Heat Section Installation 

Before installing the electric heat section, check the unit 

rating plate to ensure that the unit meets the job require-

ments, that proper electrical power is available, and that 

proper duct clearances are maintained.

KNOCK OUT EXTENDED WIDTH WHEN USING 

20KW OR 25KW ELECTRIC HEAT

FIGURE 1. Air Handler Electric Heat Knockouts

NOTE

 – 

It is easier to install the electric heat section in-

side the air handler unit before the unit is set and the ple-

num is attached.

1 - 

 Shut off all power to the air handler. More than one 

disconnect may be required. 

2 -  Remove air handler access panel. 
3 -   Remove the electric heat knockout from the air 

handler vestibule panel to accommodate the heater 

being used. Remove the extended width knockout 

to allow for installation of 20kW or 25kW heater (see 

figure 1). 

4 -   Slide the electric heat section into the air handler. 

Be careful that the heating elements do not rub 

against the sheet metal opening when they slide 

into the air handler. The hole(s) on each side of the 

heater line up with holes in the air handler control 

box. Secure the electric heater into place with the 

screws that are provided in the bag assembly. 

Cabinet Modifications for 460 Volt 3 Ton Models

Modifications  are  necessary  when  an  ECB29-10F-G  / 

15F-G volt age (460 volt) electric heat section is installed 

in a 460 volt, 3 ton air handler (see figure 2). 

ISSUE:

SOLUTION:

Remove the tabs identified below.

Tabs restricting electric

heat section installation.

Tabs on a 460 volt, 3 ton air handler prevent proper installation of the ECB29-10F-G / 15F-G voltage (460 volt)

electric heat section.

FIGURE 2

. Cabinet Modifications 

Summary of Contents for ECB29 Series

Page 1: ...ing Replace all parts and panels before operating Failure to do so can result in death or electrical shock Electric Heat Section The ECB29 series electric heat section provides field in stalled electr...

Page 2: ...ed Remove the extended width knockout to allow for installation of 20kW or 25kW heater see figure 1 4 Slide the electric heat section into the air handler Be careful that the heating elements do not r...

Page 3: ...ied Thereisapatchplateoverthecircuitbreakeropening Remove the circuit breaker patch plate from the air handler access panel See figure 4 3 Replace the air handler access door 4 Choose the appropriatel...

Page 4: ...B29 5CB ECB29 6CB ECB29 8CB ECB29 9CB ECB29 10CB ECB29 12 5CB ECB29 15CB ECB29 20CB ECB29 25CB ECB29 30CB ECB29 10CB 3 Ph ECB29 15CB 3 Ph ECB29 20CB 3 Ph ECB29 25CB 3 Ph SIDE OF UNIT DISCARD BREAK AT...

Page 5: ...ith 1 1 2 inch trade size 1 31 32 inch diameter conduit A conduit reducer washer has been provided if you are installing a smaller sized conduit For single point power supply refer to the nameplate on...

Page 6: ...ERMOSTAT IS USED CONNECT SECOND STAGE NALS R AND W2 FACTORY INSTALLED JUMPER L3 CONNECTION USED ON Y VOLTAGE 3 PHASE ELECTRIC HEATERS ONLY FIGURE 11 Typical Field Wiring Cooling Application with Elect...

Page 7: ...PHASE ELECTRIC HEATERS ONLY STATS Y2 USED ONLY WHEN TWO SPEED COMPRESSOR IS USED HP21 COMMON USED ONLY ON SOME THERMOSTATS USING SERVICE LIGHT OPTION S54 WITH SOME ELECTRONIC THERMOSTATS MAY REQUIRE...

Page 8: ...Page 8 Unit Field Wiring Diagrams FIGURE 13 Typical Unit Wiring Diagram Air Handlers with Constant Torque Motors P Voltage 208 230V 1 phase 60Hz...

Page 9: ...Page 9 FIGURE 14 Typical Unit Diagram Air Handlers with PSC Non Communicating Motors P Voltage 208 230V 1 phase 60Hz...

Page 10: ...Page 10 FIGURE 15 Typical Unit Diagram Air Handlers with Constant Torque Motors G Voltage 460V 3 Phase 60Hz...

Page 11: ...4 01 ECB29 8 P 537816 01 ECB29 10 P 537770 02 ECB29 5CB P 537764 01 ECB29 6CB P 537764 01 ECB29 8CB P 537816 01 ECB29 9CB P 537770 02 ECB29 10CB P 537770 02 ECB29 12 5CB P 537787 02 ECB29 15CB P 53778...

Reviews: