32
The three cables for connection from the keypad to the power
board must be kept separate from other cables, using an
individual cable channel; and use shielded cables, with a
cross-section of 1 mm
2
.
MODELS
VOLTAGE
LIMIT
009-011-015-019
009
019-021-025-029-035-
043-047-055-067-081
100-110-120-130
1N~230V-50Hz
3~230V-50Hz
3N~400V-50Hz
3~230V-50Hz
3N~400V-50Hz
1N~198-264V-50Hz
3~180-242V-50Hz
3N~342-462V-50Hz
3~198-264V-50Hz
3N~342-462V-50Hz
3N~400V-50Hz
3N~342-462V-50Hz
Three-lead shielded cable
with a cross-section of 1 mm
2
*
Terminal block
Remote
controller
(option)
2
1
x 1000
Electrical box
at the unit
PE
L2
L1
L3
PE
N
L
L2
L1
L3
PE
N
230V THREE-PHASE
UNITS
400V THREE-
PHASE UNITS
230V SINGLE PHASE
UNITS
UNIT MODEL
POWER SUPPLY
0091S
0111S
0151S
0191S
0211S
0251S
0291S
0351S
0431S
0472S
0552S
0672S
0812S
NUMBER OF WIRES X SECTION
3 ~ 230V - 50 Hz + PE
3N ~ 400V - 50 Hz + PE
1N ~ 230V - 50 Hz + PE
1003S
1103S
1203S
1303S
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
- AEH: Auxiliary Electric Heater
- The cable sections have been calculated based on a distance of 50m and variation of -10V.
Do not start the unit if the drop is greater than this.
- The wiring and circuit breakers to be mounted in the installation must comply with the Regulations in force.
- Ground wires must be properly connected and have a greater length than the phase wires.
A remote controller is offered as an option.
To install this option remote controller proceed as follow:
- Connect exactly as indicated in electrical diagram
- The wire should not exceed 50 m.
- BEFORE MAKING ANY ELECTRICAL CONNECTIONS, BE SURE THAT ALL CIRCUIT BREAKERS ARE OPEN AND SUPPLY IS OFF.
- IN ORDER TO CARRY OUT THE ELECTRICAL CONNECTIONS, FOLLOW THE ELECTRICAL DIAGRAM SUPPLIED WITH THE UNIT
(*) Remove wire.
(1) Remote changeover summer-winter
(Voltage free contact).
(2) Dynamic set point (outdoor sensor).
Not available for units EAC 0472 to 0812.
Without AEH
With AEH
Without AEH
With AEH
Without AEH
With AEH
(**) For these models it is needed choose between (1) and (2) functions.
They can not operate simultaneously.
X1
(2)
PE 90 91 92 93 94 95 96
N L1
PE
R3
Alarm
L2 L3
97 98
Remote
ON / OFF
Screen wire
24 25 26
12
ON/OFF
RC
Option remote
keyboard
MODE
Screen wire
3N 400V 50Hz + PE
(*)
Screen wire
(1)
(2)
PE 90 91 92 93 94 95 96
N L1
PEX1
R3
Alarm
L2 L3
97 98
12
24 25 26
ON/OFF
RC
Option remote
keyboard
MODE
Screen wire
Remote
ON / OFF
3N 400V 50Hz + PE
(EAR) 0091 TO 0431S
(**)
(*)
99 100
(1)
(2)
PE 90 91 92 93 94 95 96
N L1
PEX1
R3
Alarm
L2 L3
97 98
Remote
ON / OFF
Screen wire
12
24 25 26
ON/OFF
RC
Option remote
keyboard
MODE
Screen wire
3N 400V 50Hz + PE
(EAR) 0472 TO 1303S
(*)
2.6.- ELECTRICAL CONNECTIONS
VOLTAGE OPERATION LIMITS
2.- INSTALLATION
(EAC) 0091 TO 1303S
3 x 4 mm
2
3 x 10 mm
2
2
4 x 4 mm
2
4 x 4 mm
2
4 x 6 mm
2
4 x 10 mm
2
4 x 10 mm
2
4 x 10 mm
2
4 x 10 mm
2
4 x 16 mm
2
4 x 16 mm
2
4 x 25 mm
2
4 x 25 mm
2
4 x 35 mm
2
4 x 50 mm
2
4 x 6 mm
2
4 x 6 mm
2
4 x 10 mm
2
4 x 10 mm
2
4 x 10 mm
2
4 x 10 mm
2
4 x 16 mm
2
4 x 25 mm
2
4 x 25 mm
2
4 x 35 mm
2
4 x 35 mm
2
4 x 50 mm
2
4 x 50 mm
2
5 x 2,5 mm
2
5 x 2,5 mm
2
5 x 4 mm
2
5 x 4 mm
2
5 x 4 mm
2
5 x 4 mm
2
5 x 6 mm
2
5 x 10 mm
2
5 x 10 mm
2
5 x 10 mm
2
5 x 16 mm
2
5 x 16 mm
2
5 x 16 mm
2
5 x 4 mm
2
5 x 4 mm
2
5 x 4 mm
2
5 x 4 mm
2
5 x 4 mm
2
5 x 6 mm
2
5 x 10 mm
2
5 x 10 mm
2
5 x 10 mm
2
5 x 16 mm
2
5 x 16 mm
2
5 x 25 mm
2
5 x 25 mm
2
5 x 25 mm
2
5 x 35 mm
2
5 x 35 mm
2
5 x 80 mm
2
5 x 50 mm
2
5 x 50 mm
2
5 x 50 mm
2
5 x 70 mm
*Connection to be made by customer. MAXIMUM CABLE LENGTH 50m