background image

Page 8

STEP 2 -- ELECTRICAL (Continued) -- Field Control Wiring

The following two illustrations provide examples of control wiring connections when using a non-communicating thermostat.
For examples of control wiring in complete- or partial-communicating systems, see the iComfort

®

-enabled thermostat

Quick Start Guide

 which is provided with the thermostat.

Y1

O

R

W1

G

D

R

Y1

L

C

C

B

Y2

Y2

i−

W

O

i+

DS

L

T

T

W2

H

W3

H

O

C

L

Y2

DS

DH

G

R

Y1

W2

W1

1

2

5

6

Air Hander Control

ComfortSense

[

 7000 Thermostats

 Catalog # Y0349 or Y2081

Single−Stage

Heat Pump Control

On−board link

Low voltage thermostat 
wiring

Flat metal jumper

4

3

1. Thermostat 

T

 terminals are used for outdoor sensor input. Sensor provides input for thermostat's outdoor

temperature display (optional).

2.

R

 to 

connection is required for this model only when used with the ComfortSense

® 

7000 thermostat - (catalog

number Y0349). Resistor Kit (catalog number 47W97) is required and must be ordered separately.

3. Air handler control ships from factory with metal jumpers installed across 

W1

W2 

and 

W3

. For single-stage electric

heat, do not remove factory-installed metal jumper.

4. Air handler control ships from factory with metal jumpers installed across 

W1

W2 

and 

W3

. For two-stage electric

heat, remove factory-installed metal jumper between 

W1 

and

 W2. 

Then,

 

connect thermostat wire between the air

handler control's 

W2 

and the thermostat's 

W2 

terminal.

5. Cut on-board link (clippable wire) from 

R-O HEAT PUMP

 for heat pump applications.

6. Cut on-board link (clippable wire) 

DS-R

 for Humiditrol

® 

or Harmony III

 applications. This will slow the indoor blower

motor to the lowest speed setting. See air handler installation instruction or product specification bulletin for lowest
fan speed information.

FIGURE 8

Summary of Contents for Dave Lennox Signature XC17

Page 1: ...rsonal inju ry or loss of life Installation and service must be performed by a licensed professional installer or equivalent or service agency CAUTION Before attempting to perform any service or maint...

Page 2: ...1 2 1003 35 1 2 902 18 1 2 470 8 203 1 25 4 7 16 113 LIQUID LINE INLET VAPOR LINE INLET ELECTRICAL INLETS BASE WITH ELONGATED LEGS SIDE VIEW ACCESS VIEW DISCHARGE AIR 37 940 024 AND 030 41 1041 036 A...

Page 3: ...ts from dryers water heaters and furnaces should be directed away from the outdoor unit Prolonged exposure to exhaust gases and the chemicals contained within them may cause condensation to form on th...

Page 4: ...Size barrier at least the same height and width as out door unit Install barrier 24 inches 610 mm from the sides of the unit in the direction of prevailing winds 24 610 WIND BARRIER PREVAILING WINTER...

Page 5: ...rs before unit start up to pre vent compressor damage as a result of slugging CAUTION ELECTROSTATIC DISCHARGE ESD Precautions and Procedures Electrostatic discharge can affect electronic components Ta...

Page 6: ...t wires between the thermostat and the furnace air han dler control and four wires between the outdoor unit and the furnace air handler control When a thermostat cable with more than four wires is use...

Page 7: ...ault setting is OFF Note If the jumper is miss ing the default is OFF 2 Defrost Auto is set to OFF Defrost will run and terminate based on J1 setting 3 Defrost Auto is set to ON Defrost termination se...

Page 8: ...is required for this model only when used with the ComfortSense 7000 thermostat catalog number Y0349 Resistor Kit catalog number 47W97 is required and must be ordered separately 3 Air handler control...

Page 9: ...alog number 47W97 is required and must be ordered separately 3 Cut on board link W951 clippable wire from R O HEAT PUMP for heat pump applications 4 Cut on board link clippable wire DS R for Humiditro...

Page 10: ...s are used in Lennox units charged with HFC 410A refrigerant Residual mineral oil can act as an insulator preventing proper heat transfer It can also clog the expansion device and reduce sys tem perfo...

Page 11: ...e care not to twist or damage distributor tubes during this pro cess 4 Remove and discard fixed orifice valve stem assembly if present and Teflon washer as illustrated above 5 Use a field provided fit...

Page 12: ...ogen flow will have an exit point NITROGEN HIGH LOW B A C PIPING PANEL REMOVAL PREPARING LINE SET CAP AND CORE REMOVAL Remove piping panel to access service valves Cut ends of the refrigerant lines sq...

Page 13: ...ditionalwater saturated cloths under the valve body to protect the base paint 4FLOW NITROGEN Flow regulated nitrogen at 1 to 2 psig through the refrigeration gauge set into the valve stem port connect...

Page 14: ...VALVE KITS AND APPLICATION INFORMATION A REMOVE THE FIELD PROVIDED FITTING THAT TEMPORARILY RECON NECTED THE LIQUID LINE TO THE INDOOR UNIT S DISTRIBUTOR ASSEM BLY B INSTALL ONE OF THE PROVIDED TEFLO...

Page 15: ...e cylinder of HFC 410A refrigerant to the center port of the manifold gauge set Open the valve on the HFC 410A cylinder vapor only B Open the high pressure side of the manifold to allow HFC 410A into...

Page 16: ...OW NITROGEN CONNECT GAUGE SET A B C D LINE SET AND INDOOR COIL NOTE Remove cores from service valves if not al ready done FIGURE 15 EVACUATE LINE SET AND INDOOR COIL The unit is shipped with a factory...

Page 17: ...gauge valve 1 to 2 psig in order to release the va cuum in the line set and indoor unit 9 Perform the following Close manifold gauge valves Shut off HFC 410A cylinder Slowly open the service valves Re...

Page 18: ...iary drain if installed Check the area around the outdoor unit monthly and re move any obstructions that may restrict airflow to the outdoor unit This would include grass clippings leaves or papers th...

Page 19: ...eplace air filters in indoor unit 3 Check the cleanliness of indoor blower and clean blower if necessary 4 Inspect the indoor coil drain pans and condensate drains for rust debris obstructions leaks o...

Page 20: ...tes START UP CHECKS Refrigerant Type Rated Load Amps Actual Amps Rated Volts Actual Volts Condenser Fan Full Load Amps Actual Amps COOLING MODE Vapor Pressure Liquid Pressure Supply Air Temperature Am...

Reviews: