background image

Page 8

506071−01 02/08

If the Fahrenheit/Celsius display must be changed, use a
plastic, non−conductive tool to push the dip switch to the
right position (see figure 18).

F/C (Fahrenheit/Celsius) switch
shown in Celsius position

1
2
3
4
5
6
7

PLUG IN (Use Care To Avoid Bending Prongs.)

Figure 18. Changing Fahrenheit/Celsius Setting

Indoor Temperature Measurement Range

Measurement Scale

Fahrenheit

. . . . . . . . . . . . . . . . . . . . 

Measurement Range

35°F to 99°F

. . . . . . . . . . . . . . . . . . 

Measurement Resolution

0.5°F

. . . . . . . . . . . . . . . . . . . . . 

Measurement Accuracy

+/−1°F

. . . . . . . . . . . . . . . . . . . . . . 

Field Offset

via DIP switches to +/−3°F

. . . . . . . . . . . . . . 

Sampling Method: temperature measurements sampled
every 15 seconds. Displayed temperature is the average
of the last four measurements.

Outdoor Temperature Measurement Range

Measurement Scale

Fahrenheit

. . . . . . . . . . . . . . . . . . . . 

Measurement Range

−22°F to 122°F

. . . . . . . . . . . . . . . . 

Measurement Resolution

1°F

. . . . . . . . . . . . . . . . . . . . . . . 

Measurement Accuracy

+/−2°F

. . . . . . . . . . . . . . . . . . . . . . 

Temperature Setpoint Range

Setting range

50°F (10°C) to 90°F (32°C)

. . . . . . . . . . . . 

Setting resolution

1°F (1°C)

. . . . . . . . . . . . . . . . . . . . . . . . . 

Smart Setback Recovery (via DIP switch #6)

Smart Setback Recovery (SSR) affects the way the ther-
mostat responds to program events. If SSR is disabled, the
thermostat will react to a program event at the time the
event occurs. However, if SSR is enabled, the thermostat
will react to a program event before the event occurs such
that the desired temperature is reached at the time of the
event, not after.

Autochangeover Deadband Selection (via DIP
switch #7)

Autochangeover deadband can be set to 4

or 6 degrees. When autochangeover is enabled (via the
AUTO button), the thermostat will automatically change
over from heating to cooling and vice versa, to keep the
room temperature in between the heating and cooling set-
points. The deadband is the minimum difference between
the heating and cooling setpoints.

Fan Control

AUTO or ON modes, gas or electric heat

compatible via DIP switches (also see Thermostat Output
section).

I/O Relays

All thermostat relays are latching type to

minimize power consumption.

Equipment Protection Timers

Minimum Compressor OFF time

5 minutes

. . . . . . . . . . . 

Minimum Compressor ON time

4 minutes

. . . . . . . . . . . . 

Minimum Furnace ON time

3 minutes

. . . . . . . . . . . . . . . 

Minimum furnace cycle time (elapsed time between any
furnace activation & next furnace activation)

6 minutes

Minimum elapsed time between any compressor activa-
tion and the next compressor activation

6 minutes

. . . . 

NOTE − All protection timers (except the compressor OFF
timer) can be over−ridden if a heating or cooling demand is
initiated or terminated using the UP, DOWN, HEAT, or
COOL buttons.

Equipment Protection Override

Both the minimum

compressor OFF timer and the minimum equipment cycle
timer can be over−ridden by pressing and holding either the
HEAT or COOL button down for 4 seconds.

Over Temperature Protection

Thermal-mechanical

switch opens W1 and W2 at 93°F+/−6°F.

Filter Reminder

Settings of Off, 1, 3, 6 or 12 (months

of fan run time) are available. When programmed time has
elapsed, a FILTER indicator is displayed.

Maintenance Reminder

Settings of Off, 6 or 12

(months of chronological time) are available. When pro-
grammed time has elapsed, a maintenance indicator
MAINTENANCE" is displayed.

Service Reminder

The SERVICE indicator is dis-

played only under the following conditions:

S

if the thermostat Y1 terminal has been activated with
24VAC for at least 5 minutes, AND the L terminal is
shorted to the R terminal;

OR

S

if the thermostat Y1 terminal has been activated with
24VAC for at least 5 minutes, AND the L terminal is
shorted to the C terminal.

