Page 26
IMPORTANT
When combining the furnace and evaporator coil
drains together, the A/C condensate drain outlet must
be vented to relieve pressure in order for the furnace
pressure switch to operate properly.
HorizontalFurnace4” Min. to 5” Max.above
condensatedrain connection)
FurnaceCondensate
DrainConnection
From Evaporator Coil
Optional
Condensate Trap With Optional Overflow Switch
FIGURE 38
Furnace with Evaporator
Coil Using a Common Drain
(1” min. to 2” Max.above
condensatedrain connection)
Condensate
DrainConnection
Evaporator drain
line required
(Trap at coil is optional)
FIGURE 39
Furnace with Evaporator Coil Using a Common Drain
(Unit shown in horizontal left−hand discharge position)
Condensate Drain
Connection
(4” min. to 5” Max.above
condensatedrain connection)
5’ max.
PVC Pipe Only
4”min
5”max
Evaporator
Coil
Drain Pan
Piping from furnace and evaporator coil must slope
down a minimum 1/4” per ft. toward trap
(Trap at coil is optional)
Figure 40