Page 8
SURELIGHT CONTROL BOARD
FIGURE 8
SURELIGHT CONTROL TERMINAL DESIGNATIONS
ACB COOL
ACB HEAT
PARK
ACB LOW
ACC
TX
HOT
HTG ACC
NEUTRALS
24VAC HOT
24VAC RTN
FLAME SENSE
Blower − Cooling Speed (Line Volt)
Blower − Heating Speed (Line Volt)
Alternate Blower Speeds (Dead)
Continuous Low Speed Blower
Accessory Terminal (Line Volt)
120VAC Hot to Transformer
120VAC Hot Input
Heat Only Accessory (Line Volt)
120VAC Neutrals
24VAC Hot from Transformer
24VAC Return from Transformer
Flame Sense Terminal
TABLE 1
FIGURE 9
SURELIGHT IGNITOR
13/32’
5/8"
MEASUREMENT IS TO I.D.
OF RETENTION RING
TABLE 2
DIAGNOSTIC CODES
MAKE SURE TO ID LED’S CORRECTLY: REFER TO INSTALLATION INSTRUCTIONS FOR CONTROL BOARD LAYOUT.
LED #1
LED #2
DESCRIPTION
SIMULTANEOUS
SLOW FLASH
SIMULTANEOUS
SLOW FLASH
Power − Normal operation
Also signaled during cooling and continues fan.
SIMULTANEOUS FAST
FLASH
SIMULTANEOUS FAST
FLASH
Normal operation − signaled when heating demand initiated at thermostat.
SLOW FLASH
ON
Primary or Secondary limit open. Units with board 63K8901 or 24L85: Limit must
close within 5 trials for ignition or board goes into one hour limit Watchguard. Units
with board 56L83 or 97L48: Limit must close within 3 minutes or board goes into
one hour limit Watchguard.
OFF
SLOW FLASH
Pressure switch open or has opened 5 times during a single call for heat; OR:
Blocked inlet/exhaust vent; OR: Condensate line blocked; OR: Pressure switch
closed prior to activation of combustion air blower.
ALTERNATING SLOW
FLASH
ALTERNATING SLOW
FLASH
Watchguard − burners fail to ignite.
SLOW FLASH
OFF
Flame sensed without gas valve energized.
ON
SLOW FLASH
Rollout switch open. OR: 9 pin connector improperly attached.
ON
ON
OFF
ON
OFF
ON
Circuit board failure or control wired incorrectly.
FAST FLASH
SLOW FLASH
Main power polarity reversed. Switch line and neutral.
SLOW FLASH
FAST FLASH
Low flame signal. Measures below .61 microAmps. Replace flame sense rod.
ALTERNATING FAST
FLASH
ALTERNATING FAST
FLASH
Improper main ground or line voltage below 75 volts; OR: Broken ignitor; OR:
Open ignitor circuit.
NOTE − Slow flash equals 1 Hz (one flash per second). Fast flash equals 3 Hz (three flashes per second). Drop out flame sense current < 0.21microAmps