![Lennox G17Q2-50 Unit Information Download Page 13](http://html.mh-extra.com/html/lennox/g17q2-50/g17q2-50_unit-information_1877426013.webp)
Page 13
CHECK:
1-UNIT POWER
2-INTERLOCK SWITCH
3-TRANSFORMER
4-LIMIT SWITCH
START
IS
24VAC ACROSS
R & T?
YES
JUMPER ACROSS
SCREWS R & G
YES
DOES UNIT
OPERATE?
NO
NO
IS
BLOWER
RUNNING ON HIGH
SPEED?
NO
IS
120VAC ACROSS
N1 & A?
REPLACE
BCC2-1
NO
YES
YES
CHECK BLOWER
WIRING AND
BLOWER
IS
120VAC ACROSS
N1 & ACC?
NO
REPLACE
BCC2-1
YES
JUMPER ACROSS
R &W
(REMOVE R & G JUMPER)
IS
DAMPER MOTOR
ON?
NO
REPLACE
BCC2-1
NO
IS
120VAC ACROSS
N1 & CAB?
CHECK
DAMPER MOTOR
WIRING AND
DAMPER MOTOR
YES
YES
ARE
BURNERS
LIT?
NO
CHECK:
1-DAMPER MOTOR
2-IGNITION CONTROL
3-GAS VALVE
4-IGNITOR
5-LIMIT SWITCHES
6-PROVE SWITCH
YES
IS BLOWER
RUNNING ON LOW
SPEED, 45 SEC.
AFTER FURNACE
LIGHTS?
NO
IS
120VAC ACROSS
N1 & H?
YES
IS
24VAC ACROSS
T & V?
REPLACE
BCC2-1
NO
NO
CHECK
WIRING
YES
IS
120VAC ACROSS
N1 & ACC?
YES
REMOVE
R & W JUMPER
AFTER
THE SELECTED
TIME, DOES THE
BLOWER TURN
OFF?
YES
NO
YES
REPLACE
BCC2-1
END OF TEST
BCC2-1
TROUBLESHOOTING
FLOWCHART
NO
REPLACE
BCC2-1
CHECK BLOWER
WIRING AND
BLOWER
FIGURE 15