background image

Page 11

SL18XP1 SERIES

STEP 4 -- REFRIGERANT PIPING -- Removing Existing Indoor Metering Device

SENSING

LINE

TEFLON

®

 RING

FIXED ORIFICE

BRASS NUT

LIQUID LINE ASSEMBLY

(INCLUDES STRAINER)

LIQUID LINE ORIFICE HOUSING

DISTRIBUTOR TUBES

DISTRIBUTOR

ASSEMBLY

REMOVE AND DISCARD

WHITE TEFLON

®

 SEAL

(IF PRESENT)

TYPICAL EXISTING FIXED ORIFICE
REMOVAL PROCEDURE 
(UNCASED COIL SHOWN)

TYPICAL EXISTING EXPANSION VALVE REMOVAL
PROCEDURE (UNCASED COIL SHOWN)

TWO-PIECE PATCH PLATE

(UNCASED COIL ONLY)

VAPOR

LINE

DISTRIBUTOR

ASSEMBLY

DISTRIBUTOR

TUBES

LIQUID

LINE

MALE EQUALIZER

LINE FITTING

EQUALIZER
LINE

CHECK

EXPANSION

VALVE

TEFLON®
RING

STUB END

TEFLON

®

RING

SENSING BULB

LIQUID LINE

ORIFICE

HOUSING

LIQUID LINE

ASSEMBLY WITH

BRASS NUT

LOW

HIGH

EXISTING

INDOOR

UNIT

GAUGE

MANIFOLD

CYLINDER CONTAINING
CLEAN HCFC-22* TO BE
USED FOR FLUSHING
(Positioned to deliver liquid
refrigerant)

LIQUID LINE SERVICE

VALVE

INLET

DISCHARGE

TANK
RETURN

CLOSED

OPENED

RECOVERY

CYLINDER

RECOVERY MACHINE

NEW

OUTDOOR

UNIT

VAPOR LINE

SERVICE VALVE

V

APOR

LIQUID

1

 A.

HCFC-22 cylinder with clean refrigerant* (positioned to deliver liquid
refrigerant) to the vapor service valve.

 B.

HCFC-22 gauge set (low side) to the liquid line valve.

 C.

HCFC-22 gauge set center port to inlet on the recovery machine with an
empty recovery tank connected to the gauge set.

 D.

Connect recovery tank to recovery machine per machine instructions.

CONNECT GAUGES AND EQUIPMENT FOR
FLUSHING PROCEDURE

A

B

C

D

OR

FLUSHING LINE SET

The line set and indoor unit coil must be flushed with at least the same
amount of clean refrigerant* that previously charged the system.
Check the charge in the flushing cylinder before proceeding.

1A

2

3

1B

1. On fully cased coils, remove the coil access and plumbing panels.

2. Remove any shipping clamps from the liquid line and distributor as­

sembly.

3. Using two wrenches, disconnect liquid line from liquid line orifice hous­

ing. Take care not to twist or damage distributor tubes during this pro­
cess.

4. Remove and discard fixed orifice, valve stem assembly (if present)

and Teflon

®

 washer as illustrated above.

5. Use a field-provided fitting to temporarily reconnect the liquid line to the

indoor unit's liquid line orifice housing.

1. On fully cased coils, remove the coil access and plumbing panels.

2. Remove any shipping clamps from the liquid line and distributor

assembly.

3. Disconnect the equalizer line from the expansion valve equalizer

line fitting on the vapor line.

4. Remove the vapor line sensing bulb.

5. Disconnect the liquid line from the expansion valve at the liquid line

assembly.

6. Disconnect the expansion valve from the liquid line orifice housing.

Take care not to twist or damage distributor tubes during this
process.

7. Remove and discard expansion valve and the two Teflon

®

 rings.

8. Use a field-provided fitting to temporarily reconnect the liquid line to

the indoor unit's liquid line orifice housing.

1. Set the recovery machine for liquid recovery and start the recovery

machine. Open the gauge set valves to allow the recovery
machine to pull a vacuum on the existing system line set and indoor
unit coil.

2. Position the cylinder of clean HCFC-22* for delivery of liquid

refrigerant and open its valve to allow liquid refrigerant to flow into
the system through the vapor line valve. Allow the refrigerant to
pass from the cylinder and through the line set and the indoor unit
coil before it enters the recovery machine.

3. After all of the liquid refrigerant has been recovered, switch the

recovery machine to vapor recovery so that all of the HCFC-22
vapor is recovered. Allow the recovery machine to pull the system
down to 0.

4. Close the valve on the inverted HCFC-22 cylinder and the gauge

set valves. Pump the remaining refrigerant out of the recovery
machine and turn the machine off.

*IMPORTANT - Clean refrigerant is any refrigerant in a system that has not had compressor burn out. If the system
has experienced burn out, it is recommended that the existing line set and indoor coil be replaced.

FIGURE 10

Summary of Contents for Dave Lennox Signature XC17

Page 1: ...rsonal inju ry or loss of life Installation and service must be performed by a licensed professional installer or equivalent or service agency CAUTION Before attempting to perform any service or maint...

Page 2: ...1 2 1003 35 1 2 902 18 1 2 470 8 203 1 25 4 7 16 113 LIQUID LINE INLET VAPOR LINE INLET ELECTRICAL INLETS BASE WITH ELONGATED LEGS SIDE VIEW ACCESS VIEW DISCHARGE AIR 37 940 024 AND 030 41 1041 036 A...

Page 3: ...ts from dryers water heaters and furnaces should be directed away from the outdoor unit Prolonged exposure to exhaust gases and the chemicals contained within them may cause condensation to form on th...

Page 4: ...Size barrier at least the same height and width as out door unit Install barrier 24 inches 610 mm from the sides of the unit in the direction of prevailing winds 24 610 WIND BARRIER PREVAILING WINTER...

Page 5: ...rs before unit start up to pre vent compressor damage as a result of slugging CAUTION ELECTROSTATIC DISCHARGE ESD Precautions and Procedures Electrostatic discharge can affect electronic components Ta...

Page 6: ...t wires between the thermostat and the furnace air han dler control and four wires between the outdoor unit and the furnace air handler control When a thermostat cable with more than four wires is use...

Page 7: ...ault setting is OFF Note If the jumper is miss ing the default is OFF 2 Defrost Auto is set to OFF Defrost will run and terminate based on J1 setting 3 Defrost Auto is set to ON Defrost termination se...

Page 8: ...is required for this model only when used with the ComfortSense 7000 thermostat catalog number Y0349 Resistor Kit catalog number 47W97 is required and must be ordered separately 3 Air handler control...

Page 9: ...alog number 47W97 is required and must be ordered separately 3 Cut on board link W951 clippable wire from R O HEAT PUMP for heat pump applications 4 Cut on board link clippable wire DS R for Humiditro...

Page 10: ...s are used in Lennox units charged with HFC 410A refrigerant Residual mineral oil can act as an insulator preventing proper heat transfer It can also clog the expansion device and reduce sys tem perfo...

Page 11: ...e care not to twist or damage distributor tubes during this pro cess 4 Remove and discard fixed orifice valve stem assembly if present and Teflon washer as illustrated above 5 Use a field provided fit...

Page 12: ...ogen flow will have an exit point NITROGEN HIGH LOW B A C PIPING PANEL REMOVAL PREPARING LINE SET CAP AND CORE REMOVAL Remove piping panel to access service valves Cut ends of the refrigerant lines sq...

Page 13: ...ditionalwater saturated cloths under the valve body to protect the base paint 4FLOW NITROGEN Flow regulated nitrogen at 1 to 2 psig through the refrigeration gauge set into the valve stem port connect...

Page 14: ...VALVE KITS AND APPLICATION INFORMATION A REMOVE THE FIELD PROVIDED FITTING THAT TEMPORARILY RECON NECTED THE LIQUID LINE TO THE INDOOR UNIT S DISTRIBUTOR ASSEM BLY B INSTALL ONE OF THE PROVIDED TEFLO...

Page 15: ...e cylinder of HFC 410A refrigerant to the center port of the manifold gauge set Open the valve on the HFC 410A cylinder vapor only B Open the high pressure side of the manifold to allow HFC 410A into...

Page 16: ...OW NITROGEN CONNECT GAUGE SET A B C D LINE SET AND INDOOR COIL NOTE Remove cores from service valves if not al ready done FIGURE 15 EVACUATE LINE SET AND INDOOR COIL The unit is shipped with a factory...

Page 17: ...gauge valve 1 to 2 psig in order to release the va cuum in the line set and indoor unit 9 Perform the following Close manifold gauge valves Shut off HFC 410A cylinder Slowly open the service valves Re...

Page 18: ...iary drain if installed Check the area around the outdoor unit monthly and re move any obstructions that may restrict airflow to the outdoor unit This would include grass clippings leaves or papers th...

Page 19: ...eplace air filters in indoor unit 3 Check the cleanliness of indoor blower and clean blower if necessary 4 Inspect the indoor coil drain pans and condensate drains for rust debris obstructions leaks o...

Page 20: ...tes START UP CHECKS Refrigerant Type Rated Load Amps Actual Amps Rated Volts Actual Volts Condenser Fan Full Load Amps Actual Amps COOLING MODE Vapor Pressure Liquid Pressure Supply Air Temperature Am...

Reviews: