background image

Page 5

Caution - do not

walk on unit

.

Lifting point should be directly above the center of gravity.

Important - all panels

must be in place for

rigging.

FIGURE 1. ELP090S4S and ELP120S4S

Installation Clearances 

See Unit Dimensions on page 2 for sizing mounting slab, 

platforms  or  supports.  Refer  to  figures  4  through  6  for 

mandatory installation clearance requirements. 

NOTES:  

•   Clearance to one of the remaining two sides may be 12 

in. (305 mm) and the final side may be 6 in. (152 mm).  

• 

 A clearance of 24 in. (610 mm) must be maintained be

-

tween two units.  

•  48 in. (1219 mm) clearance required on top of unit.

CONTROL BOX

ACCESS

SEE

NOTES

SEE

NOTES

36”

30”

FIGURE 2. ELP090S4S and ELP120S4S  

Installation Clearances

Line Set 

Field refrigerant piping consists of liquid and suction lines 

connecting the condensing unit and the indoor unit. Liquid 

and suction service valves are located in a compartment 

at the corner of the unit below the control box. 

Piping can be routed directly from the service valves or 

field supplied elbows can be added to divert the piping as 

required. 

Refer to table 1 for field-fabricated refrigerant line sizes for 

runs up to 50 linear feet (15 m).

TABLE 1. Refrigerant Line Sizes for Runs  

Up to 50 Linear Feet 

Unit

Liquid Line

Suction Line

ELP090

5/8” (16mm)

1-1/8” (29mm) 

ELP120

5/8" (16mm)

1-1/8” (29mm)

Refrigerant Line Limitations

You may install the unit in applications that have line set 

lengths of up to 50 linear feet (15 m) with refrigerant line 

sizes as outlined in table 1 (excluding equivalent length of 

fittings). Size refrigerant lines greater than 50 linear feet 

(15m or greater) according to the Lennox Refrigerant Pip-

ing Design and Fabrication Guidelines (Corp. 9351-L9) or 

latest version.

Electrical Connections 

 WARNING

Electric Shock Hazard. Can cause injury or 

death. Unit must be properly grounded in 

accordance with national and local codes.
Line voltage is present at all components 

when unit is not in operation on units with 

single-pole contactors. Disconnect all remote 

electric power supplies before opening 

access panel. Unit may have multiple power 

supplies.

In the United States, wiring must conform with current lo-

cal codes and the current National Electric Code (NEC). In 

Canada, wiring must conform with current local codes and 

the current Canadian Electrical Code (CEC). 

TRANSFORMER – 24VAC, 70VA – PROVIDED 

NOTE

 – 

The addition of accessories to the system could 

exceed the 70VA power requirement of the factory-pro-

vided transformer. Measure the system’s current and 

voltage after installation is complete to determine trans-

former loading. If loading exceeds the factory-provided 

transformer  capacity,  a  larger  field-provided  transformer 

will need to be installed in the system.

Summary of Contents for ELP090S4S

Page 1: ...tective clothing INSTALLATION INSTRUCTIONS HEAT PUMPS 7 5 AND 10 TONS 507744 01 11 2017 Elite Class ELP Series 7 5 and 10 Ton Shipping and Packing List Check the unit for shipping damage If damaged or...

Page 2: ...HOLES For Rigging FRONT VIEW TOP VIEW FORKLIFT SLOTS Both Sides SIDE VIEW 1108 48 3 4 1238 3 1 2 89 1149 FF EE INLET AIR INLETAIR B B AA CC DD CENTER OF GRAVITY ELECTRICAL INLETS Above Refrigerant Li...

Page 3: ...ITCH S24 CTXV SENSING BULB DEFROST SWITCH LOCATION S6 REVERSING VALVE CHECK EXPANSION VALVE CTXV ELP120S4S HIGH PRESSURE SWITCH S4 PRESSURE SWITCH S192 DEFROST SWITCH LOCATION S6 REVERSING VALVE LIQUI...

Page 4: ...ressor Unit Control Box Components Arrangement ELP090S4S AND ELP120S4S TRANSFORMER T1 CONTACTOR K1 RUN CAPACITORS C1 C2 GROUND LUG TERMINAL STRIP TB14 DEFROST CONTROL BOARD Rigging the Unit for Liftin...

Page 5: ...LP090 5 8 16mm 1 1 8 29mm ELP120 5 8 16mm 1 1 8 29mm Refrigerant Line Limitations You may install the unit in applications that have line set lengths of up to 50 linear feet 15 m with refrigerant line...

Page 6: ...DELS NOTE ANY EXCESS HIGH VOLTAGE FIELD WIRING SHOULD BE TRIMMED AND SECURED AWAY FROM ANY LOW VOLTAGE FIELD WIRING ROUTE EARTH GROUND THROUGH LEFT CUTOUT AND CONNECT TO GROUND LUG 2 TYPICAL HIGH VOLT...

Page 7: ...S C D TIGHTEN WIRE TIE TO SECURE 24VDC CONTROL WIRING NOTE FOR PROPER VOLTAGES SELECT THERMOSTAT WIRE CONTROL WIRING GAUGE PER TABLE ABOVE NOTE WIRE TIE PROVIDES LOW VOLTAGE WIRE STRAIN RELIEF AND MAI...

Page 8: ...ISCONNECT ALL POWER BEFORE SERVICING 7 C2 C2 B5 MOTOR OUTDOOR FAN 2 CAPACITOR OUTDOOR FAN 2 1 4 K10 1 2 1 K8 1 2 8 5 K8 2 CB8 CIRCUIT BREAKER TRANS T1 S9 T1 TRANSFORMER CONTROL SWITCH DEFROST COMPRESS...

Page 9: ...gerant is added or removed 2 Minor variations in these pressures may be expected due to differences in installations Significant differences could mean that the system is not properly charged or that...

Page 10: ...d TABLE 4 HFC 410A Normal Operating Pressures Cooling Mode Liquid 10 and Suction 5 psig Temp ELP090 ELA090 ELP120 ELA120 Liquid Suction Liquid Suction 65 F 18 C 226 119 247 132 75 F 24 C 261 125 291 1...

Page 11: ...30 475 6 146 579 8 38 113 6 54 152 8 69 197 3 85 254 1 100 317 2 116 396 0 131 481 6 147 586 8 39 115 8 55 155 5 70 200 6 86 258 0 101 321 8 117 401 3 132 487 8 148 593 8 40 118 0 56 158 2 71 203 9 87...

Page 12: ...s with defrost control 100269 02 The factory de fault defrost interval is 60 minutes Units with defrost control 100269 04 or higher The fac tory default defrost interval is 90 minutes If the timing se...

Page 13: ...rmal operation Alternating Slow Flash 5 min anti short cycle delay Fault and Lockout Codes OFF Slow Flash Loss of Charge Fault OFF ON Loss of Charge Lockout Slow Flash OFF High Pressure Fault ON OFF H...

Page 14: ...e or Circuit Breaker Electrical Connections Tight Indoor Filter clean Supply Voltage Unit Off Indoor Blower RPM S P Drop Over Indoor Dry Outdoor Coil Entering Air Temp Vapor Pressure Refrigerant Lines...

Reviews: