THIS MANUAL MUST BE LEFT WITH THE

HOMEOWNER FOR FUTURE REFERENCE

General

This SL18XP1 outdoor heat pump with 

all-aluminum coil

is designed for use with HFC-410A refrigerant only. This
unit must be installed with an approved indoor air handler
or coil. See the Lennox SL18XP1 Product Specifications
bulletin (EHB) for matching indoor components.
These instructions are intended as a general guide and do
not supersede local codes in any way. Consult authorities
having jurisdiction before installation.

NOTICE !

For more in-depth information, consult the Installa­
tion and Service Procedures manual, available as
Corp.1406-L10 on LennoxPROS.com or through the
Technical Support department at 800-453-6669.

INSTALLATION
INSTRUCTIONS

Dave Lennox Signature

®

Collection SL18XP1 System

HEAT PUMPS
507468-01
7/2018

WARNING

Improper installation, adjustment, alteration, service or
maintenance can cause property damage, personal inju­
ry or loss of life.

Installation and service must be performed by a licensed
professional installer (or equivalent) or service agency.

CAUTION

Before attempting to perform any service or mainte­
nance, turn the electrical power to unit OFF at discon­
nect switch.

STEP 1 -- SETTING THE UNIT -- Clearances

ÍÍÍÍÍÍÍÍÍÍÍÍÍ

ÍÍÍÍÍÍÍÍÍÍÍÍÍ

ÍÍÍÍÍÍÍÍÍÍÍÍÍ

ÍÍÍÍÍÍÍÍÍÍÍÍÍ

ÍÍÍÍÍÍÍÍÍÍÍÍÍ

ÍÍÍÍÍÍÍÍÍÍÍÍÍ

ÍÍÍÍÍÍÍÍÍÍÍÍÍ

ÍÍÍÍÍÍÍÍÍÍÍÍÍ

ÍÍÍÍÍÍÍÍÍÍÍÍÍ

ÍÍÍÍÍÍÍÍÍÍÍÍÍ

ÍÍÍÍÍÍÍÍÍÍÍÍÍ

ÍÍÍÍÍÍÍÍÍÍÍÍÍ

ÍÍÍÍÍÍÍÍÍÍÍÍÍ

See

NOTES

See NOTES

NOTES:

Service clearance of 30 in. must be maintained on one of the sides
adjacent to the control box. 

Clearance to one of the other three sides must be 36 in.

Clearance to one of the remaining two sides may be 12 in. and the
final side may be 6 in.

A clearance of 24 in. must be maintained between two units.

48 in. clearance required on top of unit.

See

NOTES

See NOTES

Control

Box

NOTICE: 

Specific applications may require adjustment of the listed installation clearances to provide protection for

the unit from physical damage or to avoid conditions which limit operating efficiency. (Example: Clearances may
have to be increased to prevent snow or ice from falling on the top of the unit. Additional clearances may also be
required to prevent air recirculation when the unit is installed under a deck or in another tight space.)

FIGURE 1

Summary of Contents for Dave Lennox Signature XC17

Page 1: ...rsonal inju ry or loss of life Installation and service must be performed by a licensed professional installer or equivalent or service agency CAUTION Before attempting to perform any service or maint...

Page 2: ...1 2 1003 35 1 2 902 18 1 2 470 8 203 1 25 4 7 16 113 LIQUID LINE INLET VAPOR LINE INLET ELECTRICAL INLETS BASE WITH ELONGATED LEGS SIDE VIEW ACCESS VIEW DISCHARGE AIR 37 940 024 AND 030 41 1041 036 A...

Page 3: ...ts from dryers water heaters and furnaces should be directed away from the outdoor unit Prolonged exposure to exhaust gases and the chemicals contained within them may cause condensation to form on th...

Page 4: ...Size barrier at least the same height and width as out door unit Install barrier 24 inches 610 mm from the sides of the unit in the direction of prevailing winds 24 610 WIND BARRIER PREVAILING WINTER...

Page 5: ...rs before unit start up to pre vent compressor damage as a result of slugging CAUTION ELECTROSTATIC DISCHARGE ESD Precautions and Procedures Electrostatic discharge can affect electronic components Ta...

Page 6: ...t wires between the thermostat and the furnace air han dler control and four wires between the outdoor unit and the furnace air handler control When a thermostat cable with more than four wires is use...

Page 7: ...ault setting is OFF Note If the jumper is miss ing the default is OFF 2 Defrost Auto is set to OFF Defrost will run and terminate based on J1 setting 3 Defrost Auto is set to ON Defrost termination se...

Page 8: ...is required for this model only when used with the ComfortSense 7000 thermostat catalog number Y0349 Resistor Kit catalog number 47W97 is required and must be ordered separately 3 Air handler control...

Page 9: ...alog number 47W97 is required and must be ordered separately 3 Cut on board link W951 clippable wire from R O HEAT PUMP for heat pump applications 4 Cut on board link clippable wire DS R for Humiditro...

Page 10: ...s are used in Lennox units charged with HFC 410A refrigerant Residual mineral oil can act as an insulator preventing proper heat transfer It can also clog the expansion device and reduce sys tem perfo...

Page 11: ...e care not to twist or damage distributor tubes during this pro cess 4 Remove and discard fixed orifice valve stem assembly if present and Teflon washer as illustrated above 5 Use a field provided fit...

Page 12: ...ogen flow will have an exit point NITROGEN HIGH LOW B A C PIPING PANEL REMOVAL PREPARING LINE SET CAP AND CORE REMOVAL Remove piping panel to access service valves Cut ends of the refrigerant lines sq...

Page 13: ...ditionalwater saturated cloths under the valve body to protect the base paint 4FLOW NITROGEN Flow regulated nitrogen at 1 to 2 psig through the refrigeration gauge set into the valve stem port connect...

Page 14: ...VALVE KITS AND APPLICATION INFORMATION A REMOVE THE FIELD PROVIDED FITTING THAT TEMPORARILY RECON NECTED THE LIQUID LINE TO THE INDOOR UNIT S DISTRIBUTOR ASSEM BLY B INSTALL ONE OF THE PROVIDED TEFLO...

Page 15: ...e cylinder of HFC 410A refrigerant to the center port of the manifold gauge set Open the valve on the HFC 410A cylinder vapor only B Open the high pressure side of the manifold to allow HFC 410A into...

Page 16: ...OW NITROGEN CONNECT GAUGE SET A B C D LINE SET AND INDOOR COIL NOTE Remove cores from service valves if not al ready done FIGURE 15 EVACUATE LINE SET AND INDOOR COIL The unit is shipped with a factory...

Page 17: ...gauge valve 1 to 2 psig in order to release the va cuum in the line set and indoor unit 9 Perform the following Close manifold gauge valves Shut off HFC 410A cylinder Slowly open the service valves Re...

Page 18: ...iary drain if installed Check the area around the outdoor unit monthly and re move any obstructions that may restrict airflow to the outdoor unit This would include grass clippings leaves or papers th...

Page 19: ...eplace air filters in indoor unit 3 Check the cleanliness of indoor blower and clean blower if necessary 4 Inspect the indoor coil drain pans and condensate drains for rust debris obstructions leaks o...

Page 20: ...tes START UP CHECKS Refrigerant Type Rated Load Amps Actual Amps Rated Volts Actual Volts Condenser Fan Full Load Amps Actual Amps COOLING MODE Vapor Pressure Liquid Pressure Supply Air Temperature Am...