OPTIONS
Outdoor temp. ºC
DYNAMIC SET POINT
9ºC
25ºC
35ºC
12ºC
Set point ºC
-10ºC
differential
cooling
set point
starting
Dynamic
set point
Outdoor temp. ºC
38ºC
6ºC
12ºC
42ºC
Set point ºC
6ºC
differential
heating
set point
starting
Dynamic
set point
KP06 nº1
KP06 nº2
KP06 nº15
(. . . .)
(. . . .)
Gateways
EB 8
BA 8
EcoLean 8
EB 2
BA 2
EcoLean 2
EB 1
BA 1
EcoLean 1
BA: Bus Adapter
EB: Electrical Box
(. . . .)
EB 8
BA 8
EcoLean 8
EB 2
BA 2
EcoLean 2
EB 1
BA 1
EcoLean 1
(. . . .)
EB 8
BA 8
EcoLean 8
EB 2
BA 2
EcoLean 2
EB 1
BA 1
EcoLean 1
BMS CONNECTION
It is possible to connect the unit to a BMS system with a MODBUS protocol.
A communication adaptor is installed in the unit. With a GATEWAY, 8 units can be connected. It is possible to
achieve a net with 16 GATEWAYS. This net communicates with a BMS system through MODBUS protocol.
Parameters:
- Units with
Climatic
®
200:
H26 Serial output configuration 1= ModBus.
H44 Family serial address= 0.
H45 Device serial address= 0..7 (different for each one connected to the GATEWAY).
- Units with Climatic
®
400:
H48 Serial output configuration 1= ModBus.
H65 Family serial address= 0.
H66 Device serial address= 0..7 (different for each one connected to the GATEWAY).
COOLING MODE
When the outdoor temperature exceeds 35ºC, the
unit set point is the set value. The Dynamic set point
function starts when the temperature is below 35ºC.
The set point value increases below 35ºC, so for
25ºC (10ºC differential) the set point is 3ºC more
than the set value.
HEATING MODE
(only for heat pump units)
When the outdoor temperature is 6ºC the unit set
point is the set value. The Dynamic set point function
starts when the temperature exceeds 6ºC. The set
point value decreases above 6ºC, so for 12ºC (6ºC
differential) the set point is 4ºC less than the fixed
value.