmosphere Meet all combustion and ventila tion air requirements as well as all local codes All gas fired ap...

Page 7: ...communicate di rectly or by ducts with the outdoors or spaces crawl or at tic that freely communicate with the outdoors or indirectly through vertical ducts Each opening shall have a minimum free are...

Page 8: ...pply flue and air intake connections and sufficient installation and servicing clearances See table 1 for correct floor opening size 2 Flange warm air plenum and lower the plenum into the opening 3 Se...

Page 9: ...re 8 5 Make certain that an adequate seal is made SECURE FROM INSIDE CABINET HEMMED EDGE FIBERGLASS SEALING STRIP Field Provided CABINET SIDE PANEL PLENUM Side View FIGURE 8 Setting Equipment WARNING...

Page 10: ...m filter sizes A filter must be in place any time the unit is operating TABLE 3 Furnace Cabinet Size Return Air Filter Size inches 14 1 2 14 X 25 X 1 1 17 1 2 16 X 25 X 1 1 21 20 X 25 X 1 1 24 1 2 24...

Page 11: ...or dedicated gas vent Unlined masonry chimneys are prohibited See figures 11 and 12 for com mon venting A chimney with one or more sides exposed to the outside of the structure is considered to be an...

Page 12: ...ney passageway must be checked periodically to ensure that it is clear and free of obstructions Do not install a manual damper barometric draft regulator or flue restrictor between the furnace and the...

Page 13: ...fastened by screws or other approved means 12 When the vent connector used for Category I ap pliances must be located in or pass through a crawl space or other areas which may be cold that portion of...

Page 14: ...22 339 5 22 65 30 130 39 219 49 330 10 29 59 40 121 51 206 64 315 15 35 53 48 112 61 195 76 301 20 0 0 97 0 202 0 349 0 540 2 10 75 14 149 18 250 20 377 5 21 71 29 143 38 242 47 367 10 28 64 38 133 50...

Page 15: ...225 115 337 5 51 63 75 128 102 216 144 326 10 NR NR 95 116 128 201 182 308 15 NR NR NR NR 158 186 220 290 20 0 35 96 54 200 78 346 114 537 2 37 74 56 148 78 248 113 375 5 50 68 73 140 100 239 141 363...

Page 16: ...1 21 50 33 89 47 142 64 220 2 22 53 35 96 49 153 66 235 3 24 55 36 102 51 163 68 248 20 1 21 54 33 99 46 157 62 246 2 22 57 34 105 48 167 64 259 3 23 60 35 110 50 176 66 271 30 1 20 62 31 113 45 181...

Page 17: ...rat ing and the other appliances which are not operating re main connected to the common venting system If the venting system has been installed improperly you must correct the system as indicated in...

Page 18: ...ng must be resistant to the actions of liquified petro leum gases NOTE Install a 1 8 inch NPT plugged tap in the field piping upstream of the gas supply connection to the unit The tap must be accessib...

Page 19: ...sting pressure of gas lines gas valve must be disconnected and isolated See figure 15 Gas valves can be damaged if subjected to pressures greater than 1 2 psig 3 48 kPa 14 inches w c MANUAL MAIN SHUT...

Page 20: ...correctly and is properly grounded One line voltage EAC terminal is provided on the fur nace control board Any electronic air cleaner rated up to one amp can be connected to this terminal with the ne...

Page 21: ...TERMINAL DESIGNATIONS HUM LINE XFMR EAC COOL HEAT PARK FLAME NEUTRALS Humidifier 120VAC Input 120VAC Transformer 120VAC Electronic Air Cleaner 120VAC Blower Cooling Speed 120VAC Blower Heating Speed 1...

Page 22: ...Page 22 G40DF X Typical Schematic Wiring Diagram FIGURE 21...

Page 23: ...ersonal injury or death Gas Valve Operation Figures 22 23 and 24 1 STOP Read the safety information at the beginning of this section 2 Set the thermostat to the lowest setting 3 Turn off all electrica...

Page 24: ...uence then restarts at step 1 Gas Pressure Adjustment Gas Flow Approximate 1 Operate unit at least 15 minutes before checking gas flow Determine the time in seconds for one revolu tions of gas through...

Page 25: ...an Control There is no cooling mode fan on delay however there is a cooling fan off delay of 45 seconds This delay is not adjust able The heating mode fan on time of 45 seconds is not adjust able The...

Page 26: ...m Watts cfm Watts 0 00 1475 616 1345 554 1150 495 990 415 0 05 1450 606 1320 543 1140 481 985 407 0 10 1425 595 1300 532 1125 466 975 398 0 15 1395 585 1275 521 1115 452 970 390 0 20 1375 574 1255 510...

Page 27: ...g Air Volume Watts at Different Blower Speeds High Medium High Medium Low Low cfm Watts cfm Watts cfm Watts cfm Watts 00 2475 1276 2280 987 1995 845 1690 698 10 2390 1248 2235 955 1990 829 1675 690 2...

Page 28: ...ective covering in front of the fur nace during cleaning Cleaning the heat exchanger requires a steel spring snake a reversible drill and a vacuum cleaner The steel spring snake may be constructed usi...

Page 29: ...place all screws may cause leaks 16 To clean the burner run a vacuum cleaner with a soft brush attachment over the face of burners Inspect in side the burners and crossovers for any blockage Clean the...

Page 30: ...nace until the items can be repaired or replaced Instruct the homeowners to pay attention to their furnace Situations can arise between annual furnace in spections that may result in unsafe operation...

Page 31: ...Pressure switch closed prior to activation of combustion air inducer ALTERNATING SLOW FLASH ALTERNATING SLOW FLASH Watchguard burners failed to ignite or lost flame 5 times during single heating dema...

Page 32: ...VE OFF COMBUSTION AIR INDUCER ON INDOOR BLOWER ON HEATING SPEED LED 1 SLOW FLASH LED 2 OFF GAS VALVE OFF COMBUSTION AIR INDUCER OFF INDOOR BLOWER OFF WITH DELAY LED 1 OFF LED 2 SLOW FLASH Sequence hol...

Page 33: ...LE HEAT DEMAND WATCHGUARD MODE GAS VALVE OFF COMBUSTION AIR INDUCER OFF INDOOR BLOWER OFF WITH DELAY LEDs SIGNAL WATCHGUARD FAILURE CODE IS 60 MINUTE RESET PERIOD COMPLETE YES 4 SECONDS YES HAS CONTRO...

Page 34: ...TCH CLOSED LED SLOW FLASH RATE REMAINS UNCHANGED THROUGHOUT COOLING CYCLE THERMOSTAT CALLS FOR COOLING COMPRESSOR CONTACTOR AND SYSTEM FAN ENERGIZED WITH 2 SECOND DELAY COOLING SPEED EAC TERM ENERGIZE...

Page 35: ...WITH COMB AIR INDUCER SYSTEM FAN REMAINS ON HEATING SPEED SYSTEM FAN REMAINS ON HEATING SPEED HUM TERM DE ENERGIZES WITH COMB AIR INDUCER G40DF X Start Up Performance Check List Filter Clean Secure El...

Reviews: