Page 42
TABLE 11
RED LED
Flash Code
2
Diagnostic Codes / Status of Furnace
Off
No power to control or board fault detected
Heartbeat
1
Normal Operation - Idle, Continuous Fan, Cool
Continuous Rapid Flash
Call For Heat / Burner Operation
1
Reverse Line Voltage Polarity
2
Improper Earth Ground
3
Burner failed to light, or lost flame during heat demand
4
Low Flame Signal - check flame sensor
5
Watchguard - burner failed to light, exceeded maximum number of retries or
recycles.
6
Not Used
7
Primary or Secondary Limit Open or Watchguard Mode - Limit Switch Open longer
than 3 minutes
8
Rollout Switch Open
9
Pressure Switch failed to close or opened during heat demand
10
Watchguard - Pressure Switch opened 5 times during one heat demand
11
Pressure Switch stuck closed prior to activation of combustion air inducer
12
Flame Sensed without gas valve energized
13
Low Line Voltage
Notes
Note - 1
A ”Heartbeat” is indicated by a ”Slow Flash” - 1 sec on 1 sec off, repeating
Note - 2
Error codes are indicated by a “rapid flash” - the LED flashes X times at ½ second on ½
second off, remains off for 3 seconds then repeats.
Note - 3
Last 10 error codes are stored in memory including when power is shut off to the
unit. - To recall, press and release button, most recent will be displayed first, LED off for 3
sec, then next error code is displayed, etc. To clear error codes, depress and hold button
longer than 5 seconds.