Power Loss/Recovery

Thermostat memory is re-

tained for a minimum of 24 hours during a power loss (in-
cludes retention of clock setting, program information,
HOLD status, programmed temperature setpoint, heat/
cool and fan mode settings, filter reminder status, mainte-
nance reminder status, and equipment protection timers).
After 24 hours of power loss, programmed settings will be
lost and replaced with default settings.

IMPORTANT

Power must be applied for at least six consecutive
hours prior to a power loss in order for memory to
be retained for the specified time.

LCD Backlight

Activated for 30 seconds when any

button is pressed.

NOTE − During an electrical storm or similar disturbance,
the backlight may activate for a few seconds. This is nor-
mal and will no longer occur after the electrical disturbance
has passed.

Thermostat Operating Conditions

35°F to 105°F


 

5% to 90% RH

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

Thermostat Storage Conditions

−40°F to 185°F

. . 

5% to 95% RH

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

Summary of Contents for ComfortSense L3722C

Page 1: ...rogram 6 FAN Controlling Fan Operation 5 Displaying Outside Temperature 6 SETTINGS Filter Maintenance Reminder 6 Service Indicator 6 Thermostat RESET 6 Removing Installing Thermostat 7 Default Thermostat Settings 7 Thermostat Output Table 7 Technical Specifications 7 General These instructions are intended as a general guide and do not supersede local codes in any way Consult authorities having ju...

Page 2: ...seconds or the HOME screen will re turn Heat Prog Fan Settings Cool Day Time Hold Enter DOOR OPEN Auto Copy Outside Figure 3 Thermostat Buttons When an Arrow HOLD HEAT or COOL button is pressed SETPOINT and the temperature setting appears for 15 seconds If desired start making changes within 15 sec onds or the HOME screen will return The backlight will turn off 15 seconds after the HOME screen rea...

Page 3: ...during a demand NOTE Heating equipment is activated for at least 3 min utes if no buttons are pressed during the demand interval COOL Using the Cool Mode Enabling and Disabling Cool Mode Use the COOL button to enable or disable cool mode as desired If the thermostat is in heat or off mode cool mode is enabled when the COOL button is pressed This is indi cated by COOL on the right side of the displ...

Page 4: ...oint is displayed to the right of the actual room temperature Each button press adjusts the setpoint up or down by 1 degree After the desired setpoint is reached the HOME screen will reappear after about 15 seconds Permanent Hold Mode At any time the program is running from the HOME screen set a permanent hold program override by press ing the HOLD button see figure 9 The thermostat now functions ...

Page 5: ...g to repeat the same program for other days A Press the PROG button then press the COPY button The display clears the screen except for Copy from MO with MO flashing Press the COPY button again to copy Monday s program B The display changes to Copy to MO Use the ar row buttons to scroll to the desired day where you want the same program as Monday Press the COPY button C Repeat steps A and B for as...

Page 6: ...onds after the final arrow button press OR press the ENTER button at any time to store any changes and exit to the HOME screen After either programmed interval has elapsed the remind er will be displayed as shown in figure 17 COOL OFF AUTO EMG HEAT I0 26 PROG A B C D HOLD FAN ON AUTO FILTER SERVICE MAINTENANCE 76 ROOM MO AM PM COOL OFF AUTO EMG HEAT FAN ON AUTO FILTER SERVICE MAINTENANCE 76 Servic...

Page 7: ... is above setpoint 0 5F but below setpoint 1 5F AND 30 minute upstage timer HAS NOT expired With a LARGE cool demand temperature is above setpoint 1 5F OR 30 minute upstage timer HAS expired Default Thermostat Settings Default thermostat settings are in table 3 and the default program is shown in table 4 Table 3 Default Thermostat Settings Mode Heat Perm Hold Heat Setpoint Perm Hold 70 F or 21 C C...

Page 8: ...me elapsed time between any furnace activation next furnace activation 6 minutes Minimum elapsed time between any compressor activa tion and the next compressor activation 6 minutes NOTE All protection timers except the compressor OFF timer can be over ridden if a heating or cooling demand is initiated or terminated using the UP DOWN HEAT or COOL buttons Equipment Protection Override Both the mini...

Reviews: