background image

12

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

Table 2

Lower Front 2” Filler Panel

The FireStar™ insert comes with a 2” panel to fill the space between the 

insert bottom and the hearth extension.  If the hearth elevations necessitate, 

the insert may be installed directly on the hearth without the leveling bolts 

or filler panel.  To install the panel, insert the four tabs on the top of the 

panel into the corresponding slots in the insert bottom.  Open the insert 

side doors, remove the two socket head screws from the hardware bag 

and install them (using a 5/32” hex wrench) through the insert bottom 
into the filler panel.  A tall adjustable filler panel is also available.

Gas Line Installation

After leveling, position the insert in the fireplace, holding it about six 
inches out from its final location.  

CAUTION: Specific Hearth Requirements apply (see Clearances 

and Specifications). 

The Firestar gas insert must be connected to the gas line in 

accordance with local codes and / or the National Fuel Gas 

Code, Z223.1-latest edition, also known as NFPA 54 

(In Canada, 

the current CAN/CSA  B149.1 installation code)

. Included in the 

manual package is an 8" gas nipple.  Locate the threaded gas 

inlet on the lower left of the insert.  Thread the 8" gas nipple 

into the inlet with a teflon sealer or equivalent.  Attach the gas 

supply line to this hard pipe.  The hard pipe can receive a 3/8” 

inch female iron pipe coupling, or a shut off valve. After con-

necting the gas line, all joints in the line and connections at 

the valve should be checked for leaks before final positioning 

of the unit. Conduct a gas leakage test of the appliance piping 

and control system downstream of the shutoff valve in the supply 

line to the appliance.

Gas Pressure Requirements

A  MAJOR  CAUSE  OF  OPERATING  PROBLEMS  WITH  GAS 

APPLIANCES I !
The most important item to check during the initial installation 

and the first thing to check when operating problems occur is 

gas pressure! This appliance will not function properly unless 

the  required  gas  pressure  is  supplied.  See  Table  1  for  gas 

pressure requirements. 

Two pressure taps are provided on the insert's valve to check gas pressures. 
The taps are located below the on/off/pilot knob (see 

Figure 14

). The left 

tap is the inlet (supply) pressure side. To check inlet pressure (with the 
insert burning), insert a small phillips screwdriver into the tap and turn a 
half turn counter-clockwise. Cover the tap with the line from a manometer 
and check the pressure. Close 
tap  gently  but  securely  after 
completing  the  check.  The 
manifold (outlet) tap is to the 
right of the inlet tap.

Gas Supply Line Sizing

The proper gas line diameter must be selected to run from the supply regu-

lator to the insert.  Refer to the Table 2 for proper gas pipe diameters.

Note:  

Some areas allow copper tubing - check with local approval agen-

cies and codes.  

COPPER  TUBING  NOT  ALLOWED  IN  MASSACHUSETTS  IN 

NATURAL GAS INSTALLATIONS, NEVER USE GALVANIZED OR 

PLASTIC PIPES.

Fuel                     

Type

Inlet Pressure

Manifold Pressure

Desired Minimum Maximum

On Hi 

Fire

On Lo 

Fire

Natural

Gas

7" WC

5" WC

10.5" WC

3.5" WC

1.7" WC

LP Gas 11" WC 10.5" WC

13" WC

10.0" WC 5.4” WC

Table 1

12

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

1

/

2

"

(1.3 cm)

7

/

8

"

(2.3 cm)

3

/

4

"

(2.0 cm)

3

/

4

"

(2.0 cm)

150-200

3

/

4

"

(2.0 cm)

100-150

1

/

2

"

(1.3 cm)

7

/

8

"

(2.3 cm)

3

/

4

"

(2.0 cm)

1

/

2

"

(1.3 cm)

3

/

4

"

(2.0 cm)

1

/

2

"

(1.3 cm)

1

/

2

"

(1.3 cm)

40-100

1

/

2

"

(1.3 cm)

5

/

8

"

(1.6 cm)

1

/

2

"

(1.3 cm)

10-40

3

/

8

"

(1.0 cm)

1

/

2

"

(1.3 cm)

3

/

8

"

(1.0 cm)

1

/

2

"

(1.3 cm)

0-10

Natural Gas

Natural Gas

L.P.

L.P.

Pipe Length

(Feet from Supply 

Regulator)

(Do Not Use Copper in Massachusetts 

with Natural Gas)

Tubing, Type L Outside Diam-

eter (Copper)

Schedule 40 Pipe

Inside Diameter

(Black Pipe)

1

/

2

"

(1.3 cm)

Gas Line Installation

After leveling, position the insert in the fireplace --- holding it 

about six inches out from its final location.

Caution: Specific Hearth Requirements apply (see Clearances 

and Specifications). The 

Designer™

 must be connected to the 

gas line in accordance with local codes and / or the National Fuel 
Gas Code--- 

Z223.1-latest edition, also known as NFPA 54 

(In Canada, the current CAN/CSA  B149.1 installation code)

.

Included in the manual package is a 8" gas nipple.  Locate the 

threaded gas inlet on the lower left of the insert.  Thread the 

8" gas nipple into the inlet with a teflon sealer or equiv.  Attach 

the gas supply line to this hard pipe.  The hard pipe can receive 

a 3/8” inch female iron pipe coupling, or a shut off valve. After 

connecting the gas line, all joints in the line and connections 

at the valve should be checked for leaks.

G

as

s

upply

l

ine

s

izinG

The proper gas line diameter must be selected to run from the 

supply regulator to the stove.  Refer to the following table for 

proper gas pipe diameters.

NOTE:  Some areas allow copper tubing - check with local approval 

agencies and codes.

COPPER  TUBING  NOT  ALLOWED  IN  MASSACHUSETTS  IN 

NATURAL GAS INSTALLATIONS, NEVER USE GALVANIZED OR 

PLASTIC PIPES.

Figure 14

To check manifold pressure (with the insert burning at the high burn 
setting) insert a small phillips screwdriver into the tap and turn a half 
turn counter-clockwise. Cover the tap with the line from the manometer 
and check the pressure. Again close the tap gently but securely after 
completing the check. Check the taps for gas leaks with a gas leak test 
solution (retighten if necessary). 
If the pressure is not sufficient, make sure the gas supply line is large 
enough, the supply regulator is properly adjusted and the total gas load 
for the residence does not exceed the amount supplied. 
Propane tanks are at pressures that will cause damage to valve com-

ponents.  Verify that the tanks have step down regulators to reduce the 

pressure to safe levels.

Inlet

Pressure

Tap

Inlet Elbow

Off/On/Pilot

Manifold 

Pressure Tap

Flame Height

Adjustment

Outlet

Orifice

These appliances must be isolated from the gas supply piping system 

(by closing their individual manual shut-off valve) during any pressure 

testing of the gas supply piping system at test pressures equal to or 

less than

 1/2 psig (3.5 kPa).

These appliances and their individual shut-off valves must be discon-

nected from the gas supply piping system during any pressure testing 

of that system at pressures 

greater than

 1/2 psig (3.5 kPa).

Summary of Contents for FIRESTAR MERIT GC3

Page 1: ...an interrupteur Ne pas vous servir des t l phones se trouvant dans le b timent o vous trouvez Appelez imm diatement votre fournisseur de gaz depuis un voisin Suivez les instructions du fournis seur Si...

Page 2: ...10 Log Installation 10 Surround Panels Installation 11 Lower Front Filler Panel 12 Gas Line Installation 12 Gas Pressure Requirements 12 Gas Supply Line Sizing 12 LP and Natural Gas Supplies 13 Air Sh...

Page 3: ...ting controls is danger ous WARNING Clothing or other flammable material should not be placed on or near the appliance AVERTISSEMENT On ne devrait pas placer de v tements ni d autres mati res inflamma...

Page 4: ...lementalheaters There fore it is advisable to have an alternate primary heat source when installed in a dwelling These appliances must not be connected to a chimney or flue serving a separate solid fu...

Page 5: ...built solid fuel wood burning fireplace listed to UL 127 or ULC S610 only All exhaust gases must be vented outside the structure Combustion air is drawn from outside the structure When installing in a...

Page 6: ...ng List 1 Insert Body with Burner Cassette and trivet 1 Set of Refractory Brick Panels 3 pieces H5866 1 Log Set H5860 1 Lower front 2 filler panel 1 Fasteners 6 slotted 1 4 truss screws 4 speed nuts 6...

Page 7: ...cleaned if it has been used to burn wood or synthetic logs Have the chimney and all inside surfaces of the fire place brushed and vacuumed so that no soot embers or loose combustion deposits can be dr...

Page 8: ...any projections such as shelves window sills mantels spacers standoffs or surfaces to com bustible construction etc above the appliance Paint or lacquer used to finish the mantel must be heat resista...

Page 9: ...ospheric pressure zone as the combustion air inlet to the appliance Flue Collar Connection This insert has a detachable flue collar to ease installation To detach flue collar lift removable vent trive...

Page 10: ...nel into the top side brick retainer and then dropping the bottom of the panel into the bot tom retainer The rounded edge on the side brick panels goes toward the front 3 Piece Brick Panel Set The siz...

Page 11: ...ing flanges to eliminate space between side and top flanges 5 Install two spring clips approximately five inches from each end of each of the three gold trim pieces The spring clips should be installe...

Page 12: ...PES Fuel Type Inlet Pressure Manifold Pressure Desired Minimum Maximum On Hi Fire On Lo Fire Natural Gas 7 WC 5 WC 10 5 WC 3 5 WC 1 7 WC LP Gas 11 WC 10 5 WC 13 WC 10 0 WC 5 4 WC Table 1 1 2 1 3 cm 7...

Page 13: ...begins to form after burning the air shutter should be opened gradually until the sooting condition stops Open the shutter a small amount at a time until the sooting ceases See Flame Color and Behavi...

Page 14: ...hermostat mural voir Figure B et le cas ch ant sur le bo tier delat l commande FigureC Pouracheverl instal lationcorrectedecefoyer proc dezcommesuitavec les tiquettesadh sivesenlangues trang resfourni...

Page 15: ...don t try to repair it call a qualified service technician Force or attempted repair may result in a fire or explosion D DO NOT use this appliance if any part has been under water Immediately call a q...

Page 16: ...a match or candle or smoke from a cigarette cigar or pipe OFF ON PiezoIgniter ON OFFSwitch No Blue Flame Center Soot at Flame Tip Dark Orange Flame IMPROPERLY BURNING FLAME Soot above Flame Tip No So...

Page 17: ...further adjustment is necessary the blower will come on automati cally whenever the insert is warm 4 If you do not wish to have the blower on turn the knob until it clicks into the OFF position Optio...

Page 18: ...e of the burner not igniting Follow the instructions included with the thermostat or remote control for wiring Millivolt and System Checks Check Test To Test Connect Meter Leads to Terminals Thermosta...

Page 19: ...ance Checklist Should Only Be Performed by a Qualified Service Technician 1 Annual inspection should be made and the following checks per formed a With unit cool remove glass and inspect burner for di...

Page 20: ...s of the front door see Figure 20a With the latches released rotate the catch part of each latch outward away from the front door The door will pivot toward you from the top hinging from the bottom as...

Page 21: ...nnection Wire Black Pan Snap Switch Snap Switch Connection Wire White Speed Control Connection Speed control Connection Wire Black Blower Main Power Cord Black Main Power Cord Wire White Main Power Co...

Page 22: ...roblem if longer purge will not light check gap between electrode and pilot should be 1 8 inch 3 mm to have a strong spark If OK replace pilot Pilot will not stay lit after carefully following lightin...

Page 23: ...2 Per Stove H5982 Main Door Decorative Nickel Bars Each 2 Per Stove H6000 Middle Bay Glass W glass Tape Installed REPLACEMENT PARTS Firestar GC3 H5880 NG Pilot Assembly Includes Thermopile Electrode...

Page 24: ...NG to LP Conversion Kit NG to LP ref form 775251M Trivets 75254 FSTR DVS2 TRV B Trivet Black 75248 FSTR DVS2 TRV G Trivet Gold 75249 FSTR DVS2 TRV N Trivet Nickel ACCESSORIES Firestar GC3 Finish Pane...

Page 25: ...UR DU FOYER EXEMPTE DE MAT RIAUX COMBUSTIBLES D ESSENCE ET AUTRES VAPEURS ET LIQUIDES INFLAMMABLES MAINTENEZ LE BR LEUR ET LE BO TIER DES COMMANDES PROPRE EN TOUT TEMPS VOIR LES MANUELS D INSTALLATION...

Page 26: ...res contactez un installateur qualifi un agent de service ou un fournisseur de gaz Si vous op rez cet appareil sans qu il ne soit correctement raccord un conduit d vacuation vous pourriez risquer d tr...

Page 27: ...27 NOTES...

Page 28: ...her documents for future refer ence Product reference information We recommend that you record the following important information aboutyourappliance PleasecontactyourLennoxHearthProductsdealer for an...

Reviews: