Lennox EL180UHE SERIES Installation Instructions Manual Download Page 28

Page 28

TABLE 10 

Manifold Pressure Settings at all Altitudes

Model 

Input Size

Gas

0 - 2000 ft.

2001 -4500 ft . 4501 - 7500 ft. 7501 - 10,000 

ft

Line Pressure in. wg.

Min

Max

045

Nat

3.5

3.2

3.0

3.5

4.5

13.0

LP/Propane

10.0

10.0

10.0

10.0

11.0

13.0

070

Nat

3.5

3.2

2.8

3.5

4.5

13.0

LP/Propane

10.0

10.0

10.0

10.0

11.0

13.0

090

Nat

3.5

3.2

2.7

3.5

4.5

13.0

LP/Propane

10.0

10.0

9.6

10.0

11.0

13.0

110

Nat

3.5

3.5

3.0

3.5

4.5

13.0

LP/Propane

10.0

10.0

9.6

10.0

11.0

13.0

135

Nat

3.5

3.5

2.9

3.5

4.5

13.0

LP/Propane

10.0

10.0

9.6

10.0

11.0

13.0

Other Unit Adjustments

Primary and Secondary Limits

The primary limit is located on the heating compartment 

vestibule panel. The secondary limits (if equipped) are lo-

cated in the blower compartment, attached to the back 

side of the blower. These auto reset limits are factory-set 

and require no adjustment.

Flame Rollout Switches

These manually reset switches are located on the front of 

the box.

Pressure Switch

The pressure switch is located in the heating compartment 

adjacent to the combustion air inducer. The switch checks 

for proper combustion air inducer operation before allow-

ing ignition trial. The switch is factory-set and requires no 

adjustment.

TABLE 11 

Pressure Switch and Gas Conversion Kits at all Altitudes

Model Input 

Size

High Altitude Pressure Switch Kit

High Altitude 

Natuarl Gas 

Orifice Kit

LP/Propane Oricifice Kit

Natuarl Gas 

Orifice Kit

045

0-4500 ft

4501-7500 ft 7501-10,000 ft 7501-10,000 ft

0-7500 ft

7501-10,000 ft

0-7500 ft

070

No Change

80W52

80W51

73W37

11K49

73W81

73W81

110

80W52

80W51

090

80W52

80W51

110

80W57

80W52

135

80W52

80W51

NOTE - A natural to L.P. propane gas changeover kit is necessary to convert this unit. Refer to the changeover kit instal

-

lation instruction for the conversion procedure.

Temperature Rise

After the furnace has been started, and supply and return 

air temperatures have been allowed to stabilize, check the 

temperature rise
If necessary, adjust the blower speed to maintain the tem-

perature rise within the range shown on the unit nameplate. 

Increase the blower speed to decrease the temperature. 

Decrease the blower speed to increase the temperature 

rise. Failure to adjust the temperature rise may cause er-

ratic limit operation.

Fan Control

The heat fan-on time of 30 seconds is not adjustable. The 

heat fan-off delay (amount of time that the blower oper-

ates  after  the  heat  demand  has  been  satisfied)  may  be 

adjusted by changing the jumper position across the five 

pins on the integrated control. The unit is shipped with a 

factory fan-off delay setting of 90 seconds. The fan-off de-

lay affects comfort and is adjustable to satisfy individual 

applications. Adjust the fan-off delay to achieve a supply 

air temperature between 90° and 110°F at the moment 

that the blower is de-energized. Longer off delay settings 

provide lower return air temperatures; shorter settings 

provide higher return air temperatures. See figure 32

Summary of Contents for EL180UHE SERIES

Page 1: ...t service agency or the gas supplier CAUTION As with any mechanical equipment contact with sharp sheet metal edges can result in personal injury Take care while handling this equipment and wear gloves...

Page 2: ...49 14 356 9 16 14 3 76 Right 7 178 Left 2 FLUE OUTLET Either Side 3 OPTIONAL EXTERNAL SIDE RETURN AIR FILTER KIT Either Side 16 406 14 3 4 375 3 OPTIONAL EXTERNAL SIDE RETURN AIR FILTER KIT Either Si...

Page 3: ...h local building codes In the absence of lo cal codes units must be installed according to the current National Fuel Gas Code ANSI Z223 1 The National Fuel Gas Code is available from the follow ing ad...

Page 4: ...heater during any phase of construc tion Very low return air temperatures harmful vapors and operation of the unit with clogged or misplaced filters will damage the unit EL180UHE units may be used for...

Page 5: ...rial is not the complete and official position of the ANSI on the referenced subject which is represented only by the standard in its entirety CAUTION Do not install the furnace in a corrosive or cont...

Page 6: ...the two spac es Each opening must have a minimum free area of 1 square inch 645 mm2 per 1 000 Btu 29 kW per hour of total input rating of all gas fired equipment in the confined space Each opening mu...

Page 7: ...hour of the total input rating of all equipment in the enclosure If the equipment room is located against an outside wall and the air openings ing shall have a free area of at least one square inch 6...

Page 8: ...le mounting leg The bolt and washer must be removed before the furnace is placed into operation After the bolt and washer have been re moved the rigid leg will not touch the blower housing RIGID LEG r...

Page 9: ...turn Air with transition and filter Figure 8 Figure 9 Optional Return Air Base Upflow Applications Only For use with A B C and D cabinets NOTE Optional Side Return Air Filter Kits are not for use with...

Page 10: ...for clearances to combustible materials as indicated on the unit nameplate Minimum clearances for closet or alcove installations are shown in figure 11 This furnace may be installed in either an attic...

Page 11: ...filter is being installed as part of this system to ensure better indoor air quality the filter must be properly sized Highefficiency filters have a higher static pressure drop than standardefficiency...

Page 12: ...4 inch diameter flue transition is factory installed on the combustion air inducer outlet of all models Figure 15 shows the combustion air inducer as shipped from the fac tory Mounting Screws Location...

Page 13: ...arbed fitting on the pressure switch assembly Remove pressure switch assembly 1 screw and cut wire tie to free pressure switch wires Re install pressure switch on the other side of orifice plate and r...

Page 14: ...ing document Use self drilling sheet metal screws or a mechanical fas tener to firmly secure the vent pipe to the round collar of the flue transition If self drilling screws are used to attach the ven...

Page 15: ...fan assisted furnace may be commonly vented into an existing lined masonry chimney if the following conditions are met The chimney is currently serving at least one drafthood equipped appliance The ve...

Page 16: ...ing to approved engineering methods 5 Multiple appliance vents The flow area of the largest section of vertical vent or chimney shall not exceed 7 times the smallest listed appliance categorized vent...

Page 17: ...equivalent insulation qualities 14 All venting pipe passing through floors walls and ceilings must be installed with the listed clearance to combustible materials and be fire stopped according to loca...

Page 18: ...22 339 5 22 65 30 130 39 219 49 330 10 29 59 40 121 51 206 64 315 15 35 53 48 112 61 195 76 301 20 0 0 97 0 202 0 349 0 540 2 10 75 14 149 18 250 20 377 5 21 71 29 143 38 242 47 367 10 28 64 38 133 5...

Page 19: ...23 47 36 86 51 136 67 206 3 24 50 37 92 52 146 69 220 15 1 21 50 33 89 47 142 64 220 2 22 53 35 96 49 153 66 235 3 24 55 36 102 51 163 68 248 20 1 21 54 33 99 46 157 62 246 2 2 57 34 105 48 167 64 25...

Page 20: ...ection CAUTION If a flexible gas connector is required or allowed by the authority that has jurisdiction black iron pipe shall be installed at the gas valve and extend outside the furnace cabinet The...

Page 21: ...985 27 89 873 24 72 791 22 39 728 20 61 677 19 17 635 17 98 600 17 00 2 50 8 2 067 52 502 4020 113 83 2760 78 15 2220 62 86 1900 53 80 1680 47 57 1520 43 04 1400 39 64 1300 36 81 1220 34 55 1160 32 8...

Page 22: ...e 27 Electrical WARNING ELECTROSTATIC DISCHARGE ESD Precautions and Procedures Electrostatic discharge can affect electronic components Take care during unit installation and service to protect the un...

Page 23: ...operly grounded in accordance with national and local codes Accessory Terminals One line voltage EAC 1 4 spade terminal is provided on the furnace integrated control See figure 30 for integrated contr...

Page 24: ...on or appro priate dual fuel thermostat instructions Indoor Blower Speeds 1 When the thermostat is set to FAN ON the indoor blower will run continuously on the fan speed when there is no cooling or he...

Page 25: ...to activation of combustion air inducer 12 Flame Sensed without gas valve energized 13 Low Line Voltage Note 1 Notes Note A Heartbeat is indicated by a Slow Flash 1 sec on 1 sec off repeating Note Las...

Page 26: ...l electrical power to the unit 4 This furnace is equipped with an ignition device which automatically lights the burners Do not try to light the burners by hand 5 Remove the upper access panel 6 Move...

Page 27: ...ve temporary gas meter if installed NOTE To obtain accurate reading shut off all other gas appliances connected to meter Supply Pressure Measurement A threaded plug on the inlet side of the gas valve...

Page 28: ...ricifice Kit Natuarl Gas Orifice Kit 045 0 4500 ft 4501 7500 ft 7501 10 000 ft 7501 10 000 ft 0 7500 ft 7501 10 000 ft 0 7500 ft 070 No Change 80W52 80W51 73W37 11K49 73W81 73W81 110 80W52 80W51 090 8...

Page 29: ...gas line pressure After one hour of continuous thermostat demand for heat the Watchguard will re set and remake thermostat demand to the furnace and automatically reset the integrat ed control to begi...

Page 30: ...erating range Thermal Limits should be checked by restricting airflow and not disconnecting the indoor blower For additional details please see Service and Application Note H049 2 Verify that system t...

Page 31: ...Page 31 EL180UHE BURNER ASSEMBLY REMOVAL Manifold And Gas Valve Retention Rings Cross Over Ignitor Sensor Rollout Switches Burner Detail Front View Figure 33...

Page 32: ...service agency or gas supplier Cabinet Parts Upper access panel Blower panel Top cap Control Panel Parts Transformer Integrated control Door interlock switch Circuit breaker Blower Parts Blower wheel...

Page 33: ...sted Supply Line Pressure W C ________ 1 VENT EXHAUST PIPE Secure to Unit Elbows Secured to Pipe Vent Pipe Supported 2 Roof Flashing water tight 3 DUCT SYSTEM SUPPLY AIR DUCT Sealed Insulated if neces...

Page 34: ...___ 5 COOLING MODE INDOOR BLOWER AMPS______ 3 TEMPERATURE DROP Return Duct Temperature _________ Supply Duct Temperature _ _______ 4 5 6 7 DRAIN LINE Leak Free THERMOSTAT Adjusted and Programmed Opera...

Reviews: