Refer to the unit nameplate for minimum circuit ampacity amperage

minimum, and maximum fuse or circuit breaker fusible (HACR per

NEC). Install power wiring and properly sized disconnect switch.

NOTE 

  UNITS  ARE  APPROVED  FOR  USE  ONLY  WITH  COPPER

CONDUCTORS.  GROUND  UNIT  AT  DISCONNECT  SWITCH  OR  TO  AN  EARTH

GROUND.

CIRCUIT SIZING AND DISCONNECT SWITCH

DISCONNECT

SWITCH

MAIN FUSE

BOX/BREAKER

PANEL

1

K1 CONTACTOR

LEFT CUTOUT

HIGH VOLTAGE WIRING

GROUND LUG

CONTROL BOX

USE THE LEFT CUTOUT TO ROUTE

HIGH VOLTAGE WIRING TO THE K1

CONTACTOR ON THE ELP090S AND

120S MODELS.

NOTE - ANY EXCESS HIGH VOLTAGE

FIELD WIRING SHOULD BE TRIMMED

AND SECURED AWAY FROM ANY LOW

VOLTAGE FIELD WIRING.

ROUTE EARTH GROUND THROUGH

LEFT CUTOUT AND CONNECT TO 

GROUND LUG.

2

TYPICAL HIGH VOLTAGE POWER SUPPLY 

CONNECTIONS

Install  room  thermostat  (ordered  separately)  on  an  inside  wall

approximately in the center of the conditioned area and 5 feet (1.5m)

from the floor. It should not be installed on an outside wall or where it

can be affected by sunlight, drafts or vibrations.

THERMOSTAT

5 FEET

(1.5M)

INSTALL THERMOSTAT

3

Install low voltage wiring from outdoor to indoor unit and from

thermostat to indoor unit as illustrated.

TYPICAL CONTROL WIRING

ELP HEAT

PUMP

C1

W1

C

R

C1

C

RO

ELA AIR

HANDER

Y1

C

R

A2

THERMOSTAT

RT2 REMOTE

SENSOR

S2

S1

W2

W

W2

W1

W2

4

Summary of Contents for ELP090S4S

Page 1: ...tective clothing INSTALLATION INSTRUCTIONS HEAT PUMPS 7 5 AND 10 TONS 507744 01 11 2017 Elite Class ELP Series 7 5 and 10 Ton Shipping and Packing List Check the unit for shipping damage If damaged or...

Page 2: ...HOLES For Rigging FRONT VIEW TOP VIEW FORKLIFT SLOTS Both Sides SIDE VIEW 1108 48 3 4 1238 3 1 2 89 1149 FF EE INLET AIR INLETAIR B B AA CC DD CENTER OF GRAVITY ELECTRICAL INLETS Above Refrigerant Li...

Page 3: ...ITCH S24 CTXV SENSING BULB DEFROST SWITCH LOCATION S6 REVERSING VALVE CHECK EXPANSION VALVE CTXV ELP120S4S HIGH PRESSURE SWITCH S4 PRESSURE SWITCH S192 DEFROST SWITCH LOCATION S6 REVERSING VALVE LIQUI...

Page 4: ...ressor Unit Control Box Components Arrangement ELP090S4S AND ELP120S4S TRANSFORMER T1 CONTACTOR K1 RUN CAPACITORS C1 C2 GROUND LUG TERMINAL STRIP TB14 DEFROST CONTROL BOARD Rigging the Unit for Liftin...

Page 5: ...LP090 5 8 16mm 1 1 8 29mm ELP120 5 8 16mm 1 1 8 29mm Refrigerant Line Limitations You may install the unit in applications that have line set lengths of up to 50 linear feet 15 m with refrigerant line...

Page 6: ...DELS NOTE ANY EXCESS HIGH VOLTAGE FIELD WIRING SHOULD BE TRIMMED AND SECURED AWAY FROM ANY LOW VOLTAGE FIELD WIRING ROUTE EARTH GROUND THROUGH LEFT CUTOUT AND CONNECT TO GROUND LUG 2 TYPICAL HIGH VOLT...

Page 7: ...S C D TIGHTEN WIRE TIE TO SECURE 24VDC CONTROL WIRING NOTE FOR PROPER VOLTAGES SELECT THERMOSTAT WIRE CONTROL WIRING GAUGE PER TABLE ABOVE NOTE WIRE TIE PROVIDES LOW VOLTAGE WIRE STRAIN RELIEF AND MAI...

Page 8: ...ISCONNECT ALL POWER BEFORE SERVICING 7 C2 C2 B5 MOTOR OUTDOOR FAN 2 CAPACITOR OUTDOOR FAN 2 1 4 K10 1 2 1 K8 1 2 8 5 K8 2 CB8 CIRCUIT BREAKER TRANS T1 S9 T1 TRANSFORMER CONTROL SWITCH DEFROST COMPRESS...

Page 9: ...gerant is added or removed 2 Minor variations in these pressures may be expected due to differences in installations Significant differences could mean that the system is not properly charged or that...

Page 10: ...d TABLE 4 HFC 410A Normal Operating Pressures Cooling Mode Liquid 10 and Suction 5 psig Temp ELP090 ELA090 ELP120 ELA120 Liquid Suction Liquid Suction 65 F 18 C 226 119 247 132 75 F 24 C 261 125 291 1...

Page 11: ...30 475 6 146 579 8 38 113 6 54 152 8 69 197 3 85 254 1 100 317 2 116 396 0 131 481 6 147 586 8 39 115 8 55 155 5 70 200 6 86 258 0 101 321 8 117 401 3 132 487 8 148 593 8 40 118 0 56 158 2 71 203 9 87...

Page 12: ...s with defrost control 100269 02 The factory de fault defrost interval is 60 minutes Units with defrost control 100269 04 or higher The fac tory default defrost interval is 90 minutes If the timing se...

Page 13: ...rmal operation Alternating Slow Flash 5 min anti short cycle delay Fault and Lockout Codes OFF Slow Flash Loss of Charge Fault OFF ON Loss of Charge Lockout Slow Flash OFF High Pressure Fault ON OFF H...

Page 14: ...e or Circuit Breaker Electrical Connections Tight Indoor Filter clean Supply Voltage Unit Off Indoor Blower RPM S P Drop Over Indoor Dry Outdoor Coil Entering Air Temp Vapor Pressure Refrigerant Lines...

Reviews: