background image

Page 5

CH35 SERIES

Refrigerant Line Connections

LINE SIZES

The refrigerant line sets should be sized according to the
recommendations given in the outdoor unit installation
instructions. See table 1 for sweat connection sizes. A
field-provided adapter may be required to match line set
connections.

Table 1. Refrigerant Line Connections

CH35

Model

Suction Line

Connection

Liquid Line

Connection

-18-2F
-24-2F
-30-2F
-36-2F

3/4 Inch

3/8 Inch

-42-2F
-48-2F
-51-2F
-60-2F

7/8 Inch

REPLACEMENT PARTS

If replacement parts are needed for the liquid line orifice
housing  or  assembly, order kit 69J46. The kit includes:

● 10 - Brass nuts for liquid line assemblies

● 20 - Teflon rings

● 10 - Liquid line orifice housings

● 10 - Liquid line assemblies

TEFLON RINGS (20)

BRASS NUTS (10)

LIQUID LINE ASSEMBLIES

(INCLUDES STRAINER) (10)

LIQUID LINE ORIFICE HOUSINGS (10)

LIQUID LINE

ASSEMBLY

COPPER
TUBE

PISTON
RETAINER

STRAINER

Figure 6. Liquid Line Orifice Kit (69J46)

Components

BRAZING GUIDELINES

Use a silver alloy brazing rod (5 or 6 percent silver alloy for
copper-to-copper connections or 45 percent silver alloy for
copper-to-brass or copper-to-steel connections).

Use AL822 Flux Cord Solder Stickers (Lennox catalog
number Y6331) for aluminum to aluminum joints.

Before making brazed connections, place a field-provided
heat shield, such as a wet rag, against the unit cabinet and
around the piping stubs. The heat shield must be in place
to prevent heat damage during brazing. See figure 7.

WATER-

SATURATED RAGS

PLACE A WET RAG AGAINST
COIL CABINET AND AROUND
THE SUCTION LINE
CONNECTION.
BRAZE CONNECTION. ALLOW
PIPE TO COOL BEFORE
REMOVING WET RAG.

1

2

Figure 7. Brazing Refrigerant Lines

SUCTION LINE CONNECTION

Use the following procedure to connect the suction line to
the indoor coil:

1. Remove rubber plug from the stubbed connection.
2. Position the properly sized refrigerant piping and make

the brazed connection following the brazing
guidelines.

3. Do not remove the water-saturated rags from the

cabinet and piping until the piping has cooled
completely.

Suction Line Equalizer Fitting

Remove the copper flare seat bonnet if present from the
male equalizer line fitting (see figure 8).

IMPORTANT

When removing the flare nut, ensure that the copper
flare seal bonnet is removed as illustrated in figure 8.

SUCTION LINE

FLARE NUT

REMOVE AND DISCARD
FLARE SEAL BONNET IF
PRESENT

MALE BRASS EQUALIZER
LINE FITTING

FLARE SEAL CAP

OR

Figure 8. Suction Line Male Equalizer Line Fitting

Modifications

LIQUID LINE CONNECTION

NOTE

 - Before the liquid line connections can be made,

the factory-provided refrigerant metering orifice must be
removed and a properly sized expansion valve must be
field-installed.

The system must include a properly matched expansion
valve which must be field-provided and installed. The
CH35 is shipped with a factory-installed refrigerant
metering orifice. 

The orifice must be removed BEFORE

a properly sized expansion valve is installed.

Fixed Orifice Removal

1. Remove any shipping clamps holding the liquid line

and distributor assembly.

Summary of Contents for CH35 Series

Page 1: ...ne Connections 5 Leak Testing Evacuating and Charging 6 Sealing Ducts 6 Condensate Drain Connection 6 Blower Speed Connection 7 Maintenance 8 General CH35 all aluminum coil horizontal evaporator coils...

Page 2: ...3 8 3 8 3 8 Condensate drain fpt in 3 4 3 4 3 4 3 4 3 4 Evaporator Coil Net face area sq ft 1 75 3 5 3 5 4 33 4 67 Tube diameter in 3 8 3 8 3 8 3 8 3 8 Number of rows 2 3 2 3 3 Fins per inch 18 14 19...

Page 3: ...d of pressure Installation WARNING Risk of explosion or fire Can cause injury or death Recover all refrigerant to relieve pressure before open ing the system Install the furnace or air handler accordi...

Page 4: ...LY AIR UNIT REAR TEST HOLE AIR FLOW FIELD FABRICATED INSULATED BLOCK OFF PLATE Figure 2 D Width Coil with C Width Furnace Top View SUPPLY AIR UNIT FRONT PLUMBING CONNECTIONS SUPPLY AIR UNIT REAR AIR F...

Page 5: ...eat damage during brazing See figure 7 WATER SATURATED RAGS PLACE A WET RAG AGAINST COIL CABINET AND AROUND THE SUCTION LINE CONNECTION BRAZE CONNECTION ALLOW PIPE TO COOL BEFORE REMOVING WET RAG 1 2...

Page 6: ...e coil cabinet flanges WARNING There must be an airtight seal between the bottom of the furnace and the return air plenum Use fiberglass sealing strips caulking or equivalent sealing method between th...

Page 7: ...EADING SECONDARY DRAIN PAN 2 51MM TRAP DEPTH P TRAP 49P66 REQUIRES A LARGER INSTALLATION SPACE THAN THE J TRAP 91P90 Figure 10 Typical Main and Overflow Drain Installations Blower Speed Connection Pro...

Page 8: ...his or any other maintenance turn off all power to the indoor unit at the main unit disconnect switch It is also recommended that you wear personal protective gear safety glasses and or a face shield...

Reviews: