Page 13
4 − Complete line voltage wiring from disconnect switch
near unit to make-up box.
NOTE − An equipment ground screw is provided. Refer
to unit wiring diagram. Ground unit using a suitable
ground wire.
5 − Any 120V accessory rated up to 1 amp can be con-
nected to the EAC terminal on the A15 ST9103A con-
trol. The EAC terminal is energized when the blower is
in operation.
WARNING
Run 24V Class II wiring only through specified low
voltage opening. Run line voltage wiring only
through specified high voltage opening. Do not com-
bine voltage in one opening.
CAUTION
Use copper conductors only.
IMPORTANT
If using a programmable thermostat, be sure to use
a type of thermostat that retains its memory in event
of a power loss.
Figure 14
Typical ELO183UF Wiring Diagram