background image

Page 12

System Operation 

The outdoor unit and indoor blower cycle on demand from 

the room thermostat. When the thermostat blower switch 

is in the ON position, the indoor blower operates contin-

uously. 

HIGH PRESSURE SWITCHES (S4 AND S7) 

These units are equipped with an auto-reset high pressure 

switch (single-pole, single-throw) which is located on the 

discharge line. The switch shuts off the compressor when 

discharge pressure rises above the factory setting. High 

Pressure (auto reset) – trip at 640 psig; reset at 512 psig. 

LOSS OF CHARGE SWITCH (S24) 

These units are equipped with a loss-of-charge switch that 

is located in the liquid line. The switch is a SPST, auto-re-

set switch that is normally closed. The switch opens at 40 

psi and closes at 90 psi.

Defrost System 

The defrost system includes a defrost thermostat and a 

defrost control. 

DEFROST THERMOSTAT 

The defrost thermostat is located on the liquid line between 

the check/expansion valve and the distributor on each 

coil. When the defrost thermostat senses 42°F (5.5°C) or 

cooler, its contacts close and send a signal to the defrost 

control board to start the defrost timing. It also terminates 

defrost when the liquid line warms up to 70°F (21°C). 

DEFROST CONTROL 

The defrost control board includes the combined functions 

of a time/temperature defrost control, defrost relay, time 

delay, diagnostic LEDs, and a terminal strip for field wiring 

connections. 
The control provides automatic switching from normal 

heating operation to defrost mode and back. During com-

pressor cycle (defrost thermostat is closed, calling for de-

frost), the control accumulates compressor run times at 

30, 60, or 90 minute field adjustable intervals. If the de

-

frost thermostat is closed when the selected compressor 

run time interval ends, the defrost relay is energized and 

defrost begins. 
Each timing pin selection provides a different accumulat-

ed compressor run time period for one defrost cycle. This 

time period must occur before a defrost cycle is initiated. 

The defrost interval can be adjusted to 30 (T1), 60 (T2), or 

90 (T3) minutes. The maximum defrost period is 14 min-

utes and cannot be adjusted. 

NOTE — Defrost control part number is listed near the P1 

timing pins.

 

•   Units with defrost control 

100269-02

: The factory de-

fault defrost interval is 60 minutes. 

•   Units with defrost control 

100269-04 or higher

: The fac-

tory default defrost interval is 90 minutes.

If the timing selector jumper is missing, the defrost control 

defaults to a 90-minute defrost interval.

Defrost Control Board 

DEFROST CONTROL TIMING PINS

24V TERMINAL

STRIP

CONNECTIONS

DIAGNOSTIC

LEDS

HIGH PRESSURE

SWITCH

TEST

PINS

FIELD SELECT

TIMING PINS

REVERSING

VALVE

DEFROST

THERMOSTAT

LOSS-OF-CHARGE

SWITCH

COMPRESSOR

DELAY PINS

S4

S24

SERVICE LIGHT

CONNECTIONS

FIGURE 5. Outdoor Unit Defrost Control Board

A TEST option is provided for troubleshooting. The TEST 

mode may be started any time the unit is operating in the 

heating mode and the defrost thermostat is closed or jum-

pered. If the jumper is in the TEST position at power-up, 

the control will ignore the test pins. When the jumper is 

placed across the TEST pins for two seconds, the con-

trol will enter the defrost mode. If the jumper is removed 

before an additional 5-second period has elapsed (7 sec-

onds total), the unit will remain in defrost mode until the 

defrost thermostat opens or 14 minutes have passed. If 

the jumper is not removed until after the additional 5-sec-

ond period has elapsed, the defrost will terminate and the 

test option will not function again until the jumper is re-

moved and re-applied. 

COMPRESSOR DELAY 

The defrost board has a field-selectable function to reduce 

occasional sounds that may occur while the unit is cycling 

in and out of the defrost mode. When the compressor de-

lay jumper is removed, the compressor will be cycled off 

for 30 seconds going in and out of the defrost mode. 

NOTE – The 30-second compressor feature is ignored 

when the TEST pins have been jumpered.

 

TIME DELAY 

The timed-off delay is five minutes long. The delay helps 

protect the compressor from short-cycling in case the 

power to the unit is interrupted or a pressure switch opens. 

The delay is bypassed by placing the timer select jumper 

across the TEST pins for 0.5 seconds. 

NOTE – The board must have a thermostat demand for 

the bypass function.

PRESSURE SWITCH CIRCUITS 

The defrost control includes two pressure switch circuits. 

The factory-installed high pressure switch (S4) wires are 

connected to the board’s HI PS terminals (figure 5). The 

board also includes LO PS terminals to accommodate the 

factory installed loss-of-charge switch. 

Summary of Contents for ELP090S4S

Page 1: ...tective clothing INSTALLATION INSTRUCTIONS HEAT PUMPS 7 5 AND 10 TONS 507744 01 11 2017 Elite Class ELP Series 7 5 and 10 Ton Shipping and Packing List Check the unit for shipping damage If damaged or...

Page 2: ...HOLES For Rigging FRONT VIEW TOP VIEW FORKLIFT SLOTS Both Sides SIDE VIEW 1108 48 3 4 1238 3 1 2 89 1149 FF EE INLET AIR INLETAIR B B AA CC DD CENTER OF GRAVITY ELECTRICAL INLETS Above Refrigerant Li...

Page 3: ...ITCH S24 CTXV SENSING BULB DEFROST SWITCH LOCATION S6 REVERSING VALVE CHECK EXPANSION VALVE CTXV ELP120S4S HIGH PRESSURE SWITCH S4 PRESSURE SWITCH S192 DEFROST SWITCH LOCATION S6 REVERSING VALVE LIQUI...

Page 4: ...ressor Unit Control Box Components Arrangement ELP090S4S AND ELP120S4S TRANSFORMER T1 CONTACTOR K1 RUN CAPACITORS C1 C2 GROUND LUG TERMINAL STRIP TB14 DEFROST CONTROL BOARD Rigging the Unit for Liftin...

Page 5: ...LP090 5 8 16mm 1 1 8 29mm ELP120 5 8 16mm 1 1 8 29mm Refrigerant Line Limitations You may install the unit in applications that have line set lengths of up to 50 linear feet 15 m with refrigerant line...

Page 6: ...DELS NOTE ANY EXCESS HIGH VOLTAGE FIELD WIRING SHOULD BE TRIMMED AND SECURED AWAY FROM ANY LOW VOLTAGE FIELD WIRING ROUTE EARTH GROUND THROUGH LEFT CUTOUT AND CONNECT TO GROUND LUG 2 TYPICAL HIGH VOLT...

Page 7: ...S C D TIGHTEN WIRE TIE TO SECURE 24VDC CONTROL WIRING NOTE FOR PROPER VOLTAGES SELECT THERMOSTAT WIRE CONTROL WIRING GAUGE PER TABLE ABOVE NOTE WIRE TIE PROVIDES LOW VOLTAGE WIRE STRAIN RELIEF AND MAI...

Page 8: ...ISCONNECT ALL POWER BEFORE SERVICING 7 C2 C2 B5 MOTOR OUTDOOR FAN 2 CAPACITOR OUTDOOR FAN 2 1 4 K10 1 2 1 K8 1 2 8 5 K8 2 CB8 CIRCUIT BREAKER TRANS T1 S9 T1 TRANSFORMER CONTROL SWITCH DEFROST COMPRESS...

Page 9: ...gerant is added or removed 2 Minor variations in these pressures may be expected due to differences in installations Significant differences could mean that the system is not properly charged or that...

Page 10: ...d TABLE 4 HFC 410A Normal Operating Pressures Cooling Mode Liquid 10 and Suction 5 psig Temp ELP090 ELA090 ELP120 ELA120 Liquid Suction Liquid Suction 65 F 18 C 226 119 247 132 75 F 24 C 261 125 291 1...

Page 11: ...30 475 6 146 579 8 38 113 6 54 152 8 69 197 3 85 254 1 100 317 2 116 396 0 131 481 6 147 586 8 39 115 8 55 155 5 70 200 6 86 258 0 101 321 8 117 401 3 132 487 8 148 593 8 40 118 0 56 158 2 71 203 9 87...

Page 12: ...s with defrost control 100269 02 The factory de fault defrost interval is 60 minutes Units with defrost control 100269 04 or higher The fac tory default defrost interval is 90 minutes If the timing se...

Page 13: ...rmal operation Alternating Slow Flash 5 min anti short cycle delay Fault and Lockout Codes OFF Slow Flash Loss of Charge Fault OFF ON Loss of Charge Lockout Slow Flash OFF High Pressure Fault ON OFF H...

Page 14: ...e or Circuit Breaker Electrical Connections Tight Indoor Filter clean Supply Voltage Unit Off Indoor Blower RPM S P Drop Over Indoor Dry Outdoor Coil Entering Air Temp Vapor Pressure Refrigerant Lines...

Reviews: