background image

Page 6

FIGURE 10. Installing Fuse Block and Transformer (575V only)

Unit Start-Up 

1 -  Replace the air handler access cover.
2 -  Restore power to the unit.
3 -  Set the thermostat heat anticipator to 0.4 amps.
4 -   Align the provided wiring diagram sticker with the 

air handler diagram on the blower housing. Remove 

the backing and affix the sticker to the housing.

5 -  Set the thermostat above room temperature.
6 -  Check the system for normal operation.
7 -  Set the thermostat to desired setting.

CIRCUIT 1

CIRCUIT

BREAKERS OR

TERMINAL

BLOCK

1

4

7

3

6

9

CB1

CIRCUIT

BREAKER

NOTE - USE COPPER CONDUCTORS ONLY

REFER TO UNIT RATING PLATE FOR MINIMUM CIRCUIT AMPACITY AND MAXIMUM

OVERCURRENT PROTECTION SIZE
NOTE - ALL REMAINING WIRES FACTORY

INSTALLED

LINE VOLTAGE FIELD

INSTALLED

CLASS 2 VOLTAGE FIELD

INSTALLED NEC/CEC

TO EXTERNAL LOAD 24VAC AT .50 AMP MAXIMUM

THERMOSTAT HEAT ANTICIPATION SETTING 0.4 AMP (ELECTRIC HEAT)

WHEN TWO

STAGE THERMOSTAT IS USED, CONNECT SECOND STAGE

NALS “R” AND “W2”

FACTORY

INSTALLED JUMPER

L3 CONNECTION USED ON (Y VOLTAGE) 3

PHASE ELECTRIC HEATERS

ONLY

FIGURE 11. Typical Field Wiring – Cooling Application with Electric Heat

Air Handler Blower Speed Connections 

When using ECB29 heat section, adjust the blower speed 

according to the size of electric heat and air handler unit. 

The minimum blower setting for each air handler size with 

any heat sections in any application is HIGH. See specific 

air handler installation instructions for blower speed adjust-

ment procedure.

Typical Unit Applications 

Refer to figures 11 and 12 for typical field wiring for cooling 

and heat pump applications including an air handler with 

electric heat. 

4 - 

Make wiring connections as follows:  

• 

Heaters equipped with circuit breakers – 

Connect 

field power supply wiring to circuit breaker(s).  

• 

Heaters equipped with terminal blocks – 

Con-

nect field power supply wiring to terminal block(s).  

• 

Heaters  equipped  with  fuses  (460V,  3-Phase, 

60Hz  and  575V,  3-Phase,  60Hz)  – 

Connect  field 

power supply wiring to fuse block. (An extension 

plate is provided for J-voltage units.) 

Summary of Contents for ECB29 Series

Page 1: ...ing Replace all parts and panels before operating Failure to do so can result in death or electrical shock Electric Heat Section The ECB29 series electric heat section provides field in stalled electr...

Page 2: ...ed Remove the extended width knockout to allow for installation of 20kW or 25kW heater see figure 1 4 Slide the electric heat section into the air handler Be careful that the heating elements do not r...

Page 3: ...ied Thereisapatchplateoverthecircuitbreakeropening Remove the circuit breaker patch plate from the air handler access panel See figure 4 3 Replace the air handler access door 4 Choose the appropriatel...

Page 4: ...B29 5CB ECB29 6CB ECB29 8CB ECB29 9CB ECB29 10CB ECB29 12 5CB ECB29 15CB ECB29 20CB ECB29 25CB ECB29 30CB ECB29 10CB 3 Ph ECB29 15CB 3 Ph ECB29 20CB 3 Ph ECB29 25CB 3 Ph SIDE OF UNIT DISCARD BREAK AT...

Page 5: ...ith 1 1 2 inch trade size 1 31 32 inch diameter conduit A conduit reducer washer has been provided if you are installing a smaller sized conduit For single point power supply refer to the nameplate on...

Page 6: ...ERMOSTAT IS USED CONNECT SECOND STAGE NALS R AND W2 FACTORY INSTALLED JUMPER L3 CONNECTION USED ON Y VOLTAGE 3 PHASE ELECTRIC HEATERS ONLY FIGURE 11 Typical Field Wiring Cooling Application with Elect...

Page 7: ...PHASE ELECTRIC HEATERS ONLY STATS Y2 USED ONLY WHEN TWO SPEED COMPRESSOR IS USED HP21 COMMON USED ONLY ON SOME THERMOSTATS USING SERVICE LIGHT OPTION S54 WITH SOME ELECTRONIC THERMOSTATS MAY REQUIRE...

Page 8: ...Page 8 Unit Field Wiring Diagrams FIGURE 13 Typical Unit Wiring Diagram Air Handlers with Constant Torque Motors P Voltage 208 230V 1 phase 60Hz...

Page 9: ...Page 9 FIGURE 14 Typical Unit Diagram Air Handlers with PSC Non Communicating Motors P Voltage 208 230V 1 phase 60Hz...

Page 10: ...Page 10 FIGURE 15 Typical Unit Diagram Air Handlers with Constant Torque Motors G Voltage 460V 3 Phase 60Hz...

Page 11: ...4 01 ECB29 8 P 537816 01 ECB29 10 P 537770 02 ECB29 5CB P 537764 01 ECB29 6CB P 537764 01 ECB29 8CB P 537816 01 ECB29 9CB P 537770 02 ECB29 10CB P 537770 02 ECB29 12 5CB P 537787 02 ECB29 15CB P 53778...

Reviews: